By Kurnia · Published November 14, 2026 · Version 1 · 19 min read
Building lighting
light quantities, lamp types and LED drivers, recommended lighting levels, calculating the number of luminaires with the lumen method, flicker and glare, and maintenance
Staff in a hotel’s accounts department complain of headaches after the light panels in the back office were replaced with cheap LED panels: a lux meter reads about 280 lux on the desks, while the annex of Permenaker 5/2018 places long office work at 500 to 1,000 lux, and a phone camera shows moving dark bands. This chapter covers building lighting from the technician’s side: luminous flux, illuminance, efficacy, color temperature, and color rendering index; lamp types and LED drivers with L70 life; lighting levels from the annex of Permenaker 5/2018 and the British HSE guidance HSG38, with illuminance ratios between areas; the lumen method with utilization factor and maintenance factor; flicker and the stroboscopic effect according to the US DOE; glare and exclusion zones; and maintenance, measurement, and lamp disposal. Official workplace measurement, work on luminaires and their circuits, and work at height are stated as limits of authority.
A hotel’s accounts department works in a windowless back office, eight hours a day in front of paper and screens. After several light panels failed, the purchasing department replaced them with the cheapest LED panels available, and within two weeks three staff members complained of headaches and eyes that tired quickly. The technician who was called brought a lux meter and read about 280 lux on the desk surface. The annex of Permenaker 5/2018 places the work of accountants, bookkeepers, and long office work at 500 to 1,000 lux. When the technician pointed a phone camera at a new panel, the screen showed moving dark bands, while under the old panels the bands were absent. The room had two problems: too little light, and light that flickered more strongly than the eye can see directly.
Scope
This chapter covers artificial lighting in buildings from the building technician’s side: the light quantities printed on data sheets, lamp types and LED drivers, recommended lighting levels, the lumen method for checking the number of luminaires, flicker and glare, and routine maintenance and measurement. Official Indonesian figures are taken only from Permenaker 5/2018 (Minister of Manpower Regulation) on occupational safety and health (K3) of the work environment; as of November 2026, JDIH Kemnaker records its status as in force. Figures from the HSE guidance HSG38 are British data and are written as British data, while DOE figures are United States data.
Lighting installation design, the lumen method formula with room index, driver inrush and leakage current, luminaire IP codes, and the PUIL provisions for lighting are covered in Chapter 33 on lighting installations, and this chapter does not repeat them. The physics of light is in Chapter 20 · Physics, LEDs and photodiodes in Chapter 26 · Physics, harmonics from electronic loads in Chapter 10, indicator lights in Chapter 49, the eye, dark adaptation, and glare from the body’s side in Chapter 39 · Biology & Microbiology, and circuit grouping in Chapter 32. Emergency lighting and exit signs are covered in Chapter 106 on emergency lighting and exit signs.
Work outside the authority of a building technician without electrical competence: opening a luminaire that is still connected, replacing a driver, changing circuit connections, or installing new luminaires. That work is done only by an authorized electrician after the circuit has been isolated and verified de-energized. Workplace measurement whose results are used as evidence of compliance is carried out by K3 personnel in the work environment field; the technician’s lux meter reading is a preliminary check.
Light quantities on the data sheet
Luminous flux, , is all the light emitted by a source, expressed in lumens (lm). This figure is used to compare lamps, because watts state only the electrical power drawn. Illuminance, , is the flux falling per unit area of a surface, expressed in lux (lx), that is, lumens per square meter. Permenaker 5/2018 calls it light intensity and defines it as the average amount of light received by workers at every observation point, expressed in lux. The word average in that definition matters: one bright spot under a lamp does not represent the room.
Luminous efficacy is the ratio of luminous flux to electrical input power, in lumens per watt (lm/W). The efficacy of a luminaire is lower than the efficacy of the LED chips inside it, because the driver, lens, and housing also absorb or waste part of the energy and light.
