    Buildings & Facilities · Chapter 30Applied

    By Kurnia · Published November 11, 2026 · Version 1 · 20 min read

    Ventilation of special hospital rooms

    operating rooms, negative and positive pressure isolation rooms, intensive care units, air changes, pressure differentials, HEPA filters, temperature and humidity, and monitoring

    One hour before the first operation, the operating room monitor shows 68 percent humidity and a pressure differential of almost zero after the filters of the air handling unit were replaced over the weekend. This chapter explains the ventilation of special hospital rooms from the building technician’s side: the purpose of ventilation in operating rooms, negative pressure isolation rooms, positive pressure isolation rooms for patients with weakened immunity, and intensive care units; total and outdoor air changes; pressure differentials and offset airflow; anterooms and doors; staged filters and HEPA; temperature and humidity; air clearance time; and daily monitoring, alarms, and records. Indonesian figures come from the annex of Permenkes 7/2019 that Permenkes 3/2026 retains, while CDC figures are written as United States data. Design, testing and balancing, HEPA filter testing, and the decision to use a room are stated to be the authority of designers, competent contractors, the infection prevention and control team, and the clinical team.

    High-risk material

    This material involves real hazards. A concept explanation doesn’t replace site procedures, competency, energy isolation, the latest SDS, or a work permit.

    Section you’re reading: Chapter opening

    At six on Monday morning, one hour before the first operation, the monitor outside operating room 2 of a hospital shows 68 percent humidity and a pressure differential to the corridor of almost zero. Over the weekend, a contractor replaced the filters of the air handling unit serving that room. The head of the operating suite asks the technician on duty whether the room may be used. The decision to use the room lies with the clinical team and the infection prevention and control team, but the data they need come from the technician: how many air changes there are, which way the air flows, whether the filters are sealed, and what the temperature and humidity are compared with the requirements.

    Scope

    This chapter covers the ventilation requirements for special hospital rooms and their monitoring from the building technician’s side. Clinical procedures, the choice of room for a patient, and the decision to use a room are not covered. Indonesian figures are taken from the annex of Permenkes 7/2019 (Minister of Health Regulation) on Hospital Environmental Health. As of November 2026, Permenkes 3/2026 on Disease Control revokes Permenkes 7/2019 except Articles 3, 10, and 11 together with its annex, so the standard tables in that annex remain in force, even though the JDIH (legal documentation network) of Kementerian Kesehatan (Ministry of Health) records the regulation’s status as not in force.

    Permenkes 40/2022, which once contained a table of requirements for hospital ventilation systems, was revoked by Permenkes 6/2026 on Hospitals. The CDC figures in this chapter come from the 2003 guideline on environmental infection control, which reprints the tables of the 2001 United States hospital design guidelines; those figures are United States data, not Indonesian requirements. Before using them for permits or accreditation, check the latest text and status.

    Bioaerosols, the basics of air changes, HEPA filters, and airflow through door gaps are covered in Chapter 10 · Biology & Microbiology on bioaerosols. Air handling units are in Chapter 16 · Fluids & Thermal, chillers in Chapter 17 · Fluids & Thermal, room air conditioners in Chapter 14 · Fluids & Thermal, respiratory infections in Chapter 28 · Biology & Microbiology, psychrometrics in Chapter 16 on ventilation of laundries and kitchens, and dew point in Chapter 15 · Physics on ideal gases. Anesthetic gas scavenging is in Chapter 29 on medical gas systems, power supply in Chapter 102 · Electrical & Control on electrical systems in medical rooms, and maintenance planning in Chapter 31 on hospital facility management.

    Designing, modifying, testing and balancing the system, resetting pressure differentials and alarms, and leak-testing HEPA filters are work for designers and competent contractors. The decision to use, close, or change the function of a room lies with the infection prevention and control team and the clinical team. The building technician reads the monitors, measures with calibrated instruments when assigned, records, checks doors and door closers, and reports; they do not change settings, silence alarms, or turn the dampers of special rooms without an approved work plan.

