Emergency lighting and exit signs
types of emergency luminaire, batteries and duration, placement on escape routes, monthly function test and annual duration test, records, and limits of work
A hotel loses power at night and two emergency lights in the seventh-floor corridor fail to come on; the log book shows that the last monthly test was carried out five months earlier. This chapter covers emergency lighting and exit signs from the building technician’s side: escape lighting and standby lighting, maintained and non-maintained luminaires, batteries inside luminaires, central batteries, and generators, duration and response time, calculating duration from battery capacity, placement on escape routes under Permenaker 5/2018 and the British fire risk assessment guide for sleeping accommodation, exit signs and their mounting heights, daily, monthly, and annual tests and the 24-hour recharge afterward, the log book, and the division of work. Opening live luminaires, replacing batteries or emergency modules, and changing circuits are stated as work for an authorized electrician.
At eleven at night, an eight-story hotel lost power because of a grid fault. The generator started and took over the load within a few seconds, but during those dark seconds two emergency lights in the seventh-floor corridor did not come on, and a guest who had just stepped out of the elevator tripped over a trolley in front of the stair door. The next morning the duty technician opened the emergency lighting log book and found that the last monthly test had been carried out five months earlier. No annual duration test had been recorded since the hotel opened. Both luminaires worked normally while power was present, so their failed batteries were invisible to everyone until that night.
Scope
This chapter covers emergency lighting and exit signs from the building technician’s side: types of emergency luminaire, batteries and duration, placement on escape routes, exit signs, daily, monthly, and annual tests, and records. The building technician inspects, tests with the test facility provided, records, and reports. The official Indonesian basis in this chapter is Permenaker 5/2018 (Minister of Manpower Regulation) on occupational safety and health (K3) of the work environment; as of November 2026, JDIH Kemnaker records its status as in force. Duration and test schedules are taken only from the British guidance cited, and are written as British data.
The PUIL provisions for emergency lighting in public buildings and the lumen method formula are covered in Chapter 33 on lighting installations, and ordinary lighting levels in Chapter 105 on building lighting. The power supply and standby batteries of fire alarms are in Chapter 22 · Buildings & Facilities, alarm panels and their periodic tests in Chapter 19 · Buildings & Facilities to Chapter 23 · Buildings & Facilities, fire protection in Chapter 17 · Buildings & Facilities, generators and transfer switches in Chapter 36, UPS in Chapter 107 on UPS in buildings, and voice evacuation announcements in Chapter 109 on building sound and paging systems.
Work outside the authority of the building technician: opening an emergency luminaire or exit sign that is still connected, replacing a battery, emergency module, or driver, changing circuit connections, switching off an MCB to test when no test facility exists, and installing or moving luminaires. That work is done only by an authorized electrician after the circuit has been isolated and verified de-energized. Deciding the system and number of emergency lights is part of the fire risk assessment by a competent person, not a decision for the technician on duty.
Types of emergency lighting and emergency luminaires
Emergency lighting is lighting that stays on when the normal lighting fails. The HSE guidance HSG38 divides it into two kinds. Standby lighting enables people to continue working safely, and its illuminance may be 5 to 100 percent of the normal lighting depending on the type of work. Escape lighting enables people to leave a building safely. This chapter mainly covers escape lighting, because that is what is installed in hotel room corridors, stairs, and exit doors.
Permenaker 5/2018 Article 19 requires emergency lighting facilities for rescue and evacuation in an emergency, with three conditions: they work automatically, have enough intensity for safe evacuation or rescue, and are installed on escape routes or exit access routes. The annex of the same regulation lists 5 lux for emergency lighting.
By the way they light, there are two kinds of luminaire. A maintained luminaire is lit all the time and stays lit from its battery when the power fails. A non-maintained luminaire lights only when the normal lighting fails. The UK government’s fire risk assessment guide for sleeping accommodation asks for maintained luminaires where people are unfamiliar with the premises, for example function rooms and bars, and in hotel corridors because guests are unfamiliar with the layout. There is an added practical benefit: a maintained luminaire that has failed is visible every day.