Correlated color temperature (CCT), in kelvin, states the color appearance of the light: low values look yellowish and warm, high values look bluish and cool. Color rendering index (CRI) states how faithfully the colors of objects appear under that source compared with a reference source. DOE writes that in general a minimum CRI of 80 is recommended for interior lighting and a CRI of 90 or higher indicates excellent color fidelity, while warning that CRI is weak for saturated reds.
Lamp types and LED drivers
Older buildings still use incandescent and halogen lamps, most of whose power becomes heat, and fluorescent and discharge lamps, which need a ballast and some of which contain mercury. LEDs now give the highest efficacy of any light-source technology. United States data from the FEMP federal procurement program set a minimum efficacy of 140 lm/W for 2 by 4 ft commercial LED luminaires with an output of at least 3,000 lm, and its savings table compares that model with an older model of only 71 lm/W.
An LED driver is the electronic power supply inside a luminaire that converts the alternating line voltage into a controlled direct current for the LED chips. A constant-current driver holds the current through a string of LEDs at its rated value; a constant-voltage driver supplies a fixed direct voltage for LED modules or strips that carry their own current limiters. Because LED chips have almost no light persistence, the quality of the driver also determines how strongly the light flickers (see the flicker section below).
L70 life is the number of operating hours until a luminaire emits only 70 percent of its initial light. DOE writes that good-quality white LED products are expected to reach a useful life of 30,000 to 50,000 hours or more, but their electronics can fail first and their light color can shift before that limit. So when an LED luminaire goes dark suddenly, the cause is more likely the electronics than the LED chips.
HSE warns that when lamps are replaced, the lamp and its control gear must be electrically and physically compatible. An incompatible lamp may be damaged, or the lamp, luminaire, and control gear may overheat and create a fire risk. LED tubes that replace fluorescent tubes, for example, include types designed to keep the ballast and types that require the ballast to be removed and the luminaire rewired. The second type is wiring work, more than a lamp change, and is done by an authorized electrician following the manufacturer’s instructions.
Recommended lighting levels
Permenaker 5/2018 Article 16 requires lighting to be measured and controlled in workplaces, distinguishes natural and artificial lighting, and requires control when measured results do not meet the standard, so that the intensity suits the type of work. Article 18 allows artificial lighting when natural lighting does not meet the standard, provided that it does not cause excessive heat or disturb indoor air quality. The standard is in the annex, arranged by type of work, not by room name:
| No | Description and examples of work in the annex | Intensity (lux) |
|---|---|---|
| 1 | Emergency lighting | 5 |
| 2 | Yards and roads | 20 |
| 3 | Distinguishing coarse items; including corridors and stairs inside buildings that are always in use, warehouses for large and coarse items | 50 |
| 4 | Distinguishing small items at a glance; including engine and steam rooms, toilets and washrooms | 100 |
| 5 | Distinguishing small items somewhat precisely; including meat packing and rough inspection | 200 |
| 6 | Precise discrimination; including precise inspection and office work alternating between writing and reading | 300 |
| 7 | Fine items with medium contrast over long periods; including accountants, bookkeepers, and long office work | 500 to 1,000 |
| 8 | Very fine items with very poor contrast over long periods | 1,000 |
The figures in the table are the content of the annex; the word “including” marks examples chosen from a longer list. A hotel room is matched to the row whose visual task is closest. The accounts office belongs in row 7 because the work involves reading small figures for long periods, not row 6, even though both are offices.
The HSE guidance HSG38, which applies in Great Britain, gives two figures for each type of work: the average illuminance of the whole work area and the minimum measured illuminance at any point. For example, corridors and circulation routes 20 lux average and 5 lux minimum, kitchens 100 and 50 lux, offices 200 and 100 lux, and drawing offices and electronic component assembly 500 and 200 lux. HSE explains the reason: if only the average is used, some places may be much darker and endanger workers. These British figures are lower than several rows of the Permenaker annex, so in Indonesia the figures of the Permenaker annex are the reference; the concept of average and minimum is borrowed as a way of reading measured results.
HSG38 also limits the difference in brightness between adjacent areas. The ratio of the illuminance of the working area to the adjacent area is at most 5 to 1 when two working areas are adjacent without a barrier, and 10 to 1 when they are separated by a barrier but people move frequently between them; when the average figures and the ratio conflict, the higher value is used. The eye needs time to adjust when people step out of a bright room into a much darker corridor.
