By Kurnia · Published November 14, 2026 · Version 1 · 20 min read
Indoor air quality
carbon dioxide as a ventilation indicator, fine particles, volatile organic compounds and formaldehyde, humidity, measuring instruments and records, and follow-up
Participants in a hotel meeting room grow drowsy and complain that the air is stuffy, and a portable monitor shows carbon dioxide at 1,800 ppm because the outdoor air damper has been closed to its minimum position. This chapter covers indoor air quality from the building technician’s side: the indoor air quality standards in the appendix to Permenkes 2/2023 and the status of that regulation, carbon dioxide as an indicator of adequate outdoor air rather than a toxicity limit, PM2.5 fine particles, volatile organic compounds and formaldehyde with their unit conversion, temperature and humidity, types of measuring instruments and the limits of their accuracy, how to place instruments and record results, and follow-up in order from ventilation and sources to reporting. Comparison values from WHO, the UK HSE, and the US EPA are given with the name of each body. The chapter gives no health diagnosis; occupants’ complaints are referred to a doctor or company doctor.
A meeting room on the third floor of a hotel is used for a full-day seminar by 40 participants. Toward late afternoon, the organizers report that participants are drowsy and complain that the room is stuffy, even though the air conditioning temperature has already been lowered. A technician brings a portable carbon dioxide monitor and reads about 1,800 ppm in the middle of the room, whereas in the morning before the seminar the figure was about 450 ppm. The appendix to Permenkes 2/2023 (a Minister of Health regulation) lists carbon dioxide at 1,000 ppm as an 8-hour average for indoor air in public places and facilities, including hotels. An inspection of the air handling unit finds the outdoor air damper set to its minimum position since an energy-saving program. The figure of 1,800 ppm does not mean that the room air is poisonous. It says that too little outdoor air is entering for the number of people inside, and what needs fixing is the ventilation.
Scope
This chapter covers indoor air quality from the building technician’s side: reading the quality standards; measuring carbon dioxide, fine particles, volatile organic compounds, formaldehyde, temperature, and humidity; recording results; and following up by checking ventilation and pollutant sources. The Indonesian standard used is the SBMKL (Standar Baku Mutu Kesehatan Lingkungan, environmental health quality standard) for indoor air in the appendix to Permenkes 2/2023. As of November 2026, JDIH Kemenkes (the Ministry of Health legal documentation network) records Permenkes 2/2023 as no longer in force because it was revoked by Permenkes 3/2026, but Article 99 of Permenkes 3/2026 excludes, among others, Article 12 and its appendix from the revocation; check its latest status with the person responsible for environmental health in the building. Figures from WHO, the UK HSE, and the US EPA are used for comparison and are given with the name of each body.
This chapter gives no health diagnosis. Complaints from occupants or guests, such as dizziness, shortness of breath, stinging eyes, or nausea, are recorded and then referred to a doctor, a company doctor, or the building’s medical team; the technician does not infer the cause of an illness from instrument readings. Bioaerosols and airborne microbes are covered in Chapter 10 · Biology & Microbiology, mold in buildings in Chapter 9 · Biology & Microbiology, respiration, carbon monoxide, and workplace air in Chapter 36 · Biology & Microbiology, air conditioning of special hospital rooms in Chapter 30, air handling units and their filters in Chapter 16 · Fluids & Thermal, ppm concentrations and dilution ventilation in Chapter 11 · Chemistry on hazardous gases, psychrometrics and condensation in Chapter 16 on ventilation of laundry rooms and kitchens, safety of paint materials in Chapter 37 on building paints and coatings, and instrument calibration in Chapter 61 · Electrical & Control. Asbestos and radon are not covered, except asbestos as a stop condition. Changing damper, fan, or schedule settings in the building management system is done only by staff who are authorized for that system.
Indoor air and its quality standards
Indoor air quality is the condition of the air inside a building as it relates to the health and comfort of its occupants. Permenkes 2/2023 defines indoor air as the air inside a building or structure, particularly as it relates to the health and comfort of its occupants, and sets its health requirements: there is air circulation and exchange; it is free from cigarette smoke, kitchen smoke, and vehicle exhaust; it has no odor; and it is free from dust.
