By Kurnia · Published November 14, 2026 · Version 1 · 21 min read
Building sound and paging systems
100-volt line loudspeakers, zones, background music, emergency announcements and voice alarm, calculating amplifier load, and intelligibility testing
After a new wing of a hotel is completed, a contractor connects ten additional loudspeakers to the old corridor zone, and from then on its amplifier goes into protection mode whenever the background music is turned up, while test announcements in the far corridor sound loud but are hard to understand. This chapter explains building sound and paging systems from the technician’s side: the chain of source, amplifier, line, and loudspeaker; the 100 V constant-voltage line with matching transformers and power taps; the relationship of power, voltage, and impedance (P = V²/Z); zones, background music, local volume controls, and priority relays; emergency announcements and voice alarm systems connected to the fire alarm, covered from the inspection side; calculating amplifier load, power reserve, and cable loss; and sound level and speech intelligibility testing. Comparison figures come from United States facility specifications and criteria and from United Kingdom fire safety guidance, and are written as data of those countries. Indonesian requirements for voice alarm systems could not be confirmed as of November 2026, and changes to a system connected to the fire alarm are stated to be the work of competent designers and contractors.
A new wing of a hotel has been completed, and the interior contractor connects ten ceiling loudspeakers in its corridor to the existing corridor zone line, because the cable happens to run above the ceiling. From then on the corridor zone amplifier goes into protection mode every time the background music is turned up at night, then comes back on a few seconds later. At the monthly announcement test, a security officer at the end of the new wing reports that the sound is loud but the words are hard to catch. The two complaints come from two different problems: an amplifier loaded beyond its power, and speech that is unclear even though it is loud enough. Both can be calculated and measured, and both concern a system that in an emergency has to deliver evacuation instructions to guests who are asleep.
Scope
This chapter covers building sound and paging systems from the side of the technician in a hotel, hospital, or large laundry: system components, the 100 V loudspeaker line, zones and background music, calculating amplifier load, and sound level and intelligibility testing. The basics of sound and decibels are in Chapter 14 · Physics on mechanical waves and sound and Chapter 9 · Units & Mathematics on logarithms and decibels; workplace noise in Chapter 7 · Safety; transformers in Chapter 12; cable voltage drop in Chapter 28; load impedance in Chapter 5; surges on long cables in Chapter 35 on overvoltage and surge protection; paging from the telephone in Chapter 96 on the hotel telephone exchange; and IP loudspeakers powered by PoE in Chapter 108 on the hotel data network.
The fire alarm is in Chapter 19 · Buildings & Facilities to Chapter 23 · Buildings & Facilities: panel, detectors, wiring, power supply and notification appliances, and periodic testing. A voice alarm system connected to the fire alarm is covered here only from the inspection side: what is observed, recorded, and reported. This chapter gives no way to switch off, delay, mute, or bypass emergency announcements, and no steps for changing priorities, the fire panel interface, or recorded messages. Indonesian requirements specific to voice alarm systems in hotels could not be confirmed as of November 2026; check with the designer of the building’s fire protection system and the local fire service. The comparison figures in this chapter are United States and United Kingdom data, written as data of those countries.
Designing the system, adding or moving loudspeakers in an evacuation zone, changing taps and zones, opening the amplifier rack on the utility supply side, and working on a line that is switched on are the work of designers, sound system or fire system contractors, and authorized technicians. The building technician reads indications, listens and measures, records, keeps loudspeakers and volume controls intact, and reports.
System components and the signal chain
A public address system (PA) is a system that delivers sound from a microphone, a recorded message, or a music source to loudspeakers in many rooms at once. Its chain has four parts: the source (paging desk microphone, music player, recorded message, telephone), the preamplifier and matrix that select the source for each zone, the power amplifier, and the cable line to loudspeakers in the ceiling, on the wall, or outside the building.