    Special rooms and the purpose of their ventilation

    Each special room protects a different party, and that purpose determines the direction of its airflow. The operating room is protected from corridor air, so its air flows outward. The negative pressure isolation room (airborne infection isolation room) keeps the patient’s infectious particles inside the room, so air flows in from the corridor. The positive pressure isolation room, which the CDC guideline calls a protective environment, protects patients with weakened immunity from airborne fungal spores, so clean, filtered air flows out of the room. The intensive care unit (ICU) serves critically ill patients, some of whom are susceptible to infection.

    The annex of Permenkes 7/2019 requires the ventilation of operating rooms and of isolation rooms for patients with reduced immunity to be kept at a slightly more positive pressure, at least 0.10 mbar, than other rooms, the ventilation of infectious disease isolation rooms to be kept more negative than the outside environment, and operating rooms, ICUs, isolation rooms, and sterile rooms to be fitted with HEPA filters. The CDC guideline states the general principle: the ventilation system is designed so that air moves from clean areas to less clean areas.

    CDC also rejects rooms whose airflow can be reversed to switch between protective environment and airborne infection isolation functions. A single switch that changes a room from positive to negative is easily left in the wrong position, and the patient inside is then left unprotected. For patients with weakened immunity who also have an airborne infection, CDC calls for a positive pressure room with an anteroom that maintains the pressure balance and exhausts contaminated air to the outside.

    Total and outdoor air changes

    Air changes per hour (ACH) is the airflow entering or leaving a room in one hour divided by the room volume:

    ACH=QV\text{ACH} = \frac{Q}{V}

    with QQ the airflow (m³/h) and VV the room volume (m³). For negative pressure rooms, WHO calculates ACH from the exhaust airflow; for positive pressure rooms, from the incoming airflow. Outdoor air changes are the part of ACH that comes from fresh outdoor air, not from recirculated air.

    RoomPermenkes 7/2019 (Indonesia)CDC 2003 (United States data)
    Operating roomat least 10 per hour; air velocity 0.3 to 0.4 m/sat least 15 total, at least 3 outdoor air
    Intensive care unitnot statedat least 6 total, 2 outdoor air
    Airborne infection isolationnot statedat least 12 total for new or renovated rooms, 6 for existing rooms; 2 outdoor air
    Protective environmentnot statedat least 12 total, 2 outdoor air

    The Indonesian figures in the table come from Table 7 of the annex of Permenkes 7/2019, and the CDC figures from Table B.2 and the summary of recommendations. WHO uses the same limit for isolation rooms, at least 12 ACH, and for natural ventilation 160 L/s per patient as an hourly average. The notes to CDC Table B.2 explain three other points that are often forgotten. ACH figures are minimum values, and higher values are used when needed to maintain temperature and humidity. ACH may be reduced while a room is unoccupied only if the direction of airflow stays the same and ACH returns to the design value whenever the room is in use. Airflow calculations account for filters becoming dirtier, so that ACH is still achieved up to the time the filters are changed. According to that table, air conditioning units that recirculate air within the room are not used in operating rooms and intensive care units, except HEPA-equipped units inside isolation rooms.

    Pressure differential, offset airflow, and doors

    Pressure differential is the difference in air pressure between a special room and the space next to it, usually a corridor or anteroom. The pressure differential is created by offset airflow, the difference between a room’s supply airflow and exhaust airflow. A positive room is supplied with more air than is exhausted, a negative room is exhausted more than it is supplied, and the difference flows through gaps around doors and walls. The relationship between the airflow difference and the pressure differential across the gaps follows the orifice equation:

    Qoffset=Cd A2 ΔpρQ_\text{offset} = C_d \, A \sqrt{\frac{2\,\Delta p}{\rho}}

    with CdC_d the discharge coefficient of about 0.6, AA the total gap area (m²), Δp\Delta p the pressure differential (Pa), and ρ\rho the air density of about 1.2 kg/m³, as in Chapter 10 · Biology & Microbiology on bioaerosols. Because the pressure differential is proportional to the square of the airflow, raising the pressure differential fourfold requires only twice the offset airflow, but gaps that become twice as large reduce the pressure differential to a quarter (Example 3).