Calculating the number of luminaires with the lumen method
The lumen method calculates the average illuminance on the working plane from the total number of lumens that actually reach that plane. The form technicians use to check an existing room is:
where is the maintained average illuminance on the working plane (lux), the number of luminaires, the number of lamps or modules per luminaire, the flux of one lamp or module (lm), the area of the working plane (m²), the utilization factor, and the maintenance factor. If the data sheet gives only one flux value for the luminaire, and is the luminaire flux. For design, the formula is inverted to and the result is always rounded up.
The utilization factor (UF) is the fraction of lamp flux that reaches the working plane. American catalogs call it the coefficient of utilization (CU), and its value is read from the manufacturer’s photometric table according to the room shape and the reflectance of the ceiling, walls, and floor. The maintenance factor (MF) accounts for the drop in light as lamps age and dust settles on luminaires and room surfaces until the next cleaning. The room index and how to read the UF table are explained in Chapter 33 on lighting installations.
The method assumes that luminaires are arranged regularly. HSG38 writes that manufacturers publish a maximum spacing to mounting height ratio for each luminaire, and if that ratio is exceeded, the illuminance on the working plane becomes very uneven. So once is found, the technician checks the layout: the spacing between luminaires divided by the luminaire height above the working plane does not exceed the manufacturer’s figure.
Installed power is calculated from efficacy: the power of one luminaire equals its flux divided by its efficacy. Annual energy equals total power times operating hours.
Flicker and the stroboscopic effect
DOE calls the change in light output over time temporal light modulation and people’s response to it temporal light artifacts. Changes up to 80 Hz are called visible flicker; changes from about 80 Hz to 2,000 Hz make moving objects appear alternately bright and dim, which is called the stroboscopic effect; the phantom array effect appears from 80 Hz up to several thousand hertz when the eyes move.
LED chips have none of the light persistence of a hot filament or the phosphor of a fluorescent lamp. DOE writes that LEDs not paired with a good driver, or with a driver designed for a dimmer, can flicker as much as 100 percent, from fully on to off. On a 50 Hz supply, a simple driver that rectifies the full wave without enough energy storage produces a 100 Hz light ripple, twice the line frequency. That figure is above the limit of visible flicker, so people do not see it directly, but it falls in the range of the stroboscopic effect.
HSE states that flicker can cause discomfort and fatigue, and may even trigger epileptic seizures in some people, so it needs to be avoided; the stroboscopic effect is uncommon with modern systems, but where it occurs it can be dangerous because rotating machinery appears stationary or moving differently. Control measures in HSG38 include changing lamps near the end of their life, checking the supply circuit for faults, using high-frequency control gear, and supplying adjacent rows of luminaires from different phases. Moving dark bands on a phone camera screen indicate modulation, but do not measure its size.
Glare and reflections
HSE defines glare as the condition in which one part of the visual field is much brighter than the average brightness to which the eye is adapted. When vision is directly impaired, the condition is called disability glare; when vision is not impaired but there is discomfort, annoyance, or distraction, it is called discomfort glare. Veiling reflections are bright reflections that cover the detail of a task, for example the reflection of a window on a computer screen.
Glare most often occurs when lamps are directly visible near the line of sight. HSG38 gives exclusion zone angles above the horizontal line of sight: 10 degrees for fluorescent tubes viewed from the side, 20 degrees for phosphor-coated discharge lamps and frosted incandescent lamps, and 30 degrees for lamps that allow a direct view of the arc tube or filament. Bare lamps within that zone are moved away or shielded. That table was prepared before LEDs were in common use; bare LED chips that can be seen are very small and very bright, so the larger angle is the more cautious choice. For indirect lighting that uses the whole ceiling as the source, HSG38 limits the average illuminance on a ceiling of normal reflectance to 2,250 lux.