A zone is a group of loudspeakers that always receives the same signal, for example the third-floor corridor, the restaurant, or the pool area. A United States facility paging specification requires a zoned system that can page one zone or all zones at once, distribute speech and music evenly, and be free of hum, hiss, or rattle. Hotel zones usually follow the function and hours of use of the spaces: restaurant, lobby, meeting rooms, and guest room corridors.
United States mass notification criteria advise that effective sound inside a building is obtained from many loudspeakers each with low intensity, not from a few loud loudspeakers. Listeners close to a loud loudspeaker are disturbed, while those far away receive more echo than direct sound. A designer’s note in the paging specification above gives a rule of thumb that corridor ceiling loudspeakers are spaced at most twice the ceiling height for ceilings up to 3 m.
The 100 V line and matching transformers
Home or stage loudspeakers are connected directly to the amplifier at low impedance, for example 4 or 8 Ω. That method does not suit buildings, because cables tens to hundreds of meters long and dozens of loudspeakers in parallel would lower the total impedance below the amplifier’s limit and waste power in the cable. The principle used is the same as in a power grid: power is sent at a high voltage, so that the current is small and the line loss is small as well.
A constant-voltage line is a method of audio distribution that sets the amplifier output voltage at its rated power, for example 100 V, and each loudspeaker is fitted with a line matching transformer that steps the line voltage down to the voice coil voltage. That transformer has several taps, which are primary connections that each draw a set power from the line, for example 1.5 W, 3 W, or 6 W. The line voltage changes with the signal; the figure of 100 V is the effective voltage when the amplifier delivers its rated power. United States specifications use 25 V and 70.7 V lines.
The relationship between tap power and the primary impedance of the transformer follows the electric power formula:
where is the power drawn by the tap in watts, the nominal line voltage in volts, and the nominal primary impedance at that tap in ohms. This formula uses nominal impedance and ignores transformer losses; the actual impedance changes with frequency. The cone loudspeaker table in the specification above shows this relationship: at 70.7 V, the 0.5 W, 1 W, and 2 W taps have primary impedances of 10 kΩ, 5 kΩ, and 2.5 kΩ.
Because all taps are connected in parallel to the same voltage, the total power of a zone is the sum of the tap powers, and the impedance seen by the amplifier is
Moving one tap from 3 W to 6 W raises the sound level of that loudspeaker by about 3 dB, because doubling the power gives a difference of dB. Taps are also used to balance sound levels between spaces.
A 100 V line is still dangerous even though it carries an audio signal. At full power its effective voltage is about 100 V AC, enough to give a shock, and on a large amplifier the signal current is several amperes. Junction boxes and loudspeaker terminals are treated as live parts while the system is switched on (Chapter 76 on safe work).
Zones, background music, and local volume controls
Background music is low-level music played continuously through public zones such as the lobby, restaurant, and corridors. Music and paging share amplifiers and loudspeakers, so a zone announcement lowers the music in that zone, and an emergency announcement takes precedence over everything.
A local volume control is a control on the wall of a room, usually a stepped transformer, that lets guests or staff turn the sound down in a meeting room or restaurant. The United States specification requires volume controls with 3 dB steps and an off position, and every remote volume control and loudspeaker switch is fitted with a priority override relay that bypasses that control for priority announcements. Mass notification criteria that use an existing paging system require emergency messages to take priority over ordinary messages, all volume controls to return to the emergency level during an emergency message, a supervisory signal when the paging system is placed in the off position, and line monitoring to continue even when local volume controls are in the off position.
For the technician, this means that a volume control turned down to zero in a meeting room must not make that room silent during an emergency announcement. This is checked during a scheduled test by the person responsible for the system: the volume control is left at its lowest position, and the listener checks whether the test message is still heard at the normal level. An additional volume control installed by a room tenant without a priority relay is a finding that is reported.
Hotel function rooms and ballrooms are often used for parties with loud music from a stage system owned by the tenant. United Kingdom fire safety guidance for places of assembly requires, at events such as discos, a public address system that can override the performance and be heard clearly in all parts of the premises. In a hotel, the way the stage system is switched off or turned down on alarm is set by the designer and tried with the tenant before the event; the technician checks that the link is connected, rather than building it themselves.