    The limit differs according to the reference. Permenkes 7/2019 gives a minimum of 0.10 mbar, that is, 10 Pa, for operating rooms and isolation rooms for patients with low immunity. CDC gives a minimum of 0.01 inch water gauge, that is, 2.5 Pa, for airborne infection isolation rooms and protective environments, and requires alarmed monitors to be given an allowance so that they do not cause nuisance alarms. For infectious disease isolation rooms, Permenkes 7/2019 only says “more negative” without a figure.

    An anteroom is a small room between the corridor and the isolation room that maintains the pressure balance when one of the doors is opened. CDC calls for isolation rooms and protective environments to have self-closing doors, to be well sealed at windows, doors, supply and exhaust openings, and ceilings, and for any leaks found to be located and repaired. A door wedged open by a trolley undoes all of that, because an open door needs an offset airflow of thousands of cubic meters per hour to hold the same pressure differential.

    Staged filters and HEPA

    A HEPA filter (high-efficiency particulate air filter), in the notes to CDC Table B.2, is a filter with an efficiency of 99.97 percent for particles of 0.3 µm, and protective environments are protected by this filter in their supply airstream. Recirculated room air from isolation rooms is also passed through HEPA filters before it enters other spaces.

    The annex of Permenkes 7/2019 requires the ventilation of sensitive rooms to be fitted with two stages of filtration: a first filter at the outdoor air intake with an efficiency of 30 percent and a second filter, a bacterial filter, of 90 percent. CDC Table B.4 uses the same arrangement for general patient care areas, 30 then 90 percent, and 30 then 99.97 percent for protective environments. In the CDC table, the 30 and 90 percent figures are dust-spot test efficiencies, which differ from HEPA efficiency at 0.3 µm, so the two are not compared directly. Filter ratings and final pressure drop are covered in Chapter 10 · Biology & Microbiology and Chapter 16 · Fluids & Thermal.

    A HEPA filter that is efficient on paper is of no use if air bypasses it through a loose frame or gasket. For that reason, replacing a HEPA filter in a special room is followed by a leak or integrity test by a competent party, and the technician records the date, room number, and test result. Replacing filters also releases trapped dust and microbes, so it is done under the infection prevention team’s procedure, as covered in Chapter 10 · Biology & Microbiology.

    Temperature and humidity

    Table 8 of the annex of Permenkes 7/2019 gives standards for temperature, humidity, and pressure by type of room. Some of its rows are as follows.

    RoomTemperature (°C)Humidity (%)Pressure
    Operating22 to 2740 to 60positive
    ICU22 to 2340 to 60positive
    Emergency20 to 2440 to 60positive
    Sterilization21 to 3040 to 60negative

    CDC Table B.2 gives different United States ranges: operating rooms 20 to 23 °C with humidity of 30 to 60 percent, and intensive care units 21 to 24 °C with the same humidity. Its notes explain that the upper and lower humidity limits do not stand alone: humidity is expected to be at the upper end of the range when the temperature is also at the upper end, and vice versa. Operating room design conditions are developed together with surgeons, anesthesiologists, and nurses, because some procedures require temperatures outside the range.

    High humidity in a cool room brings a risk of condensation. Dew point is the temperature at which water vapor in the air begins to condense on a colder surface (Chapter 15 · Physics on ideal gases). For an air temperature TT (°C) and relative humidity RHRH (fraction), the dew point TdT_d is approximated by the Magnus formula:

    γ=ln⁡RH+17.62 T243.12+T,Td=243.12 γ17.62−γ\gamma = \ln RH + \frac{17.62\,T}{243.12 + T}, \qquad T_d = \frac{243.12\,\gamma}{17.62 - \gamma}

    This formula is accurate enough for ordinary room temperatures. If the surface of a duct, supply grille, or ceiling in an operating room is colder than the dew point of the room air, water drips and mold can grow in the place that should be the cleanest (Example 6).

