By Kurnia · Published November 14, 2026 · Version 1 · 20 min read
Noise and vibration from building equipment
machine noise sources, decibels and how to add them, vibration isolators, guest complaints, measurement, and repair
A guest in a second-floor hotel room complains of a hum every night when the water transfer pump in the room below starts, and the technician finds the pump’s mounting springs fully compressed and the pipe clamped rigidly to the floor slab. This chapter covers noise and vibration from building equipment as they affect rooms and guests: machine noise sources and their airborne and structure-borne paths, decibels and A-weighting, room noise standards in the appendix to Permenkes 2/2023 and the WHO guidelines, adding and subtracting decibels including background noise correction, the effect of distance and walls, vibration isolation with static deflection and transmissibility, handling guest complaints, measuring with a sound level meter, energy averaging over time intervals, and the order of repairs from the source and the path to the receiving room. Practice numbers are used unless their origin is stated. Noise for workers and machine condition monitoring are referred to other chapters.
A guest in a second-floor room of a hotel calls the front desk on the second night of their stay: every few minutes a low hum comes from the floor, and the surface of the water in a glass on the bedside table trembles. Below the room is the domestic water transfer pump room, whose pump starts and stops according to the roof tank level. The duty technician measures in the room with a sound level meter: about 37 dB(A) with the pump off and about 41 dB(A) with the pump running. In the pump room, the technician finds the pump’s mounting springs compressed until their coils touch, and the discharge pipe clamped directly to the floor slab without a flexible connector. The WHO guideline for noise inside bedrooms at night is 30 dB as an 8-hour average and 45 dB as a maximum level. The guest’s problem is not solved by closing the door or window, because the pump’s vibration travels through the structure, and that is the path that needs to be broken.
Scope
This chapter covers noise and vibration from building equipment, such as pumps, fans and air handling units, fan coil units, chillers, cooling towers, generator sets, compressors, and elevators, as they affect rooms used by guests, patients, and occupants. The building technician’s side covered here is recognizing sources and transmission paths, calculating with decibels, measuring, recording complaints, and choosing repairs. The Indonesian standard used is the appendix to Permenkes 2/2023 (a Minister of Health regulation). As of November 2026, JDIH Kemenkes (the Ministry of Health legal documentation network) records Permenkes 2/2023 as no longer in force because it was revoked by Permenkes 3/2026, but Article 99 of Permenkes 3/2026 excludes, among others, Article 12 and its appendix from the revocation; check its latest status with the person responsible for environmental health in the building. The WHO guidelines and the facilities standards of the US GSA are used for comparison and are given with the name of each body.
Noise and vibration for workers, including dose, threshold limit values, and hearing protection, are covered in Chapter 7 · Safety on noise and hand-arm vibration and are not repeated here. Machine condition monitoring from vibration, temperature, and sound is in Chapter 14 · Mechanical & Mechatronics on condition monitoring and mechanical maintenance decisions, pipe vibration and pipe supports in Chapter 9 · Fluids & Thermal on expansion, supports, and vibration of pipes, the basics of sound waves and decibels in Chapter 14 · Physics on mechanical waves and sound, logarithms in Chapter 9 · Units & Mathematics on exponents, logarithms, and decibels, and forced vibration and the theory of vibration isolation in Chapter 22 · Physics on forced vibration and vibration isolation. How the ear hears is covered in Chapter 39 · Biology & Microbiology on the ear and the eye. This chapter gives no health diagnosis; guests who complain of disturbed sleep or ringing in the ears are referred to a doctor. Assessing structural cracks, lifting or moving heavy machines, and replacing machine mounts are work for a mechanical technician or contractor with a work plan, and are written here as limits.
Sources of noise and vibration in building equipment
Building equipment produces sound from rotating parts and from fluid flow. Fans produce sound from blades cutting through air and from air flowing fast in ducts and grilles. Pumps produce sound from the motor, the impeller, and the flow in the pipe, including a crackling sound when cavitation occurs. Chillers and compressors hum, cooling towers produce the sound of falling water and fans, and generator sets produce engine and exhaust sound. Transformers hum at twice the line frequency.