The appendix to that regulation contains the SBMKL for indoor air in residential areas, recreation places, and public places and facilities, which include accommodation services such as hotels and restaurants. The table below lists the parameters covered in this chapter.
| Parameter | SBMKL | Notes |
|---|---|---|
| Temperature | 18 to 30 °C | depends on room use |
| Humidity | 40 to 60 %RH | depends on room use |
| PM2.5 | 25 μg/m³ | 24-hour duration, upper limit |
| PM10 | 70 μg/m³ | 24-hour duration, upper limit |
| Carbon dioxide (CO₂) | 1,000 ppm | 8 hours, additional chemical parameter |
| Formaldehyde | 0.1 ppm | 30 minutes |
| Volatile organic compounds as CH₄ | 3 ppm | 8 hours |
For health care facilities, the same appendix contains a separate table, including formaldehyde at 100 µg/m³ as a 30-minute average and total volatile organic compounds at 3 ppm as an 8-hour average. The carbon dioxide figure in the hospital table is printed as “1 ppm” for 8 hours, a value far below the outdoor air concentration and therefore impossible to meet; that figure is not used until it has been confirmed with the person responsible for environmental health at the hospital. Air conditioning of operating rooms and isolation rooms follows Chapter 30.
These standards are used for surveillance, not for judging a person’s health. The same appendix calls for internal surveillance in public places and facilities at least once a year for physical and chemical parameters, with the results recorded on the internal surveillance form. Official decisions are based on measurements by an accredited laboratory; the technician’s portable instruments are useful for finding problems and checking the results of repairs.
Carbon dioxide as a ventilation indicator
When little outdoor air enters, carbon dioxide from the occupants’ breath builds up in the room. The UK HSE states that a build-up of carbon dioxide indicates that ventilation needs improving, that 1,000 ppm is roughly equivalent to 10 liters per second of outdoor air per person, and that levels consistently above 1,500 ppm in an occupied room indicate poor ventilation. HSE also cautions that carbon dioxide measurements are only a broad guide to ventilation and do not demonstrate that any level is safe.
A ventilation indicator is a quantity that is measured not because it is hazardous in itself but because it shows how much outdoor air is diluting the pollutants from occupants. Carbon dioxide works as an indicator because its source is proportional to the number of people. For a room whose air is well mixed and at steady state, a carbon dioxide balance gives:
where and are the indoor and outdoor carbon dioxide concentrations in ppm, is the number of people, is the rate of carbon dioxide exhaled by one person in L/s, and is the outdoor air rate in L/s. The value of depends on body size and activity, so the result is an estimate.
Before steady state, the concentration rises toward its steady-state value according to:
where is the initial concentration, is the room volume in m³, is in m³/s, and is the time constant in seconds. A large room with little outdoor air is slow to reach its steady-state concentration (Example 2).
A concentration of 1,000 ppm is not a toxicity limit. Permenaker 5/2018 (a Minister of Manpower regulation) lists a threshold limit value for carbon dioxide for workers of 5,000 bds (ppm) and a short-term exposure value of 30,000 bds, far above the levels usually read in a meeting room. The 1,000 ppm standard for public rooms is therefore read as a sign of adequate outdoor air: when carbon dioxide is high, other pollutants from occupants and furnishings are also poorly diluted. There is an important exception: rooms that contain a source of carbon dioxide, such as a dry ice store, beverage carbon dioxide cylinders, or a room protected by a carbon dioxide gas extinguishing system, carry a different asphyxiation hazard and are not a matter for ventilation monitoring (Stop condition 2). HSE also states that carbon dioxide monitors are not suitable in areas with air cleaning units, because these units remove contaminants but do not remove carbon dioxide or improve ventilation.
PM2.5 fine particles
Fine particulate matter (PM2.5) is solid or liquid particles in air with a diameter of 2.5 micrometers or smaller. The US EPA states that particles indoors consist of particles of outdoor origin that migrate indoors and particles from indoor sources, such as cooking, combustion including candles and cigarettes, and some hobbies, and that their levels depend on outdoor levels, infiltration, the type of ventilation and filtration, indoor sources, and occupant activities. In buildings without strong sources, indoor levels would be expected to be the same as or lower than outdoor levels.
The Indonesian SBMKL for PM2.5 in public places and facilities is 25 μg/m³ for a 24-hour duration (table above). WHO set its 2021 air quality guideline for PM2.5 at 15 μg/m³ as a 24-hour average and 5 μg/m³ as an annual average, and states that the guidelines apply to outdoor and indoor environments but not to occupational settings. Both figures use a 24-hour average, so a single instantaneous reading taken while the restaurant kitchen is frying is not compared directly with the standard (Example 4).