    Air clearance time after a disturbance

    After a door has been open for a long time, the system has been restarted, or a coughing patient has left the room, the concentration of airborne particles falls exponentially. CDC Table B.1 derives the time from the formula

    t=ln⁡(C1/C2)ACH×60t = \frac{\ln \left( C_1 / C_2 \right)}{\text{ACH}} \times 60

    with tt the time (minutes) and C1/C2C_1/C_2 the ratio of the initial to the final concentration, for example 100 for 99 percent removal and 1,000 for 99.9 percent. The table gives, for example, 18 minutes for 99 percent and 28 minutes for 99.9 percent at 15 ACH, and 23 and 35 minutes at 12 ACH. These figures apply to an empty room with no aerosol source and perfect mixing; in rooms with poor mixing the time is longer.

    CDC uses this time in its recommendations: after a tuberculosis patient is intubated or extubated in the operating room, the doors are not opened until 99 percent of airborne contaminants have been removed, and after system repairs, the air is given enough time to clear before the room is used. For the technician, this means that a special room is not reported ready the moment the fans start again, but once the pressure differential reads normal and the clearance time has passed.

    Monitoring, alarms, records, and the limits of the work

    The annex of Permenkes 7/2019 requires the air temperature and humidity in special areas to be monitored routinely every day and documented in monitoring reports. Air temperature, humidity, airflow, and pressure may be measured in-house with suitable instruments or by an external laboratory with national accreditation. The same annex sets limits for airborne microbial counts: 35 cfu/m³ for an empty operating room, 180 cfu/m³ for an operating room in use, and 10 cfu/m³ for an ultraclean operating room. The schedule for monitoring air quality is written as at least twice a year in one part of the annex and at least once a year in another, so the hospital sets its schedule together with the infection prevention team.

    CDC calls for the pressure of airborne infection isolation rooms to be monitored periodically, preferably daily, with audible manometers or smoke tubes at the door for existing rooms or with a permanently installed monitor, and for the airflow direction of protective environments to be monitored daily with flutter strips or smoke tubes; the results are documented. CDC also calls for emergency power and backup air handling systems to maintain filtration, ACH, and pressure differentials in these rooms, and shutting down systems in office areas to save energy must not disturb the pressure differentials of special rooms. The division of work can be summarized as follows.

    WorkWho does it
    Reading monitors, recording temperature, humidity, and pressure differential, checking door closers, reportingbuilding technician
    Measuring airflow, pressure differential, temperature, and humidity with calibrated instrumentsassigned technician, or an accredited laboratory
    Testing and balancing, resetting pressure differentials and alarms, changing damperscompetent contractor, according to the design
    Replacing HEPA filters and leak-testing themcompetent workers following the infection prevention procedure
    Deciding whether a room may be used, closed, or changed in functioninfection prevention and control team and clinical team

    Worked example

    The numbers in the examples below are practice numbers, unless their origin is stated.

    Example 1: air changes in an operating room. An operating room 7 m by 6 m by 3 m has a volume of 7×6×3=1267 \times 6 \times 3 = 126 m³. A measured supply airflow of 1,800 m³/h gives 1,800/126=14.31{,}800/126 = 14.3 ACH, above the minimum of 10 under Permenkes 7/2019 but below 15 according to CDC data. For 15 ACH, 15×126=1,89015 \times 126 = 1{,}890 m³/h is needed. If outdoor air is 400 m³/h, the outdoor air change rate is 400/126=3.2400/126 = 3.2 ACH. The technician reports both comparisons and the reference the hospital uses, rather than choosing one themselves.