Sound reaches guest rooms by two paths. Airborne noise is sound that travels through air and passes through walls, doors, gaps, or air ducts. Structure-borne noise is machine vibration that travels through mounts, floor slabs, walls, pipes, and ducts and is then radiated again as sound by surfaces in another room. Structure-borne noise is often heard as a low hum that seems to come from the whole room, as in the opening case, and does not drop much when the door is closed.
Frequency determines how sound is perceived and dealt with. Tonal sound, that is, sound with one prominent frequency such as the hum of a motor or transformer, is more disturbing than broadband hissing at the same level. WHO notes that if noise includes a large proportion of low-frequency components, lower guideline values should be applied, and that for indoor environments reverberation time is also an important factor.
The facilities standard of the US GSA for federal government buildings requires all mechanical equipment to be vibration isolated from the building frame, and requires water, wastewater, and drain piping in the walls, ceilings, and floors enclosing noise-sensitive spaces to be vibration isolated from the structure, finishes, and other piping. Those two provisions summarize a general rule: vibration is broken near its source, before it enters the structure.
Decibels, A-weighting, and room noise standards
Sound intensity level is expressed in decibels:
where is in dB, is the sound intensity in W/m², and is the reference intensity, the threshold of hearing at a frequency of 1 kHz. Because the scale is logarithmic, doubling the intensity adds about 3 dB. The ear can discern differences of about 1 dB at the same frequency, and a change of 3 dB is easily noticed. A sound level meter reads sound pressure level, whose relationship to intensity level is covered in Chapter 14 · Physics on mechanical waves and sound.
A-weighting is a filter in a sound level meter that attenuates low and very high frequencies so that the reading approximates the ear’s sensitivity; the result is written dB(A). The equivalent continuous level is the steady level with the same energy as a fluctuating sound over a given time interval, while is the highest level during that interval. Because A-weighting attenuates low frequencies, a structure-borne hum can be disturbing even when its dB(A) reading is not high.
The appendix to Permenkes 2/2023 lists noise as a physical parameter of indoor air: 55 dB(A) for residential areas and 60 dB(A) for other public places and facilities except health care facilities, measured by direct reading with a sound level meter. For health care facilities there is a separate table:
| Room in a health care facility | Maximum noise pressure level |
|---|---|
| Patient room while awake | 65 dBA |
| Patient room while asleep | 55 dBA |
| Isolation room | 55 dBA |
| Kitchen | 70 dBA |
| Laundry room | 80 dBA |
| Special high-noise rooms such as generator sets | 85 dBA |
The WHO guidelines on environmental noise give much lower figures for sleeping rooms: inside bedrooms 30 dB for 8 hours at night and 45 dB , and in hospital ward rooms 30 dB at night with 40 dB . WHO also states that energy-based measures such as alone are not enough and that maximum values, together with the number of events, should be shown. For offices, GSA uses mechanical background noise criteria in the form of NC or RC values, for example 35 to 40 for private offices without an electronic sound masking system. These figures use different measures, so they are compared only with the same measure: with , and maximum level with maximum level.
Adding and subtracting decibels
Decibels are not added directly; their energies are added. For several unrelated sources:
Two equal sources produce a level 3 dB higher than one source, and ten equal sources produce a level 10 dB higher. If one source is 10 dB higher than another, the smaller source adds only about 0.4 dB. Fixing the largest source therefore almost always gives the biggest result, and fixing a small source next to a large one is hardly audible (Example 1).
When measuring the sound of one machine in a room that already has sound, the meter reads the sum of the machine’s sound and the background noise, that is, the room’s sound when that machine is off. The machine’s own level is obtained by subtracting energies:
This subtraction is sensitive to instrument accuracy. If the difference between the total and background levels is large, for example 10 dB or more, the correction is small. If the difference is only 1 to 3 dB, an instrument error of 1 dB already changes the result by several decibels, so the result is recorded as an estimate and the measurement is repeated when the background is quieter (Example 2).