By power source, the same guide names three options: rechargeable batteries inside each luminaire, a central battery bank, or an automatic-start generator. A self-contained luminaire carries its own battery, charger, and changeover circuit, so one faulty luminaire does not darken the others. A central battery system supplies many luminaires from one battery bank through protected wiring, so the batteries are maintained in one place. HSG38 adds that the choice depends on the size and nature of the installation.
The British guidance also describes a way-guidance system near the floor, made of photoluminescent material, lines of LEDs, or small lamps forming a continuously marked escape route; such systems are effective when people have to escape through smoke. Permenaker 5/2018 requires exit access routes to be fitted with exit guidance lines made of reflective material or material that emits light.
Batteries, response time, and duration
Duration is the time an emergency luminaire stays lit from its battery after the power fails. The sleeping accommodation guide writes that systems or luminaires are designed for durations of one to three hours, and that the three-hour design is the most popular because it also helps the premises stay in limited use during a power failure outside an emergency. HSG38 writes the same for battery-powered escape lighting, one to three hours depending on the size of the building and the difficulty of evacuation. The duration that applies to a building is set by the designer and the fire risk assessor, and the technician tests against that figure.
Response time is the interval between the failure of normal lighting and the emergency illuminance being reached. HSG38 cites the British standard BS 5266 Part 1, which recommends that the illuminance be reached within five seconds, extendable to fifteen seconds if workers are familiar with their workplace. In the opening case, a generator that takes over within a few seconds does not replace emergency lighting, because those first seconds are when people are most likely to trip.
Battery duration can be estimated from its energy:
where is the duration (hours), the nominal battery voltage (V), the battery capacity (Ah), the efficiency of the circuit that turns battery energy into light, and the lamp power in emergency mode (W). The formula assumes that the rated capacity is still intact. Battery capacity falls with age, high temperatures inside the luminaire housing, and incomplete charging, and that loss is invisible while power is present. So the data sheet figure is only a starting point, and the real proof is the duration test.
After the battery is discharged, it needs time to recharge. The sleeping accommodation guide writes that batteries typically take 24 hours to recharge, and the premises should not be reoccupied until the emergency lighting system is fully functioning unless alternative arrangements have been made; this is particularly important for premises providing sleeping accommodation seven days a week. For self-contained luminaires, the charging supply must stay connected even when the room light switch is turned off, so that the battery charges and the luminaire can detect a power failure.
Placement on escape routes
The sleeping accommodation guide lists the places an escape lighting system would usually cover: each exit door, escape routes, intersections of corridors, outside each final exit and on external escape routes, emergency escape signs, stairways so that each flight receives adequate light, changes in floor level, windowless rooms and toilets exceeding 8 m², firefighting equipment, fire alarm call points, equipment that would need to be shut down in an emergency, lifts, and halls or other areas greater than 60 m². Not every item needs its own luminaire, but all of them must be lit well enough to be seen and used.
The guide also distinguishes simple premises from larger ones. For a small two-floor guest house with no floor larger than 200 m² and simple escape routes, borrowed lighting from a dependable source, for example street lamps, may be acceptable; for multi-story buildings, hotels, student accommodation, and residential conference centers, a system of automatic escape lighting that illuminates all escape routes is likely to be needed. Escape routes that are not permanently lit by normal lighting, for example external stairs, are given a switch marked “Escape lighting” or another means of switching the lighting on at their entrance.
HSG38 asks that emergency luminaires be mounted at least two meters above the floor to prevent glare, but not much higher, because smoke from a fire may reduce the light on the escape route; lighting outside the building must also be adequate for safe evacuation. Particular attention is paid to stairs, obstructions, and changes in direction.
Exit signs
An exit sign is a sign that shows the direction to exit doors and escape routes. The British guide writes that signs must be pictograms; a pictogram may be supplemented by text, but a fire safety sign that uses only text must not be used, and different types of sign are not mixed. HSG38 asks that direction and fire exit signs be illuminated.
The sign placement criteria in the sleeping accommodation guide can be checked directly by the technician:
- Every escape route sign, where necessary, includes a directional arrow; arrows are not used on their own.
- Signs are positioned so that a person escaping can always see the next sign.
- Signs are fixed above the door in the direction of escape, not on the door leaf, because they are not visible when the door is open.
- Signs above doors are mounted 2.0 to 2.5 m above the floor, and signs on walls 1.7 to 2.0 m.