Maintenance, measurement, and lamp disposal
HSE writes that lamps and luminaires need to be kept clean and replaced because illuminance declines with age; how often depends on the type of luminaire and its environment, and a luminaire in a dirty place that is rarely reached needs replacing more often than the same luminaire in an ordinary office. Routine maintenance under HSG38 includes cleaning lamps and luminaires, repairing and replacing damaged or ineffective ones, maintaining emergency lighting, and disposing of lamps safely. Damaged luminaires may expose dangerous live parts.
The technician checks with a lux meter on the working plane, for example the desk surface, at several spread-out points, records the average and the lowest value, and compares them with the annex figure for that type of work. The lighting inspection form in Permenaker 5/2018 records the meter and its calibration date, the measuring point numbers, the natural or artificial light source, the window area, the measured result, the standard, and the type of measurement, general or local. Article 45 states that measurement and control of the work environment are carried out by licensed K3 personnel in the work environment field. The technician’s readings are used to find problems and judge the result of cleaning; the official report is still made by those K3 personnel.
Maintenance records hold the cleaning date, the readings before and after, the lamps or drivers replaced, and occupant complaints, so that a drop in light caused by dust can be separated from lamp aging. Fluorescent and discharge lamps contain mercury, and HSE asks that such lamps be disposed of in a well-ventilated area or outdoors with eye protection and gloves. Storing and handing over spent lamps as hazardous waste (B3) is covered in Chapter 35 · Water & Water Treatment on hazardous waste in hotels, laundries, and workshops. Access to high luminaires follows Chapter 10 · Safety on work at height.
Worked example
The figures in the examples below are practice figures, unless their origin is stated.
Example 1: hotel accounts office. A room 6 m by 5 m, m², is used for long office work, so the target is taken as the lower limit of row 7 of the annex, 500 lux. The ceiling is 2.8 m and the desk 0.75 m, so m and the room index is . Each luminaire holds two LED tubes of 2,000 lm each; the manufacturer’s table at gives a UF of 0.60, and MF is taken as 0.80.
The result is rounded up to 8 luminaires. The back check gives lux maintained and lux when new. A 2 by 4 layout gives spacings of 2.5 m and 1.5 m, with the largest spacing to mounting height ratio , which is compared with the manufacturer’s limit.
Example 2: efficacy and energy. Each luminaire in Example 1 draws 36 W, so its efficacy is lm/W, the total power is W, or W/m². With 3,000 operating hours a year, the energy is kWh. A replacement panel of 4,000 lm that meets the FEMP limit of 140 lm/W (United States data) draws W, and eight panels use kWh, a saving of 178.3 kWh or 20.6 percent. This saving is valid only if the UF of the new panel is the same; if it is lower, the number of luminaires is recalculated.
Example 3: the annex table and ratios between areas. The hotel’s technicians’ workshop is used for precise inspection, row 6, 300 lux, and its door opens onto a corridor that is always in use, row 3, 50 lux. The workshop and corridor are separated by a wall with a frequently used door, so the HSG38 limit of 10 to 1 applies: the corridor near the door needs at least lux. The annex figure of 50 lux is higher, so 50 lux is used, and the ratio is . If the workshop instead opened without a barrier into a spare parts store, the limit would be 5 to 1 and the store would need lux, above the 50 lux of row 3.
Example 4: inspection after 18 months. In the room of Example 1, the technician measures five desk points: 520, 480, 455, 430, and 465 lux. The average is lux and the lowest 430 lux, below 500 lux. Against 640 lux when new, the remaining light is , lower than the assumed MF of 0.80 (512 lux). After the luminaires and ceiling are cleaned, the average rises to 590 lux, or . Cleaning recovered 120 lux, while the remaining drop of , about 7.8 percent, is lamp aging. The conclusion is that the cleaning interval is shortened; the lamps do not yet need replacing.
Example 5: a mixer under 100 Hz light. A dough mixer in a hotel kitchen turns at 3,000 rpm, that is, revolutions per second. Under luminaires with a 100 Hz light ripple, each light pulse arrives after the mixer has turned revolution. A two-blade mixer that is symmetric through 180 degrees appears in the same position at every pulse, so it looks stationary or slowly turning while it is in fact turning fast. If three rows of luminaires are supplied from three different phases and are equally bright, the pulses from the three are shifted by one third of the ripple period, so the combined light pulses at Hz with much smaller modulation.