Sound that varies over a time interval is averaged by its energy, not by its decibel figures:
where is the duration of interval , is the level during that interval, and is the sum of all in the same unit. A plain average of decibel figures is always lower than when the level fluctuates, so a pump that starts occasionally seems quieter than it really is (Example 6).
Distance, walls, and transmission paths
For a point source in the open air without reflections, intensity falls with the square of distance, so doubling the distance reduces the intensity to one quarter. In decibels:
where is the level at distance and is the level at distance . Each doubling of distance lowers the level by about 6 dB. This formula applies to equipment on a roof or in a yard away from reflecting walls, for example a cooling tower relative to a guest room balcony (Example 3). Inside a machine room with hard walls, reflections make the sound level nearly uniform over most of the room, so moving a few meters away from the machine does not lower the reading much.
Walls, floors, and doors reduce airborne noise. The level difference is the difference in sound level between the source room and the receiving room: . The value of depends on frequency, the mass and construction of the wall, the tightness of joints, and absorption in the receiving room. A single dB(A) figure for is enough for estimating, not for design. GSA uses the STC rating for building elements tested in a laboratory and the NIC rating for sound isolation between two rooms tested in the field, and gives a rule of thumb that at STC 50 loud speech is not audible and shouting is barely audible.
The weakest path determines the result. A good wall loses most of its performance if there is a gap under the door, a pipe penetration that is not tightly sealed, or an air duct connecting the machine room to the guest room without a silencer. The energy from two paths is added with the decibel addition formula, so a single gap can matter more than the whole wall (Example 4). Air velocity in ducts and grilles also determines flow noise; GSA, for example, recommends an air velocity of about 6 m/s in main ducts and about 4 m/s in branch ducts for private offices.
Vibration isolators
Vibration isolation is reducing the force a machine transmits to the structure by means of flexible mounts, such as steel springs, rubber pads, or spring hangers. Chapter 22 · Physics on forced vibration and vibration isolation derives the theory. Without damping, the transmissibility, that is, the ratio of the transmitted force to the disturbing force, is:
where is the forcing frequency, generally the machine’s rotational frequency in Hz, and is the natural frequency of the machine on its mounts. Isolation only works when is greater than ; below that, the mount actually amplifies the force, and around resonance occurs. The natural frequency is estimated from the static deflection , that is, how far the mount settles under the machine’s weight:
This formula comes from with m/s² and in millimeters. Slow-running machines need a large deflection and therefore use springs; fast-running machines can use rubber with a small deflection (Example 5).
Common isolation failures in the field are springs that are fully compressed or broken, transport locking bolts that were not removed after installation, rubber that has hardened and cracked with age and oil, mounts loaded unevenly so that the machine tilts, and a rigid bridge, that is, a rigid object connecting the machine to the structure outside the mounts, such as a pipe without a flexible connector, rigid electrical conduit, seismic restraint bolts in tight contact, or debris under the machine base. A single rigid bridge can cancel the effect of all the mounts, because vibration takes the stiffest path.
The technician’s visual inspection covers spring height compared with the installed height on the drawing or nameplate, the clearance around the machine base, the condition of rubber, flexible connectors on pipes and ducts on the machine side, and pipe hangers near the machine. Increased machine vibration due to imbalance, misalignment, or damaged bearings is read according to Chapter 14 · Mechanical & Mechatronics on machine condition monitoring, because fixing the mounts does not cure a damaged machine.
Guest complaints and measurement
Noise complaints are recorded like measurement data: room number, date and time, the guest’s description of the sound (hum, hiss, knocking, rattling, vibration that can be felt), whether it is continuous or intermittent, and since when. That record is matched against equipment schedules and logs from the building management system: pump run times, compressor cycles, fan schedules, or generator set tests. An intermittent sound that matches the cycle of one machine already points to its source. The disturbed guest is moved to another room through the front desk while the inspection takes place, and health complaints are referred to a doctor.