For the technician, high indoor PM2.5 leads to three checks: whether the outdoor level is in fact high, whether the air handling unit filters are seated tightly and not torn (Chapter 16 · Fluids & Thermal on air handling units), and whether there is an indoor source such as kitchen smoke not captured by the exhaust hood or dusty renovation work. The ratio of indoor to outdoor concentration helps separate the two sources: a ratio well below 1 shows that the building envelope and filters are working, while a ratio above 1 points to an indoor source.
Volatile organic compounds and formaldehyde
Volatile organic compounds (VOCs) are organic compounds emitted as gases from solids or liquids. The US EPA states that concentrations of many of these compounds are consistently higher indoors, up to ten times outdoor levels, and that their sources include paints and solvents, cleansers and disinfectants, air fresheners, building materials and furnishings, copiers and printers, and glues. During and for several hours after certain activities such as paint stripping, levels may reach 1,000 times background outdoor levels. EPA also notes that not much is known about the health effects at the levels usually found in homes.
Formaldehyde is a volatile organic compound emitted by, among other things, furniture made of particleboard and plywood bonded with formaldehyde resins, paints, glues, and cleaning products. The Indonesian SBMKL for public places and facilities gives it as 0.1 ppm for 30 minutes, and for health care facilities as 100 µg/m³ for 30 minutes. WHO sets a short-term guideline of 0.1 mg/m³ as a 30-minute average to prevent sensory irritation in the general population, and states that this guideline also prevents long-term effects, including cancer. The two figures use different units. WHO gives the conversion factor for formaldehyde at 20 °C and 760 mmHg:
so 0.1 ppm is equivalent to 0.125 mg/m³, and 0.1 mg/m³ is equivalent to about 0.08 ppm (Example 3).
For volatile organic compounds, the most effective action is source control: choosing low-emission materials, giving newly painted or newly furnished rooms time to release their emissions under increased ventilation before guests occupy them, and storing solvents and cleaning products in an enclosed, ventilated room. Ventilation dilutes the remaining emissions; the dilution formula is the same as the carbon dioxide balance, , where is the emission rate (Example 6). The appendix to Permenkes 2/2023 also calls for not using building materials, furniture, and household products that contain hazardous chemicals such as lead, asbestos, and formaldehyde.
Temperature and humidity
Relative humidity is the ratio of the water vapor pressure in air to the saturation vapor pressure at the same temperature, expressed as a percentage. The Indonesian SBMKL requires an indoor air temperature of 18 to 30 °C and humidity of 40 to 60 percent. The same appendix suggests, when humidity is below 40 percent, opening windows, changing air circulation, or using a humidifier, and when it is above 60 percent, adding natural light, changing air circulation, or using a device that lowers humidity. The US EPA, in its mold guidance for homes, recommends keeping indoor humidity below 60 percent, ideally 30 to 50 percent, and names condensation on windows, walls, or pipes as a sign of high humidity.
In air-conditioned buildings in a tropical climate, high humidity usually appears in rooms where the cooling coil runs for too short a time, for example rooms with an oversized unit or rooms that receive humid outdoor air without treatment. Prolonged high humidity promotes condensation and mold, which are covered in Chapter 9 · Biology & Microbiology on mold in buildings, and how to read the dew point is in Chapter 16 on ventilation and air conditioning of laundry rooms and kitchens.
Measuring instruments and how to place them
Every portable measuring principle has its limits. For carbon dioxide, HSE recommends non-dispersive infrared (NDIR) monitors as the most appropriate portable devices. Fine particles are generally measured by portable instruments using light scattering, which count particles and estimate their mass, whereas the gravimetric method, which weighs a filter, is the basis of reference measurement. Low-cost volatile organic compound sensors usually display a total or an index without distinguishing the compounds, so they cannot replace laboratory analysis of formaldehyde.
The US EPA notes several limitations of low-cost air sensors: data can be systematically biased high or low, low or high temperatures and high humidity can cause inaccurate readings, sensors may require field calibration, and many gas sensors become less sensitive over time, some being usable for only one to two years. Readings from low-cost sensors are therefore used to see patterns, not to declare that a standard is met or exceeded.
Where the instrument is placed determines what its reading means. HSE recommends placing carbon dioxide monitors at head height, away from windows, doors, and air supply openings, and more than 50 cm from people because their exhaled breath contains carbon dioxide. Snapshot readings can be misleading; HSE recommends several measurements throughout the day while the room is occupied, and recording the concentration, the number of occupants, and the type of ventilation in use. Large rooms need more than one measuring point. A simple calibration check is to read the instrument in outdoor air away from vehicle exhaust and compare it with a reference instrument; a large difference is a reason to send the instrument for calibration according to Chapter 61 · Electrical & Control on instrument calibration.