Emergency announcements and voice alarm
A voice alarm is a system that delivers a fire warning as a spoken message, recorded or live, as a replacement for or a supplement to siren sound. United Kingdom guidance for premises with sleeping accommodation states that some people, in particular members of the public, do not always react quickly to a conventional fire alarm, so voice alarms are increasingly used and can also incorporate a public address facility. Its messages are carefully considered, and the system is designed and installed by a person with specialist knowledge of these systems.
In large multi-story hotels, the same guidance mentions the possibility of phased evacuation: the people most at risk are evacuated first, while others receive an alert signal and only leave if necessary. Such a system requires a two-stage warning or a voice alarm triggered automatically by the detection system, with an alert signal that differs from the evacuate signal, and its recorded messages include the necessary languages. The languages, order, and content of the messages for a hotel with international guests are set by the designer together with management.
A paging system that is part of the fire warning system is connected to a standby power source so that it keeps working during a fire or other emergency. For fire warning systems in premises with sleeping accommodation, United Kingdom guidance mentions a backup that is normally capable of operating the system for at least 24 hours and sounding the alarm in all areas for 30 minutes. Battery calculations are covered in Chapter 22 · Buildings & Facilities on power supplies and notification appliances for fire alarms, and UPS units in Chapter 107.
United States criteria for mass notification systems require the ability to interrupt ordinary paging and to silence background music while an emergency message is delivered. In a hotel, background music that keeps playing under an evacuation message is a finding.
What the building technician checks on this side is limited: the standby and fault lamps on the voice alarm amplifier rack, the test records, and the results of the weekly test. The weekly checklist in the United Kingdom guidance asks whether voice alarm systems work correctly and whether the message was understood. A message that is heard but not understood is recorded as a failure.
Calculating amplifier load and power reserve
A 100 V line amplifier is given a rated power, for example 120 W. The zone load is safe when the sum of tap powers multiplied by the reserve factor does not exceed that rated power. The reserve covers peaks in speech and music, transformer losses, and zones added later. A designer’s note in the United States specification calculates amplifier power with 1 W per loudspeaker and a multiplier of 1.4 for reserve power. Written in general form,
where is the rated power of the amplifier or channel in watts, the dimensionless reserve factor, and the sum of the zone’s tap powers in watts. The value above is the choice of one specification; the value for a particular system is read from its design documents. The line current at full power is .
The line cable also takes part of the power. For a two-core copper cable of length from the amplifier to the end of the zone,
where is the loop resistance in ohms, the resistivity of copper in Ω mm²/m, the one-way length in meters, and the cross-sectional area of one core in mm². If the whole load is assumed to be concentrated at the end of the cable and resistive, the fraction of the voltage that reaches the load is . That assumption gives the largest loss, because in a real zone the loudspeakers are spread along the cable. The method of calculation is similar to voltage drop in Chapter 28.
Sound level and intelligibility testing
Sound level in decibels is ten times the logarithm of the ratio of sound intensity to a reference intensity. The change in level between two states is calculated from the power ratio:
where is the level difference in dB and , the power before and after. Raising a tap from 3 W to 6 W gives about +3 dB, and lowering it from 6 W to 1.5 W gives about −6 dB.
For bedrooms, United Kingdom guidance requires a sufficient fire warning sound level at the head of the bed, namely 75 dBA, so that people are woken, and notes that this will usually mean one sounder in each bedroom. Indonesian figures for fire alarm sounders and sound loss with distance and through doors are covered in Chapter 22 · Buildings & Facilities.
Speech intelligibility is how well the broadcast words can be understood by listeners. A high sound level does not guarantee intelligibility: echo in a stone-floored lobby, machine noise, and loudspeakers that are too far away can make loud speech blurred. The speech transmission index (STI) and the common intelligibility scale (CIS) are intelligibility measures with values from 0 to 1 that are read with an intelligibility meter.