Measurement uses a calibrated sound level meter, which is checked with an acoustic calibrator before and after measuring if one is available. The meter is placed at the guest’s head position, for example above the pillow, about one meter from walls and away from reflecting surfaces, with the windows, door, and room air conditioning in the state the guest normally uses while sleeping. The technician records the weighting and time response used, over a stated interval, and , in two states: the suspected machine running and off. Measurements are taken at the hour of the complaint, because background noise at night is much lower than during the day.
Vibration that can be felt can be checked simply by placing a hand on the wall or floor, or by watching the water surface in a glass, and matching it with the machine’s cycle. Measuring floor vibration for human comfort requires special instruments and methods; GSA refers to ISO 2631-2 for vibration in buildings, and such measurements are handed over to an acoustics and vibration consultant. Measurements in a very noisy machine room follow the exposure limits and hearing protection in Chapter 7 · Safety.
Repair
Repairs are arranged by three places: the source, the path, and the receiver. At the source, a machine that is louder than usual is first checked for its condition: bearings, shaft alignment, fan balance, belts, and pump cavitation. Lowering fan or pump speed with a speed controller reduces flow noise, but that setting change affects flow rate and is a decision for the air conditioning or pump technician.
On the path, repairs for structure-borne noise include replacing or readjusting failed mounts, removing transport locking bolts, fitting flexible connectors on pipes and ducts, replacing rigid pipe hangers with spring hangers, and removing rigid bridges. Repairs for airborne noise include sealing gaps and pipe penetrations with suitable material, fitting a tight door threshold, installing duct silencers, and adding absorptive material in the machine room. Penetrations in fire-rated walls or floors are sealed with material that meets fire protection requirements (Chapter 17 on fire protection).
At the receiver, interim measures are not selling the most affected room or changing the machine’s schedule so that it does not run during sleeping hours, if the system allows. After a repair, the measurement is repeated at the same point and under the same conditions, and the before and after results are kept in the asset record. If the result is still above the guideline, the problem lies in the design and is handed over to an acoustics consultant.
Worked example
The numbers in the examples below are practice numbers unless their origin is stated.
Example 1: three machines in one room. A pump, an exhaust fan, and a compressor in one machine room produce 78, 75, and 72 dB(A) respectively at the measuring point. The total level is dB(A). If the compressor is repaired until silent, the total becomes dB(A), a drop of less than 1 dB. If the pump is the one repaired, the total becomes dB(A), a drop of more than 3 dB. Two identical pumps of 60 dB(A) each produce dB(A), not 120 dB(A).
Example 2: background noise in the room. In the room in the opening case, the pump running reads 41 dB(A) and the pump off reads 37 dB(A). The pump’s own sound is dB(A). The difference between total and background is only 4 dB, so this result is an estimate. If the next night the background reads 33 dB(A) and the pump running still reads 41 dB(A), the pump’s sound becomes dB(A), more trustworthy because the difference is 8 dB.
Example 3: cooling tower and balcony. A cooling tower on the roof produces 72 dB(A) at a distance of 3 m. The nearest guest room balcony is 24 m away with no barrier. Assuming a point source in the open air, the level at the balcony is dB(A). Getting down to 50 dB(A) requires a reduction of dB, that is, m; if the distance cannot be increased, a barrier or a silencer on the tower is considered.
Example 4: good wall, door with a gap. An AHU room next to a meeting room has a level of 80 dB(A). The separating wall gives a level difference of 45 dB, so through the wall alone the meeting room receives dB(A). The connecting door with a gap at the bottom gives a difference of only 35 dB, so through the door dB(A) enters. The combination is dB(A), almost entirely from the door. Sealing the door gap until its difference is 45 dB lowers the combination to dB(A).
Example 5: springs and rubber under a pump. A pump runs at 1,450 rpm, that is, Hz. With springs of 25 mm deflection, Hz, , and , that is, about 98 percent of the force is blocked. If the springs are fully compressed and the pump effectively sits on rubber pads with 2 mm deflection, Hz, , and ; the transmitted force is about 16 times larger. The same rubber pads under a 600 rpm (10 Hz) fan give and : the mount amplifies the force.