Records and follow-up
A useful measurement record contains the date and time, the room and measuring point, the number of people, the ventilation condition (damper position, fan speed, windows), the parameter and its value, the instrument used and its calibration date, the name of the person measuring, and any complaints reported with their times. Complaints are recorded as reported, for example “participants complain the room is stuffy and they feel drowsy,” without writing medical conclusions. Carbon dioxide data from the building management system are read as trends (Chapter 33 on alarms, trends, and schedules in the BMS).
Follow-up is ordered from the most likely and cheapest to check. First, ventilation: whether the outdoor air damper is open as designed, the supply and exhaust fans are running, the filters are not clogged, and the operating schedule matches the hours the room is used. Second, sources: smoking, kitchen smoke, painting or gluing work, cleaning products, new furniture, or a water leak wetting the ceiling. Third, room load: a number of people exceeding the room’s ventilation design. After a repair, the measurement is repeated under the same conditions.
The appendix to Permenkes 2/2023 states that follow-up recommendations are given to the manager or person in charge when air quality deviates from the standard, and that internal surveillance results are reported to the district or city health office. In a building, the technician hands the records to the engineering supervisor and the person responsible for environmental health or K3 (occupational safety and health), who decide on laboratory testing, closing the room, or changing the ventilation. If an occupant is ill, the medical decision belongs to a doctor or company doctor.
Worked example
The numbers in the examples below are practice numbers unless their origin is stated. A carbon dioxide rate per person of L/s and an outdoor concentration of 420 ppm are used in Examples 1, 2, and 5.
Example 1: outdoor air per person from a carbon dioxide reading. A meeting room holds 40 people. To maintain 1,000 ppm, the outdoor air required is L/s, that is, L/s per person. The afternoon reading of 1,800 ppm means L/s, only L/s per person. Outdoor air needs to increase by about times, which matches the finding of the outdoor air damper at its minimum position.
Example 2: a reading in the first half hour is misleading. The same room has a volume of 300 m³ and an outdoor air rate of 0.145 m³/s. Its time constant is s, about 34.5 minutes, and its steady-state concentration is about 1,800 ppm. Starting from 420 ppm, after 30 minutes the concentration reaches ppm, and after 1 hour ppm. Someone who measures 30 minutes after the meeting starts will record about 1,200 ppm and underestimate the afternoon problem.
Example 3: formaldehyde in ppm and mg/m³. A laboratory result in a newly furnished hotel room is 0.09 ppm as a 30-minute average. Against the SBMKL for public places and facilities of 0.1 ppm, the result complies. In mg/m³, mg/m³, above the WHO guideline of 0.1 mg/m³, and if the room were a hospital ward with a standard of 100 µg/m³, the result would also exceed it. Conversely, the 0.1 ppm standard equals mg/m³, and the WHO guideline equals ppm. The report gives the result in the laboratory’s original unit, the standard used, and the conversion.
Example 4: the 24-hour average of PM2.5. A monitor in a lobby near a restaurant records four-hour averages of 18, 22, 35, 48, 30, and 20 μg/m³. Its 24-hour average is μg/m³, above the SBMKL of 25 μg/m³, even though four of the six blocks are below 35. The average outdoor level that day was 40 μg/m³, so the indoor to outdoor ratio is . The peak of 48 μg/m³ coincides with cooking hours, so the first check is the kitchen exhaust hood and the air pressure between the kitchen and the lobby.
Example 5: correcting an instrument offset. Before a survey, a carbon dioxide monitor is placed in outdoor air together with a reference instrument; the monitor reads 510 ppm and the reference instrument 425 ppm, a difference of ppm. A reading of 1,385 ppm in an office is corrected to ppm. That value is above 1,000 ppm but below 1,500 ppm, so the ventilation of that room is recorded as needing inspection. The 85 ppm difference is recorded, and the instrument is scheduled for calibration.
Example 6: diluting emissions from new furniture. A 75 m³ room contains 30 m² of new furniture that releases formaldehyde at 0.5 mg/h per m², so mg/h. With outdoor air of one room volume per hour, m³/h and mg/m³. For to be no more than 0.1 mg/m³, must be at least m³/h, that is, two room volumes per hour. With 2.5 room volumes per hour, mg/m³. It is better not to sell the new room until emissions have dropped and measured results meet the standard.