Example 6: glare zone in the office. Seated staff have their eyes 1.2 m above the floor, and the luminaires are mounted on a 2.8 m ceiling, so the height difference is 1.6 m. A luminaire appears inside the 30-degree zone above the horizontal line of sight when its horizontal distance is more than m. For the 20-degree zone the limit is m, and for 10 degrees m. In a 6 m room, staff facing along the room see the luminaires at the far end close to their line of sight, so those luminaires need a diffuser or louver.
Stop conditions
- A luminaire is broken, its cover has come off, its wiring is visible, or it smells burnt: do not touch it and do not leave it on; switch it off at the switch if safe, tag it, and hand it over to an authorized electrician.
- The lamp change would require removing a ballast, replacing a driver, or changing the luminaire connections: stop; that work is done only by an authorized electrician after the circuit has been isolated and verified de-energized according to Chapter 2 · Safety on verifying a safe state.
- The replacement lamp or tube is not listed as compatible with the luminaire and its control gear: do not fit it; ask the supplier or manufacturer through the engineering supervisor.
- Flicker visible to the eye, repeated on-off cycling, or humming in many luminaires at once: stop replacing lamps one by one and report to an authorized electrician, because the cause may be a supply or connection fault.
- A mixer, saw, or other rotating machine appears stationary or slowed under certain lamps: stop using the machine under those lamps until the lighting is replaced, and report to the kitchen supervisor and the technician.
- A fluorescent or discharge lamp has broken: keep people away, open ventilation, do not sweep it up dry with bare hands, and hand the fragments to the hazardous waste (B3) officer.
- The luminaire can be reached only from a tall ladder, scaffold, or above a machine: postpone until safe access has been prepared according to Chapter 10 · Safety on work at height.
- The measured result is below the annex figure and is needed as evidence of compliance: the technician does not declare a pass or fail; official measurement is handed to K3 personnel in the work environment field.
Common misinterpretations
Guess what’s wrong first, then open the explanation.
Common misconception
An 18 W lamp is certainly brighter than a 15 W lamp.
Why is it wrong?
Watts state electrical power. Brightness is read from lumens, and LED efficacy varies widely between products.
Common misconception
One point under a lamp already meets 500 lux, so the room passes.
Why is it wrong?
Permenaker defines intensity as the average over the observation points, and HSE asks that the lowest value be checked too. One bright point does not represent the desk in the corner.
Common misconception
If the eye does not see flicker, there is no flicker.
Why is it wrong?
A 100 Hz ripple is not seen directly, but it causes the stroboscopic effect and, in some people, headaches.
Common misconception
LEDs last 50,000 hours, so they need no maintenance.
Why is it wrong?
The L70 figure means the light has fallen to 70 percent, not that it stays bright. Dust still reduces the light, and the driver can fail first.
Common misconception
An office is an office, so everything is 300 lux.
Why is it wrong?
The annex arranges the standard by type of work. Office work that alternates is in row 6, while accounting and long office work are in row 7.
Links to other chapters
The lumen method formula, room index, driver inrush current, and luminaire IP codes are explained in Chapter 33 on lighting installations; this chapter uses that formula to check rooms already in service. Light waves and reflection are in Chapter 20 · Physics, how LEDs work in Chapter 26 · Physics, and harmonics from drivers in Chapter 10. Planned maintenance is in Chapter 81, and light and night work in Chapter 34 · Biology & Microbiology.
Exercises and worked solutions
The figures in the exercises are for practice.
Try to answer first, then open the worked solution.
A hotel restaurant of 10 m by 8 m needs 200 lux. The luminaires are 3,000 lm single-module units, UF 0.55, and MF 0.75. How many luminaires are needed, and what is the maintained illuminance?
Check my answer
See the worked solution
The area is 80 m², so , rounded up to 13 luminaires. The maintained illuminance is lux, slightly above the target, and rounding down to 12 would give less than 200 lux.