    Example 2: units of pressure differential. Permenkes 7/2019 gives 0.10 mbar. Since 1 mbar = 100 Pa, the value is 0.10×100=100.10 \times 100 = 10 Pa. CDC gives 0.01 inch water gauge; with 1 inch water gauge about 249 Pa, the value is 0.01×249=2.490.01 \times 249 = 2.49 Pa, rounded to 2.5 Pa, that is, 2.5/100=0.0252.5/100 = 0.025 mbar. An operating room monitor reading 4 Pa meets the CDC figure but does not meet 10 Pa under Permenkes 7/2019.

    Example 3: offset airflow for two pressure limits. An operating room has a total door and wall gap of 0.015 m². For 10 Pa, CdA=0.6×0.015=0.009C_d A = 0.6 \times 0.015 = 0.009 m² and

    Q=0.009×2×101.2=0.009×4.08=0.0367 m3/sQ = 0.009 \times \sqrt{\frac{2 \times 10}{1.2}} = 0.009 \times 4.08 = 0.0367 \ \text{m}^3/\text{s}

    that is, 0.0367×3,600=1320.0367 \times 3{,}600 = 132 m³/h. For 2.5 Pa, 2×2.5/1.2=2.04\sqrt{2 \times 2.5/1.2} = 2.04, so Q=0.009×2.04×3,600=66Q = 0.009 \times 2.04 \times 3{,}600 = 66 m³/h, half as much. If the door gasket is damaged and the gap becomes 0.030 m², an offset airflow of 132 m³/h holds only 10/4=2.510/4 = 2.5 Pa.

    Example 4: waiting for clean air after the system restarts. An isolation room with 12 ACH has just restarted after a power outage. To remove 99.9 percent of contaminants with perfect mixing, t=ln⁡1,000/12×60=6.908/12×60=34.5t = \ln 1{,}000/12 \times 60 = 6.908/12 \times 60 = 34.5 minutes, consistent with the 35 minutes in Table B.1. For 99 percent at 15 ACH, t=ln⁡100/15×60=4.605/15×60=18.4t = \ln 100/15 \times 60 = 4.605/15 \times 60 = 18.4 minutes. This time is counted from when ACH and the pressure differential have returned to normal, not from when the power came back.

    Example 5: an isolation room with too few air changes. WHO gives the equivalent of 12 ACH as more than 80 L/s for a room 4 m by 2 m by 3 m. The volume of that room is 24 m³, so 12×24=28812 \times 24 = 288 m³/h, that is, 288/3.6=80288/3.6 = 80 L/s. A hospital isolation room measuring 3.5 m by 4 m by 3 m has a volume of 42 m³, and a measured exhaust airflow of 450 m³/h gives 450/42=10.7450/42 = 10.7 ACH. For 12 ACH, 12×42=50412 \times 42 = 504 m³/h is needed, that is, 140 L/s. This finding is reported to the infection prevention team and the designer.

    Example 6: operating room humidity and the risk of condensation. The morning record for an operating room shows 24 °C and 65 percent humidity. Under Permenkes 7/2019 the temperature is within the range of 22 to 27 °C, but the humidity is above 60 percent; according to CDC data both are outside the range. Its dew point is

    γ=ln⁡0.65+17.62×24243.12+24=−0.431+1.583=1.152\gamma = \ln 0.65 + \frac{17.62 \times 24}{243.12 + 24} = -0.431 + 1.583 = 1.152

    and Td=243.12×1.152/(17.62−1.152)=17.0T_d = 243.12 \times 1.152/(17.62 - 1.152) = 17.0 °C. A cold supply grille below 17 °C will condense. The technician reports the out-of-range humidity and checks whether the cooling coil and dehumidification of the air handling unit are working, as in Chapter 16 · Fluids & Thermal.