- Signs are mounted at the same height along the escape route as far as reasonably practicable.
- Signs must not be obscured or overwhelmed by advertising and information boards.
Exit signs must be clearly visible whenever guests, staff, or contractors are in the building. Changes in decoration, promotional boards, or exhibition partitions in a hotel lobby often cover signs, and that is the most common finding of the daily check.
Monthly function test and annual duration test
The sleeping accommodation guide writes that all escape lighting systems should be tested regularly and properly maintained; most existing systems are tested manually, while modern systems with a self-testing facility reduce routine checks. The test facility often takes the form of a special fishtail-shaped key inserted into a test switch near the main fuse board or next to the light switches. That switch simulates a power failure to the luminaires without opening the luminaires or the panel.
According to that guide, testing typically includes:
- A daily visual check of central controls.
- A monthly function test: the test facility is operated long enough to ensure that each emergency lamp lights.
- An annual full discharge test: the battery is fully discharged to prove the design duration.
Another part of the same guide adds a daily check, where practicable, that emergency lighting units are in good repair and working and that all safety signs are legible; the monthly test is carried out at an appropriate time when the lights will not be needed immediately after the test; and every six months a competent person tests and maintains the alarm and emergency lighting systems. Most routine tests can be carried out personally if the test facility is available; if in doubt, the supplier or a competent person is contacted.
The annual duration test needs planning for two reasons. During the test and the 24 hours of charging afterward, the tested area has no full backup. In a hotel that is occupied every night, the test is divided by floor or by area, started in the morning, and alternative arrangements are set in advance by the manager responsible for fire safety, for example the rooms in that area are not sold that night.
Records
The sleeping accommodation guide considers a log book of all maintenance and testing useful, and describes recording emergency lighting test results as good practice. The records also serve as evidence for the enforcing authority that maintenance is being done. Useful content for each test:
- date, time, type of test (daily, monthly, annual), and name of the tester;
- number or location of each luminaire and sign according to the floor plan;
- result: lit, not lit, dim, or minutes lit in the duration test;
- faults, report to the electrician, and date of repair;
- time the recharge finished after the duration test.
Records arranged by luminaire show trends. A battery whose duration falls a little from year to year can be replaced before it fails, while a record that only says “good” cannot be used for that.
Limits of work
The division of work in a hotel can be stated as follows. The appointed building technician carries out visual checks, makes sure signs are not covered, operates the test facility that is actually provided for users, reads the self-test indicators, measures the illuminance on the floor of escape routes with a lux meter during the duration test, and records the results. The British guide states that installing or modifying an escape lighting system is done by a competent person in accordance with the appropriate standards.
A self-contained emergency luminaire stays connected to its charging supply, so its interior is live even when its lamp is off. Opening the luminaire, removing or replacing batteries and emergency modules, and switching off or changing circuits are done by an authorized electrician after the circuit has been isolated and verified de-energized according to Chapter 2 · Safety on verifying a safe state and Chapter 76 on safe work. Spent batteries are handed over as hazardous waste (B3) according to Chapter 35 · Water & Water Treatment on hazardous waste (B3) in hotels, laundries, and workshops. Checks of the generator and transfer switch that supply a central system follow Chapter 36.
Worked example
The figures in the examples below are practice figures, unless their origin is stated.
Example 1: list of places covered on one floor. A hotel’s meeting floor has a function room of 9 m by 7.5 m, a windowless public toilet of 3 m by 3.2 m, and a staff toilet of 2 m by 3 m. The function room is m², more than 60 m², so it is on the guide’s list. The public toilet is m², more than 8 m², so it is also included. The staff toilet is m² and does not meet that toilet area limit, but if the room has no window, the windowless room item is still raised with the fire risk assessor. The technician records all three rooms, together with exit doors, intersections, stairs, manual call points, and firefighting equipment, on the test floor plan.
Example 2: duration from battery capacity. A self-contained luminaire uses a 3.6 V 1.8 Ah battery, efficiency 0.85, and a 1.8 W emergency lamp.
A new battery meets the three-hour design by a narrow margin. If its capacity has fallen to 70 percent, its duration is hours, less than three hours, even though the luminaire still works normally while power is present. Only the duration test finds this condition.