United States facility criteria give an example of the test method and limits used there. Intelligibility is verified by measurement after installation, with a CIS value of at least 0.7 or 0.8 depending on the military service that owns the facility in every area where occupants are normally present, and an STI of 0.5 is considered equivalent to a CIS of 0.7. Measurements are taken near the head height of people in their usual position in the space, standing, sitting, or sleeping, and the value at each test point is the mean of at least three readings. Areas with hard surfaces that cause excessive sound reflection may have a lower value with approval, if occupants can tell that a broadcast is under way and need to walk no more than 10 m to a point that meets the requirement. These figures are used here as an example of how to assess, not as limits binding on hotels in Indonesia.
The United States paging specification above requires acceptance tests that can serve as a checklist: an operational test of all sources and zones, signal-to-noise ratio, distortion, the spread of sound level with pink noise at five points in each zone with a difference between points and between zones of at most ±3 dB, amplifier output power, an outage test for UPS-backed components, and a list of the final tap of each loudspeaker transformer. That tap list is the basis for every later change, and the measurements are repeated whenever taps, zones, or the room layout change (Chapter 23 · Buildings & Facilities on periodic testing and maintenance of fire alarm systems).
Worked example
The figures in the examples below are practice figures, unless their origin is stated.
Example 1: tap impedance and the specification table. On a 100 V line, a 6 W tap has an impedance of Ω, a 3 W tap Ω, and a 1.5 W tap Ω. The same formula checks the United States specification table: at 70.7 V, a 0.5 W tap gives Ω, which is 10 kΩ in the table, and at 25 V a 2 W tap gives Ω, which is written as 312 Ω. A transformer with a 1,667 Ω label at 100 V is a 6 W tap; the same tap used on a 70.7 V line draws only W.
Example 2: restaurant zone load. The restaurant zone contains 14 ceiling loudspeakers on 3 W taps and 2 wall loudspeakers on 6 W taps. The total power is W, the impedance seen by the amplifier Ω, and the line current at full power A. With a reserve multiplier of 1.4, the amplifier channel is at least W. A 120 W channel meets this with a 45 percent load, while a 60 W channel does not, even though it is larger than 54 W.
Example 3: the new wing on the corridor zone. The corridor zone originally contained 18 loudspeakers on 6 W taps, which is 108 W, on a 120 W channel. Ten additional 6 W loudspeakers raise the load to W, which is times the rated power; this is why the amplifier goes into protection mode in the opening case. If all 28 loudspeakers are set to the 3 W tap, the load is W and with the reserve W, still below 120 W, but the sound level of all loudspeakers drops by about 3 dB. The new wing corridor, 50 m long with a 2.7 m ceiling, with a spacing of at most twice the ceiling height, namely 5.4 m, requires , rounded up to 10 loudspeakers. The choice between lowering the taps and adding an amplifier channel is the designer’s decision, and afterward intelligibility is measured again.
Example 4: 100 V line cable loss. A 120 W channel sees a load of Ω. A copper cable of 2 × 1.5 mm², 150 m long to the end of the zone, with Ω mm²/m, has a loop resistance of Ω. If the load is assumed to be concentrated at the end, the voltage at the load is V, the power that arrives is of the total, which is a loss of dB, and the power in the cable is about 4.6 W. If an 8 Ω loudspeaker is connected directly with the same cable, the voltage fraction is and the power fraction , a loss of about 3.2 dB. That difference is the reason buildings use constant-voltage lines.
Example 5: taps and room sound level. In the corridor, a loudspeaker on the 6 W tap gives 78 dBA at the measuring point. Lowering it to 3 W gives about dBA, and to 1.5 W about 72 dBA. At the head of the bed in a room with the door closed, 62 dBA is measured, 13 dB short of the 75 dBA in the United Kingdom guidance for bedrooms. To gain 13 dB from the same corridor loudspeaker, its power would have to be times greater, far above the available taps. The shortfall is covered by a loudspeaker or sounder inside the room, designed by the designer.