    Stop conditions

    1. The monitor of a negative pressure isolation room shows zero or positive, or its alarm sounds: report immediately to the nurse in charge of the room and the infection prevention and control team; do not silence the alarm or change the settings; the door stays closed, and the decision to move the patient lies with the clinical team.
    2. An operating room is not at positive pressure, or its temperature and humidity are outside the range set by the hospital, as a scheduled operation approaches: report to the head of the operating suite and the infection prevention team with the measured figures; do not open the door, wedge the door, or turn the dampers to correct it.
    3. A request has been made to switch off, reduce the airflow of, or modify an air handling unit or exhaust fan serving an operating room, ICU, or isolation room for maintenance: postpone until the work plan has been approved by the infection prevention team and the clinical unit, with backup ventilation or closure of the room arranged.
    4. The work involves replacing HEPA filters, opening the exhaust duct of an isolation room, or entering an exhaust filter plenum: only by competent workers with PPE and the infection prevention team’s procedure; a new filter is not considered functional before it has been leak-tested by a competent party.
    5. There is a request to reverse a room from negative to positive pressure or the other way round by changing settings: do not do it; hand it over to the designer and the infection prevention team.
    6. The door of an isolation room or anteroom is wedged open, or the door closer is broken: report to the nurse in charge and record it; repair of the door closer is given priority before the room is used for an isolation patient.
    7. Dripping water, condensation, or mold on grilles, ducts, or ceilings of an operating room, ICU, or isolation room: report to the infection prevention team and facility management; work above the ceiling of a special room requires a work permit and dust control approved by that team.
    8. After a power outage or repair, the ACH or pressure differential of a special room has not returned to the design values: the room is not reported ready; report the measured figures and wait until the air clearance time has passed and the infection prevention team declares the room usable.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    A cold operating room means its ventilation is good.

    Why is it wrong?

    Temperature is only one requirement. An operating room also needs air changes, positive pressure, sealed filters, and humidity within the range.

    Common misconception

    The CDC figure of 2.5 Pa is the Indonesian requirement.

    Why is it wrong?

    That figure is United States data. Permenkes 7/2019 gives a minimum of 0.10 mbar, that is, 10 Pa, for operating rooms and isolation rooms for patients with low immunity.

    Common misconception

    A room that can be switched between positive and negative is more flexible.

    Why is it wrong?

    CDC states that rooms whose airflow can be reversed to change function are not acceptable, because a wrong setting leaves the patient inside unprotected.

    Common misconception

    Air coming out of a HEPA filter makes the room sterile.

    Why is it wrong?

    HEPA cleans the supply air, but people and activity in the room keep releasing particles. That is why the microbial limit for an operating room in use, 180 cfu/m³, is far above that for an empty room, 35 cfu/m³.

    Common misconception

    ACH can be reduced at night at any time to save energy.

    Why is it wrong?

    According to the notes to the CDC table, ACH may be reduced only while the room is unoccupied, if the airflow direction stays the same and ACH returns to the design value whenever the room is in use.

    The basics of air changes, filters, and airflow through gaps are in Chapter 10 · Biology & Microbiology on bioaerosols, and the diseases that are the reason for isolation rooms are in Chapter 28 · Biology & Microbiology on respiratory infections. The air handling units that supply special rooms are covered in Chapter 16 · Fluids & Thermal, chilled water for their coils in Chapter 17 · Fluids & Thermal, and psychrometrics in Chapter 16. Operating rooms also use anesthetic gas scavenging from Chapter 29 on medical gas systems, their fans need the backup supply covered in Chapter 102 · Electrical & Control on electrical systems in medical rooms, and their monitoring records go into Chapter 31 on hospital facility management.

    Exercises and worked solutions

    The numbers in the exercises are for practice.

    Try to answer first, then open the worked solution.

    1. An ICU room 8 m by 5 m by 3 m is supplied with 700 m³/h. What is its ACH, and how does it compare with CDC data?

      Check my answer
      See the worked solution

      The room volume is 8×5×3=1208 \times 5 \times 3 = 120 m³, so ACH =700/120=5.8= 700/120 = 5.8, slightly below the minimum of 6 in CDC data. Permenkes 7/2019 does not give an ACH for the ICU, so the technician reports the figure together with the reference the hospital uses.

    2. The monitor of a negative isolation room shows minus 1.5 Pa relative to the corridor. How is this read against CDC data, and what does the technician do?