Example 3: a year’s test schedule. A hotel has 64 emergency luminaires. A monthly function test at about one minute per luminaire, including walking and recording, takes minutes per month and 12 tests a year, plus one annual duration test and 365 daily visual checks. For a three-hour design, an area loses full backup for hours at each duration test. If the test starts at 09:00, the batteries are full again only at 12:00 the next day, so that area goes through one night with batteries that are not yet full and needs alternative arrangements.
Example 4: exit sign height. The frame of the stair exit door is 2.10 m high, and a sign 0.2 m tall is mounted with its lower edge 0.05 m above the frame, so its lower edge is at m and its upper edge at m. The whole sign lies within the 2.0 to 2.5 m range for signs above doors. A direction sign on the corridor wall mounted at 1.5 m is below the wall range of 1.7 to 2.0 m and is recorded to be moved by an authorized technician.
Example 5: reading the duration trend. The duration test records of a luminaire in the east stair show 215, 200, and 188 minutes in three consecutive years. The drops are minutes and minutes, an average of minutes per year. If the trend continues, next year’s duration will be about minutes, below the 180 minutes of the three-hour design. The technician reports so that battery replacement by an authorized electrician is planned before the next annual test, rather than waiting for failure.
Example 6: standby lighting and escape lighting. A hotel kitchen is lit to 300 lux and has fryers that need to be shut down if the power fails. According to HSG38, standby lighting for continuing work safely is 5 to 100 percent of the normal lighting, that is, at least lux, with the level chosen according to the task. A corridor normally lit to 50 lux drops to the 5 lux of emergency lighting in the Permenaker annex, that is, percent. The kitchen needs light to work by, not only to walk by, and that need is set by the designer.
Stop conditions
- An emergency luminaire or exit sign does not light during the test, its housing is cracked, it smells burnt, or its battery is swollen or leaking: do not open it and do not touch its interior; tag the luminaire, record it, and hand it over to an authorized electrician.
- The test could only be done by switching off an MCB, opening a panel, or removing the luminaire cover because there is no test facility: stop; that test is done by an authorized electrician following the isolation procedure.
- A battery, emergency module, driver, or lamp inside an emergency luminaire needs replacing: only an authorized electrician does that work, after the circuit has been isolated and verified de-energized according to Chapter 2 · Safety on verifying a safe state.
- After a duration test, the batteries are not yet fully recharged while the area is to be occupied by guests that night: do not let the area be occupied without alternative arrangements; the manager responsible for fire safety decides before nightfall.
- More than one luminaire on one escape route fails in the same test, or the emergency lighting of a central system goes out entirely: report immediately to the engineering supervisor and an authorized electrician, and inform the duty manager so that the route is watched.
- An exit sign points the wrong way, is permanently covered by a partition, or the escape route has changed because of renovation: do not move the sign yourself; report to the person responsible for the fire risk assessment.
Common misinterpretations
Guess what’s wrong first, then open the explanation.
Common misconception
The emergency light is on, so its battery is healthy.
Why is it wrong?
A maintained luminaire runs from the utility supply while power is present. Battery health shows only in the function test and the duration test.
Common misconception
The hotel has a generator, so emergency lighting is not needed.
Why is it wrong?
A generator needs time to start and take over, and it can fail. Escape lighting is recommended to be reached within five seconds according to the British standard cited by HSG38.
Common misconception
The monthly test means leaving the lamps on battery for three hours.
Why is it wrong?
The monthly test lasts long enough to ensure that each lamp lights. A full discharge is done in the annual duration test, which needs 24 hours of charging afterward.
Common misconception
A sign that just says EXIT is enough.
Why is it wrong?
The British guide asks for pictograms; text may supplement them, but signs that use only text are not used.
Common misconception
The emergency light has failed, so just replace the battery.
Why is it wrong?
An emergency luminaire stays connected to its charging supply, so opening it is electrical work. The building technician records and reports; an authorized electrician replaces the battery after isolation.