Example 6: the mean of three intelligibility readings. In the far corridor of the new wing, three STI readings at head height are 0.52, 0.47, and 0.49, with a mean of , below the 0.5 that the United States criteria consider equivalent to a CIS of 0.7. The 0.52 reading alone does not make that point pass. After the designer adds one loudspeaker and lowers the tap near the glass wall, the readings become 0.55, 0.53, and 0.54, with a mean of 0.54, and the point is recorded as meeting the requirement.
Stop conditions
- During a scheduled test, the emergency announcement or evacuation signal is not heard, is too weak, or is not understood in a zone: record the zone and the time, report to the person responsible for the building’s fire protection system, and hand the repair to a competent system contractor; do not change the priority settings, levels, or messages yourself.
- Someone asks for emergency announcements to be switched off, delayed, or muted, or for a zone to be excluded from the voice alarm, for example during an event or renovation: refuse, and report to the fire safety manager and the building manager; changes to the system are decided only by the designer together with the competent authority.
- The amplifier goes into protection mode, is abnormally hot, smells of burning, or the rack fuse blows repeatedly: do not add load or turn up the volume, record the zone load, and report; the rack and the utility supply side are inspected by an authorized technician.
- The voice alarm amplifier rack or the panel shows a line fault, amplifier fault, or supply fault: record it and report to the person responsible for the system, and treat that zone as less protected until it is repaired; do not disconnect the line to clear the fault indication.
- The work would require opening a junction box, a loudspeaker terminal, or a transformer on a line that is switched on: postpone it; the line is treated as live, and isolation is done by an authorized person with a work permit (Chapter 76).
- There is a plan to add or move loudspeakers, change taps, install a volume control, or merge zones on a system connected to the fire alarm: hand it to the designer and the system contractor, and ask for the tap list and intelligibility test results to be updated before the space is used.
- The standby supply of the voice alarm amplifier has failed during a test, its battery is past its service life, or the voice alarm amplifier is not included in the standby load: report it as a critical finding to the person responsible for the fire system (Chapter 22 · Buildings & Facilities and Chapter 107).
Common misinterpretations
Guess what’s wrong first, then open the explanation.
Common misconception
A 120 W amplifier is enough for twenty 6 W loudspeakers.
Why is it wrong?
Twenty 6 W taps draw exactly 120 W, so the amplifier works at full power with no reserve for peaks, transformer losses, and the cable. Amplifier power is compared with the sum of the taps multiplied by the reserve factor.
Common misconception
Louder means clearer.
Why is it wrong?
In a reverberant or noisy room, raising the sound level also raises the echo. Intelligibility is measured with STI or CIS and improved through the arrangement, number, and direction of loudspeakers, not just the volume.
Common misconception
A volume control turned to zero makes that room silent, also in an emergency.
Why is it wrong?
Volume controls in an evacuation zone are fitted with a priority relay that bypasses them for emergency messages. A control without that relay is a finding.
Common misconception
A 100 V line only carries an audio signal, so it is safe to touch.
Why is it wrong?
At full power its effective voltage is about 100 V AC. Its terminals are treated as live parts while the system is switched on.
Common misconception
Line impedance can simply be measured with the ohmmeter of a multimeter.
Why is it wrong?
An ohmmeter reads the direct-current resistance of the transformer winding, which is much smaller than its impedance at speech frequencies (Chapter 5). The line load is checked from the tap list or with a line impedance meter by the contractor.
Links to other chapters
Chapter 22 · Buildings & Facilities on power supplies and notification appliances for fire alarms covers sounder sound levels and battery capacity, Chapter 19 · Buildings & Facilities on fire alarm panels covers the alarm and fault states that also appear on voice alarm systems, and Chapter 23 · Buildings & Facilities on periodic testing and maintenance of fire alarm systems provides the framework for test schedules and forms. Chapter 106 on emergency lighting and exit signs and Chapter 107 on UPS units in buildings complete the standby supply side, while Chapter 96 on the hotel telephone exchange covers paging that comes in from telephone sets.