      Check my answer
      See the worked solution

      The direction of airflow is correct, but its magnitude is below the minimum of 2.5 Pa in CDC data. The technician checks whether the doors are closed and the door closers work, records the reading, and reports to the nurse in charge and the infection prevention team without changing the settings.

    3. Why does raising the pressure differential of an operating room from 2.5 Pa to 10 Pa not require four times the offset airflow?

      Check my answer
      See the worked solution

      Airflow through a gap is proportional to the square root of the pressure differential, so four times the pressure differential requires only 4=2\sqrt{4} = 2 times the offset airflow. This holds only if the gaps do not change; a damaged door gasket can cancel the advantage.

    4. An operating room with 15 ACH has just been cleaned after maintenance of the air handling unit. How many minutes until 99.9 percent of contaminants are removed with perfect mixing?

      Check my answer
      See the worked solution

      The time is ln⁡1,000/15×60=6.908/15×60=27.6\ln 1{,}000/15 \times 60 = 6.908/15 \times 60 = 27.6 minutes, consistent with the 28 minutes in CDC Table B.1. In a room with poor mixing the time is longer, so the room is reported ready after that time and after the pressure differential reads normal.

    5. The head of a ward asks for a negative isolation room to be made positive for a month for a transplant patient by changing the fan settings. What is the technician’s answer?

      Check my answer
      See the worked solution

      The technician does not reverse the room by changing settings, because CDC rejects rooms whose airflow can be reversed and a transplant patient needs a HEPA supply and positive pressure that have been designed for that purpose. The request is passed to the infection prevention team and the designer.

    6. The operating room record shows 22 °C and 55 percent humidity. Does it meet Table 8 of Permenkes 7/2019 and the CDC ranges?

      Check my answer
      See the worked solution

      A temperature of 22 °C is within the range of 22 to 27 °C and a humidity of 55 percent is within 40 to 60 percent under Permenkes 7/2019. According to CDC data, 22 °C is within 20 to 23 °C and 55 percent is within 30 to 60 percent, so both are met.

    References

    External sources

    • Peraturan Menteri Kesehatan Nomor 7 Tahun 2019 tentang Kesehatan Lingkungan Rumah Sakitjdih.kemkes.go.id
    • Peraturan Menteri Kesehatan Nomor 3 Tahun 2026 tentang Penanggulangan Penyakitjdih.kemkes.go.id
    • Appendix B. Aircdc.gov
    • Summary of Recommendationscdc.gov
    • Natural ventilation for infection control in health care settingsiris.who.int
    • Peraturan Menteri Kesehatan Nomor 6 Tahun 2026 tentang Rumah Sakitjdih.kemkes.go.id

    Revision history

    DateVersionChange
    November 11, 20261First published

    How to cite

    Kurnia (2026). Ventilation of special hospital rooms: operating rooms, negative and positive pressure isolation rooms, intensive care units, air changes, pressure differentials, HEPA filters, temperature and humidity, and monitoring. ARSTEMA Academy. Revised November 11, 2026. arstema.com/en/academy/konsep/tata-udara-ruang-khusus-rumah-sakit-kamar-operasi-ruang-isolasi-bertekanan-negatif-dan-positif-ruang-rawat-intensif-pertukaran-udara-beda-tekanan-filter-hepa-suhu-dan-kelembapan-serta-pemantauan

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated

    Safety limits still apply. This quiz tests reasoning; it doesn’t authorize mixing, adjusting, dismantling, live measurement, or field action.

    1

    An ICU room 8 m by 5 m by 3 m is supplied with 700 m³/h. What is its ACH, and how does it compare with CDC data?

    2

    The monitor of a negative isolation room shows minus 1.5 Pa relative to the corridor. How is this read against CDC data, and what does the technician do?

    3

    Why does raising the pressure differential of an operating room from 2.5 Pa to 10 Pa not require four times the offset airflow?

    Self-assessment progress0%