Links to other chapters
The PUIL provisions for emergency lighting in public buildings and the electrical properties of LED luminaires are covered in Chapter 33 on lighting installations, and ordinary lighting levels in Chapter 105 on building lighting. Standby batteries and fire alarm tests are in Chapter 22 · Buildings & Facilities and Chapter 23 · Buildings & Facilities, generators in Chapter 36, UPS in Chapter 107 on UPS in buildings, and voice evacuation announcements in Chapter 109 on building sound and paging systems. Planned maintenance and its records are covered in Chapter 81.
Exercises and worked solutions
The figures in the exercises are for practice.
Try to answer first, then open the worked solution.
A hotel has a meeting room of 12 m by 6 m and a windowless toilet of 2.5 m by 2.8 m. Which room is on the area list of the sleeping accommodation guide?
Check my answer
See the worked solution
The meeting room is m², more than 60 m², so it is on the list. The toilet is m², not more than 8 m², so it does not meet the toilet area limit, but because it is windowless, its need is still raised with the fire risk assessor.
A self-contained luminaire uses a 3.6 V 2.5 Ah battery, efficiency 0.8, and a 2.4 W emergency lamp. What is its duration when new, and what is it if the capacity has fallen to 80 percent?
Check my answer
See the worked solution
When new, hours, exactly three hours. At 80 percent capacity, the duration is hours, less than the three-hour design, so such a battery has already failed the duration test.
A sign above an exit door is mounted 2.6 m above the floor and a wall sign at 1.5 m. What are the findings?
Check my answer
See the worked solution
The sign above the door at 2.6 m exceeds the 2.0 to 2.5 m range, and the wall sign at 1.5 m is below the 1.7 to 2.0 m range. Both are recorded and reported to be moved by an authorized technician, because moving an illuminated sign involves its circuit.
A three-hour duration test on the fifth floor starts at 10:00. When are the batteries expected to be full again, and what does that mean for guests who check in at 14:00?
Check my answer
See the worked solution
The test ends at 13:00, and with 24 hours of charging the batteries are full only at about 13:00 the next day. Guests who check in at 14:00 would spend the night in an area whose batteries are not yet full, so alternative arrangements decided by the manager are needed, or the test is scheduled on an empty floor.
A two-floor guest house of 180 m² per floor with one staircase, and a six-story hotel. How do their escape lighting needs differ?
Check my answer
See the worked solution
For a two-floor guest house with no floor larger than 200 m² and simple routes, dependable borrowed lighting may be acceptable. For a six-story hotel, the guide considers that a system of automatic escape lighting illuminating all routes is likely to be needed.
In the monthly test, 4 of 50 luminaires do not light. What percentage is that, and what does the technician do?
Check my answer
See the worked solution
percent of the luminaires failed. Each failed luminaire is recorded with its location and reported to an authorized electrician, and if several are on the same route, the duty manager is informed so that the route is watched until it is repaired.
References
External sources
- Peraturan Menteri Ketenagakerjaan Nomor 5 Tahun 2018 tentang Keselamatan dan Kesehatan Kerja Lingkungan Kerjajdih.kemnaker.go.id
- Fire safety risk assessment: sleeping accommodationassets.publishing.service.gov.uk
- Lighting at work (HSG38)hse.gov.uk
Revision history
| Date | Version | Change |
|---|---|---|
| November 14, 2026 | 1 | First published |
How to cite
Kurnia (2026). Emergency lighting and exit signs: types of emergency luminaire, batteries and duration, placement on escape routes, monthly function test and annual duration test, records, and limits of work. ARSTEMA Academy. Revised November 14, 2026. arstema.com/en/academy/konsep/lampu-darurat-dan-tanda-keluar-jenis-luminer-darurat-baterai-dan-lama-nyala-penempatan-di-jalur-evakuasi-uji-fungsi-bulanan-dan-uji-durasi-tahunan-catatan-serta-batas-pekerjaan
Self-check · 3 questions
Check your understanding before moving on
Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.
A hotel has a meeting room of 12 m by 6 m and a windowless toilet of 2.5 m by 2.8 m. Which room is on the area list of the sleeping accommodation guide?
A self-contained luminaire uses a 3.6 V 2.5 Ah battery, efficiency 0.8, and a 2.4 W emergency lamp. What is its duration when new, and what is it if the capacity has fallen to 80 percent?
A sign above an exit door is mounted 2.6 m above the floor and a wall sign at 1.5 m. What are the findings?