Example 6: energy average at night. In a guest room, a one-hour measurement is divided into six 10-minute intervals with of 32, 32, 45, 45, 32, and 32 dB(A); the two middle intervals are when the pump is running. The one-hour dB(A), whereas the plain average of the decibel figures is only dB(A). Both figures are well above the WHO guideline of 30 dB for bedrooms, and the 45 dB(A) intervals already equal the limit of 45 dB, so the maximum level while the pump runs also needs to be recorded.
Stop conditions
- New sound or vibration from a machine accompanied by a burning smell, smoke, excessive heat, or the sound of metal striking metal: do not approach rotating parts; stop the machine only through its button or operating procedure if that is within your authority, then report to the mechanical technician and the operator on duty (Chapter 14 · Mechanical & Mechatronics on machine condition monitoring).
- New cracks in a concrete base, beam, or floor slab near a vibrating machine, or loose anchor bolts: do not assess the strength of the structure yourself; report to the building manager and a structural engineer.
- The repair requires lifting a machine, replacing the springs or mounting pads of a chiller, generator set, AHU, or large pump, or disconnecting pipes: hand over to a mechanical technician or contractor working with a lifting plan, a work permit, and energy isolation (Chapter 76 · Electrical & Control on safe work and Chapter 4 · Safety on non-electrical energy isolation).
- The measurement has to be taken in a very noisy machine room or near rotating parts: enter only with a permit and hearing protection according to Chapter 7 · Safety, and do not open belt, coupling, or fan guards.
- The measuring point is on the roof, at the edge of the building, or near a cooling tower: do not go up without a work-at-height permit and an assigned companion.
- A guest complains of headaches, being unable to sleep for days, or ringing in the ears: do not give any health judgment; refer them to a doctor or the hotel medical team, record the complaint, and move the guest through the front desk.
- The repair requires changing fan or pump speed, or a schedule in the building management system, that serves hospital rooms or special rooms: hand over to the air conditioning technician and the building management system operator (Chapter 30 on air conditioning of special hospital rooms).
- The noise source is a fire pump, an emergency generator set, or a fire protection alarm: do not switch it off, move its test schedule, or muffle the alarm without a decision from the fire safety manager (Chapter 17 on fire protection).
Common misinterpretations
Guess what’s wrong first, then open the explanation.
Common misconception
Two 60 dB machines produce 120 dB.
Why is it wrong?
Decibels are added by their energy. Two equal sources add 3 dB, so two 60 dB(A) machines produce 63 dB(A).
Common misconception
The reading on the meter is the sound of that machine.
Why is it wrong?
The meter reads the machine’s sound plus the background noise. The machine’s own sound is calculated by subtracting the background energy, and the result can be trusted only if the difference between them is large enough.
Common misconception
Thicker and harder rubber always isolates better.
Why is it wrong?
Isolation depends on the ratio of the machine frequency to the natural frequency of the mount. A mount that is too stiff for a slow machine can sit near resonance and actually amplify the transmitted force.
Common misconception
The average decibel level is found by adding up and dividing.
Why is it wrong?
The average of a fluctuating sound is calculated by energy as . A plain average underestimates short loud sounds, such as a pump that starts occasionally.
Common misconception
Meeting the quality standard means guests will not be disturbed.
Why is it wrong?
The 60 dB(A) standard for public places is far above the WHO guideline for bedrooms, and dB(A) attenuates low-frequency hum. Guest complaints are still investigated even when the reading is below the standard.
Links to other chapters
Decibel addition and the inverse square law are derived in Chapter 14 · Physics on mechanical waves and sound, and are used for worker exposure in Chapter 7 · Safety. The theory of flexible mounts is in Chapter 22 · Physics, while pipe vibration and pipe supports are in Chapter 9 · Fluids & Thermal. The sources most often complained about in buildings are covered as equipment in Chapter 9 on building pumps, Chapter 16 · Fluids & Thermal on air handling units, Chapter 15 · Fluids & Thermal on fan coil units in hotel rooms, Chapter 17 · Fluids & Thermal on chillers, Chapter 18 · Fluids & Thermal on cooling towers, and Chapter 36 · Electrical & Control on generator sets. Equipment schedules and logs are read in Chapter 33 on alarms, trends, and schedules in the BMS.