Exercises and worked solutions
The figures in the exercises are for practice.
Try to answer first, then open the worked solution.
What is the primary impedance of a 10 W tap on a 100 V line, and what is it on a 70.7 V line?
Check my answer
See the worked solution
At 100 V, Ω, and at 70.7 V, Ω. The impedance of taps with the same power depends on the line voltage, so the transformer is chosen for the installed line, and a label that only states ohms is read together with its line voltage.
The lobby zone contains 24 loudspeakers on 1.5 W taps and 4 loudspeakers on 6 W taps. Calculate the total power, the impedance seen by the amplifier, and the smallest channel power with a reserve multiplier of 1.4.
Check my answer
See the worked solution
The total power is W, the impedance Ω, and the smallest channel W. A 60 W channel that looks like an exact fit leaves no reserve, so a channel above 84 W is chosen or the zone is split.
An event committee in a meeting room asks the technician to turn the volume control to zero and disconnect the room’s loudspeakers so that emergency announcements do not disturb important guests. What is the technician’s answer?
Check my answer
See the worked solution
The technician refuses to disconnect the loudspeakers or to exclude the room from emergency announcements, because the people in that room also need to receive evacuation instructions. The volume control may be turned for music and ordinary paging, but the priority relay must still bypass it, and the request is reported to the fire safety manager.
The voice alarm amplifier rack draws 40 W on standby and 300 W when all zones are broadcasting a message. What is the battery energy for 24 hours of standby followed by 30 minutes of broadcast, and how many ampere-hours is that at 24 V before aging factors?
Check my answer
See the worked solution
The energy is Wh, which is Ah at 24 V. This figure does not yet include the aging and efficiency factors in Chapter 22 · Buildings & Facilities, so the installed capacity is larger and is set by the designer.
Why is the intelligibility value of one point calculated from the mean of three readings at head height, and not from a single reading?
Check my answer
See the worked solution
Intelligibility readings change from second to second because of background noise and the test signal, so a single reading may happen to be high or low. The mean of three readings at head height represents what is actually received by people standing, sitting, or sleeping in that space.
The ballroom is rented for a party with a stage system owned by the tenant. What is checked before the event so that emergency announcements can still be heard?
Check my answer
See the worked solution
What is checked is the link that turns down or switches off the stage system on alarm while the building loudspeakers still override the performance, as the United Kingdom guidance for places of assembly requires. A trial is carried out with the tenant and the person responsible for the system before the event, and the technician does not build that connection themselves.
References
External sources
- UFGS-27 51 16 Public Address Systemswbdg.org
- UFC 4-021-01 Design and O&M: Mass Notification Systemswbdg.org
- Fire safety risk assessment: sleeping accommodation (accessible)gov.uk
- Fire safety risk assessment: small and medium places of assembly (accessible)gov.uk
- College Physics 2eopenstax.org
Revision history
| Date | Version | Change |
|---|---|---|
| November 14, 2026 | 1 | First published |
How to cite
Kurnia (2026). Building sound and paging systems: 100-volt line loudspeakers, zones, background music, emergency announcements and voice alarm, calculating amplifier load, and intelligibility testing. ARSTEMA Academy. Revised November 14, 2026. arstema.com/en/academy/konsep/tata-suara-dan-sistem-panggil-gedung-pengeras-suara-saluran-100-volt-zona-musik-latar-pengumuman-darurat-dan-evakuasi-suara-menghitung-beban-penguat-serta-uji-kejelasan
Self-check · 3 questions
Check your understanding before moving on
Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.
What is the primary impedance of a 10 W tap on a 100 V line, and what is it on a 70.7 V line?
The lobby zone contains 24 loudspeakers on 1.5 W taps and 4 loudspeakers on 6 W taps. Calculate the total power, the impedance seen by the amplifier, and the smallest channel power with a reserve multiplier of 1.4.
An event committee in a meeting room asks the technician to turn the volume control to zero and disconnect the room’s loudspeakers so that emergency announcements do not disturb important guests. What is the technician’s answer?