Stop conditions
- An occupant or guest faints, has severe shortness of breath or chest pain, or several people in the same room complain of dizziness and nausea at the same time: stop measuring, call the medical team or company doctor and the building safety officer, and do not infer the cause from instrument readings.
- A carbon monoxide detector alarm sounds, exhaust gas can be smelled indoors, or the carbon dioxide level is very high in a room that contains dry ice, carbon dioxide cylinders, or a gas extinguishing system: get people out, do not go back in, and hand over to the K3 officer and the fire department (Chapter 36 · Biology & Microbiology on carbon monoxide and workplace air).
- A strong solvent odor from painting, gluing, or floor coating work in a room being used by guests or patients: stop using that room and report to the building manager and the K3 officer (Chapter 37 on building paints and coatings).
- Extensive visible mold, a strong musty odor, or a ceiling wet from a leak: do not clean extensive mold without a procedure and protective equipment; hand over to the designated team according to Chapter 9 · Biology & Microbiology on mold in buildings.
- Dust from removing old ceilings, insulation, or flooring that may contain asbestos: stop the work and the use of that area, do not sweep it or vacuum it with an ordinary vacuum cleaner, and hand over to a contractor authorized for asbestos.
- Deviations in temperature, humidity, pressure, or particles in an operating room, isolation room, or intensive care unit: do not change the settings yourself; report to the hospital air conditioning technician and the infection prevention and control committee (Chapter 30 on air conditioning of special hospital rooms).
- A laboratory result for formaldehyde or volatile organic compounds exceeds the standard in a guest room or ward: the room is not used until the person responsible for environmental health decides.
- The repair would require changing the outdoor air damper, fan speed, or schedule settings in a building management system that is not within your authority: hand over to the air conditioning technician or the building management system operator (Chapter 16 · Fluids & Thermal on air handling units and Chapter 32 on building management systems).
Common misinterpretations
Guess what’s wrong first, then open the explanation.
Common misconception
Carbon dioxide at 1,000 ppm is a toxicity limit.
Why is it wrong?
The figure of 1,000 ppm in the standard for public rooms is an indicator of adequate outdoor air. The threshold limit value for workers in Permenaker 5/2018 is 5,000 ppm; the problem at 1,800 ppm in a meeting room is a lack of outdoor air, not carbon dioxide poisoning.
Common misconception
A portable air cleaner lowers carbon dioxide.
Why is it wrong?
An air cleaner filters particles but does not remove carbon dioxide or add outdoor air. A carbon dioxide reading in a room with an air cleaner still describes ventilation, not how clean the air is.
Common misconception
A low-cost sensor reading is the same as a laboratory result.
Why is it wrong?
Low-cost sensors can be biased, are affected by temperature and humidity, and become less sensitive over time. Their readings are used to see patterns; a decision that a standard is met or exceeded is made from calibrated or laboratory measurements.
Common misconception
An air-conditioned room must have fresh air.
Why is it wrong?
Air conditioners and fan coil units mainly cool the air circulating in the room. Outdoor air comes from the outdoor air damper or other ventilation; if that path is closed, a cold room can still be stuffy.
Common misconception
No odor means formaldehyde is safe.
Why is it wrong?
The sense of smell cannot be used to judge concentration. Some people may not smell a concentration above the guideline, and conversely some people smell formaldehyde below the guideline; the concentration is known from measurement.
Links to other chapters
The dilution balance in this chapter is the same as the dilution ventilation in Chapter 11 · Chemistry on hazardous gases. A shortage of outdoor air often starts at the air handling unit (Chapter 16 · Fluids & Thermal), and its monitoring is covered in Chapter 32 on building management systems. If complaints concern airborne transmission of disease, Chapter 10 · Biology & Microbiology on bioaerosols and Chapter 28 · Biology & Microbiology on respiratory infections are the basis; if they concern damp and musty odors, Chapter 9 · Biology & Microbiology on mold. How the body responds to carbon dioxide and carbon monoxide is covered in Chapter 36 · Biology & Microbiology.
Exercises and worked solutions
The numbers in the exercises are for practice.
Try to answer first, then open the worked solution.
A training room holds 25 people with a steady-state reading of 1,300 ppm. With L/s per person and outdoor air at 420 ppm, how much outdoor air is there per person?