Exercises and worked solutions
The numbers in the exercises are for practice.
Try to answer first, then open the worked solution.
Two identical exhaust fans on the roof each produce 68 dB(A) at a balcony. One fan is switched off for repair. What is the level at the balcony, and is the change easily noticed by the guest?
Check my answer
See the worked solution
Two fans produce dB(A), so the level at the balcony drops from 71 dB(A) to 68 dB(A). A change of 3 dB is easily noticed, but the sound is still audible because one fan is still running.
A room measures 39 dB(A) with the fan coil unit running and 37 dB(A) with that unit off. Calculate the sound of the fan coil unit alone and explain how confident the result is.
Check my answer
See the worked solution
The unit’s own sound is dB(A). The difference between total and background is only 2 dB, so an instrument error of 1 dB changes the result by several decibels; the measurement is repeated when the background is quieter.
A generator set produces 85 dB(A) at a distance of 4 m in an open yard. What is its level at a guest room window 32 m away?
Check my answer
See the worked solution
Assuming a point source in the open air, dB(A). Building walls, reflections, and the exhaust direction can change this figure, so the result is a first estimate.
An AHU fan runs at 900 rpm. What is the smallest static deflection for to be at least 3?
Check my answer
See the worked solution
The rotational frequency is Hz, so is at most Hz. The static deflection must be at least mm, which is usually achieved with springs, not thin rubber pads.
A technician finds the chilled water pipe from the chiller clamped directly to the wall of a guest room without spring hangers, even though the chiller stands on good springs. Why does the guest still hear a hum?
Check my answer
See the worked solution
The rigidly clamped pipe becomes a rigid bridge: vibration from the chiller and the water flow travels through the pipe to the guest room wall, bypassing the spring mounts. The fix is a flexible connector on the chiller side and spring hangers on the pipe near the sensitive room.
The manager wants to resolve a room noise complaint by laying a thick carpet in that room. When does this help and when does it not?
Check my answer
See the worked solution
A carpet absorbs sound inside the room and dampens footstep sound from the floor above, so it helps if the problem is reflections or impact sound. A carpet hardly reduces hum entering through the structure from machines or noise entering through gaps, so the source and the path still need to be repaired.
References
External sources
- Peraturan Menteri Kesehatan Nomor 2 Tahun 2023 tentang Peraturan Pelaksanaan Peraturan Pemerintah Nomor 66 Tahun 2014 tentang Kesehatan Lingkunganjdih.kemkes.go.id
- Peraturan Menteri Kesehatan Nomor 3 Tahun 2026 tentang Penanggulangan Penyakitjdih.kemkes.go.id
- Guidelines for community noiseiris.who.int
- P100 Facilities Standards for the Public Buildings Service, October 2021 with 2022 Addendumgsa.gov
- 17.3 Sound Intensity - University Physics Volume 1openstax.org
Revision history
| Date | Version | Change |
|---|---|---|
| November 14, 2026 | 1 | First published |
How to cite
Kurnia (2026). Noise and vibration from building equipment: machine noise sources, decibels and how to add them, vibration isolators, guest complaints, measurement, and repair. ARSTEMA Academy. Revised November 14, 2026. arstema.com/en/academy/konsep/kebisingan-dan-getaran-peralatan-gedung-sumber-bising-mesin-desibel-dan-penjumlahannya-peredam-getaran-keluhan-tamu-pengukuran-serta-perbaikan
Self-check · 3 questions
Check your understanding before moving on
Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.
Two identical exhaust fans on the roof each produce 68 dB(A) at a balcony. One fan is switched off for repair. What is the level at the balcony, and is the change easily noticed by the guest?
A room measures 39 dB(A) with the fan coil unit running and 37 dB(A) with that unit off. Calculate the sound of the fan coil unit alone and explain how confident the result is.
A generator set produces 85 dB(A) at a distance of 4 m in an open yard. What is its level at a guest room window 32 m away?