A 40 m² room has 10 luminaires each holding two 1,800 lm lamps, UF 0.50, and MF 0.80. What is the maintained illuminance, and for which row of the annex is the room adequate?
Check my answer
See the worked solution
lux. That value is adequate for row 6 of the annex, 300 lux, but does not reach the lower limit of row 7, 500 lux, so the room is not suitable for long office work without additional light.
A hotel replaces 40 spotlights of 800 lm rated at 11 W with lamps of 800 lm rated at 8 W, operating 4,000 hours a year. What is the efficacy of each lamp, and how much energy is saved per year?
Check my answer
See the worked solution
The efficacy of the old lamp is lm/W and of the new lamp lm/W. The saving is kWh a year with the same light, provided that the beam angles of the two lamps are also the same.
A staff member sees moving dark bands on a phone screen when photographing a new LED panel, but sees no flicker with the eye. What does this mean, and what does the technician do?
Check my answer
See the worked solution
Moving bands indicate that the panel’s light is modulated, probably a 100 Hz ripple from a simple driver, which is above the 80 Hz limit of visible flicker but falls in the range of the stroboscopic effect. The technician records the location and type of panel, asks about occupant complaints, and proposes replacement with luminaires whose drivers have low modulation through the engineering supervisor, rather than taking the driver apart personally.
A laundry washing room is lit to 300 lux and opens without a barrier into a folding room planned at 50 lux. Does that ratio meet HSG38, and what is the lowest value for the folding room?
Check my answer
See the worked solution
The ratio is , exceeding 5 to 1 for two working areas adjacent without a barrier. The folding room needs at least lux, and the annex figure for the folding task is checked as well.
An office with a 300 lux target is measured at five points: 250, 240, 230, 260, and 220 lux. After cleaning, the average is 285 lux. What is the conclusion?
Check my answer
See the worked solution
The initial average is lux, that is, 80 percent of the target, and after cleaning 285 lux or 95 percent. Cleaning helped, but the remaining shortfall comes from lamp aging or a number of luminaires that is simply too low, so the technician proposes replacing lamps or adding luminaires and requests a new measurement.
References
External sources
- Peraturan Menteri Ketenagakerjaan Nomor 5 Tahun 2018 tentang Keselamatan dan Kesehatan Kerja Lingkungan Kerjajdih.kemnaker.go.id
- Lighting at work (HSG38)hse.gov.uk
- Flicker Basicsenergy.gov
- LED Basicsenergy.gov
- Purchasing Energy-Efficient Commercial and Industrial LED Luminairesenergy.gov
Revision history
| Date | Version | Change |
|---|---|---|
| November 14, 2026 | 1 | First published |
How to cite
Kurnia (2026). Building lighting: light quantities, lamp types and LED drivers, recommended lighting levels, calculating the number of luminaires with the lumen method, flicker and glare, and maintenance. ARSTEMA Academy. Revised November 14, 2026. arstema.com/en/academy/konsep/pencahayaan-gedung-besaran-cahaya-jenis-lampu-dan-driver-led-tingkat-pencahayaan-yang-dianjurkan-menghitung-jumlah-luminer-dengan-metode-lumen-kedip-dan-silau-serta-perawatan
Self-check · 3 questions
Check your understanding before moving on
Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.
A hotel restaurant of 10 m by 8 m needs 200 lux. The luminaires are 3,000 lm single-module units, UF 0.55, and MF 0.75. How many luminaires are needed, and what is the maintained illuminance?
A 40 m² room has 10 luminaires each holding two 1,800 lm lamps, UF 0.50, and MF 0.80. What is the maintained illuminance, and for which row of the annex is the room adequate?
A hotel replaces 40 spotlights of 800 lm rated at 11 W with lamps of 800 lm rated at 8 W, operating 4,000 hours a year. What is the efficacy of each lamp, and how much energy is saved per year?
Nearby chapters
Reading order by shelf: Electrical & Control · Chapter 106.
Reading order by shelf: Electrical & Control · Chapter 104.