Check my answer
See the worked solution
From the steady-state balance, L/s, that is, L/s per person. This is below the roughly 10 L/s per person that HSE equates with 1,000 ppm, so the room’s outdoor air damper and supply fan need inspection.
The manager wants to install an air cleaner in a meeting room that reads 1,600 ppm so that the reading goes down. How does the technician respond?
Check my answer
See the worked solution
An air cleaner does not remove carbon dioxide or add outdoor air, so the reading of 1,600 ppm will not drop because of it. What needs fixing is the outdoor air supply, and an air cleaner is relevant only if the problem is particles.
A laboratory result for formaldehyde in a hospital waiting room is 0.09 mg/m³. Compare it with the standard for health care facilities and with the standard for public places and facilities.
Check my answer
See the worked solution
The standard for health care facilities is 100 µg/m³, that is, 0.1 mg/m³, so 0.09 mg/m³ complies. In ppm, ppm, also below the standard for public places and facilities of 0.1 ppm; the result is still recorded in its original unit together with the standard used.
A humidity record for a guest room over 12 hours, one reading per hour, shows 5 readings above 60 percent. For what percentage of the time was the room above the standard, and what is checked first?
Check my answer
See the worked solution
The room was above 60 percent for percent of the observation time. The first check is how the room’s air conditioning works, including whether the unit cycles off too often or is oversized, followed by signs of condensation and mold according to Chapter 9 · Biology & Microbiology.
A guest calls and says they have been dizzy since entering a newly painted room. What does the technician do?
Check my answer
See the worked solution
The technician does not judge the cause of the dizziness; the guest is referred to the medical team or hotel doctor and moved to another room through the front desk. That room is not sold again until its ventilation has been increased and the person responsible for environmental health has decided whether formaldehyde and volatile organic compounds need to be measured.
Why is a carbon dioxide monitor not placed on the table directly in front of meeting participants?
Check my answer
See the worked solution
People’s breath contains concentrated carbon dioxide, so an instrument that is too close reads higher than the room air. HSE recommends a distance of more than 50 cm from people, at head height, and away from windows, doors, and supply openings, so that the reading represents the room.
References
External sources
- Peraturan Menteri Kesehatan Nomor 2 Tahun 2023 tentang Peraturan Pelaksanaan Peraturan Pemerintah Nomor 66 Tahun 2014 tentang Kesehatan Lingkunganjdih.kemkes.go.id
- Peraturan Menteri Kesehatan Nomor 3 Tahun 2026 tentang Penanggulangan Penyakitjdih.kemkes.go.id
- Peraturan Menteri Ketenagakerjaan Nomor 5 Tahun 2018 tentang Keselamatan dan Kesehatan Kerja Lingkungan Kerjajdih.kemnaker.go.id
- WHO guidelines for indoor air quality: selected pollutantsiris.who.int
- WHO global air quality guidelines: particulate matter (PM2.5 and PM10), ozone, nitrogen dioxide, sulfur dioxide and carbon monoxideiris.who.int
- Using CO2 monitors - Ventilation in the workplacehse.gov.uk
- Volatile Organic Compounds' Impact on Indoor Air Qualityepa.gov
- Indoor Particulate Matterepa.gov
- A Brief Guide to Mold, Moisture and Your Homeepa.gov
- Frequent Questions About Air Sensorsepa.gov
Revision history
| Date | Version | Change |
|---|---|---|
| November 14, 2026 | 1 | First published |
How to cite
Kurnia (2026). Indoor air quality: carbon dioxide as a ventilation indicator, fine particles, volatile organic compounds and formaldehyde, humidity, measuring instruments and records, and follow-up. ARSTEMA Academy. Revised November 14, 2026. arstema.com/en/academy/konsep/kualitas-udara-dalam-ruang-karbon-dioksida-sebagai-penanda-ventilasi-partikel-halus-senyawa-organik-mudah-menguap-dan-formaldehida-kelembapan-alat-ukur-dan-pencatatan-serta-tindak-lanjut
Self-check · 3 questions
Check your understanding before moving on
Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.
A training room holds 25 people with a steady-state reading of 1,300 ppm. With L/s per person and outdoor air at 420 ppm, how much outdoor air is there per person?
The manager wants to install an air cleaner in a meeting room that reads 1,600 ppm so that the reading goes down. How does the technician respond?
A laboratory result for formaldehyde in a hospital waiting room is 0.09 mg/m³. Compare it with the standard for health care facilities and with the standard for public places and facilities.