    Buildings & Facilities · Chapter 29Applied

    By Kurnia · Published November 11, 2026 · Version 1 · 21 min read

    Hospital medical gas systems

    oxygen, medical compressed air, vacuum, and nitrous oxide, supply sources and manifolds, piping and valve zones, alarms and pressure, outlets, purity testing, and the limits of technician work

    In the early hours of the morning, a low oxygen pressure alarm sounds at the nurses’ station of an intensive care unit, and in the central supply room one side of a manual manifold is already empty. This chapter explains the medical gas and medical vacuum installation system from the hospital building technician’s side: the types of gas under Permenkes 4/2016; supply sources in the form of cylinders, liquid oxygen, concentrators, and medical air compressors; manifolds and the arrangement of the central supply room; copper piping, main valves, zone valves, and emergency valves; the three types of alarm and working pressures; the position and order of outlets; purity requirements; cylinder colors and labels; the fire hazard of oxygen; and testing before use and periodic testing at least once every three years. Installing, modifying, and testing the installation are stated to be work for competent installers and authorized testing institutions, while the building technician reads, records, reports, and stops use.

    High-risk material

    This material involves real hazards. A concept explanation doesn’t replace site procedures, competency, energy isolation, the latest SDS, or a work permit.

    Section you’re reading: Chapter opening

    At two in the morning, the alarm panel at the nurses’ station of the intensive care unit of a district hospital sounds: low oxygen pressure. The nurse on duty phones the building technician. In the central medical gas room, the technician finds the pressure gauge on the right side of the manifold reading almost zero, while the left side is full but its header bar valve is still closed. The manifold is a manual type, which does not change over by itself, and eight patients on the third floor receive oxygen from the same pipeline network. The technician needs to know what the alarm means, whether they are the staff member designated to operate the manifold, and who must be informed.

    Scope

    This chapter covers hospital medical gas and medical vacuum as building infrastructure. The use of gas on patients, oxygen dosing, and medical decisions are not covered. The governing rule is Permenkes 4/2016 (Minister of Health Regulation) on the Use of Medical Gas and Medical Vacuum in Health Care Facilities; as of November 2026, the JDIH (legal documentation network) of Kementerian Kesehatan (Ministry of Health) records its status as in force. Permenkes 40/2022 on the technical requirements for hospital buildings, infrastructure, and medical equipment, which once contained a section on medical gas installation systems, was revoked by Permenkes 6/2026 on Hospitals. Before using them for permits or audits, check the latest text and status.

    Industrial compressed air is in Chapter 7 · Utilities on compressed air and Chapter 8 · Utilities on compressed air leaks, non-electrical energy isolation in Chapter 4 · Safety, gas cylinders in Chapter 5 · Commercial Kitchens on LPG, gas laws in Chapter 15 · Physics on ideal gases, gas concentration in Chapter 11 · Chemistry on hazardous gases, and fire protection in Chapter 17. Electrical systems in medical rooms are in Chapter 102 · Electrical & Control, ventilation of special hospital rooms in Chapter 30, and hospital facility management in Chapter 31.

    Cutting, brazing, joining, or modifying pipework, installing or relocating outlets, replacing regulators, setting alarms, and testing the installation and declaring it fit for operation are work for competent installers and authorized testing institutions. This chapter does not give steps for opening, cutting, or joining medical gas pipework. The building technician reads, records, reports, and stops the use of any part that is in doubt; they operate the manifold only when designated and trained to do so.

    Medical gas, medical vacuum, and their installation system

    Medical gas is gas with a special specification used for medical services in health care facilities. Medical vacuum is equipment with a special specification for suctioning body fluids during medical services. The medical gas and medical vacuum installation system (Indonesian instalasi gas medik dan vakum medik, IGVM) is the set of medical gas and medical vacuum central supplies, pipework, shut-off valves, and medical gas alarms up to the medical outlet and inlet points.

    Permenkes 4/2016 divides medical gases into pure gases and gas mixtures. Pure gases include oxygen, dinitrogen oxide or nitrous oxide (N₂O), nitrogen, carbon dioxide, helium, argon, medical compressed air, and instrument air. Medical vacuum covers central vacuum equipment and pipe networks for suctioning body fluids and for anesthetic gas scavenging (Indonesian buangan sisa gas anestesi, BSGA), that is, capturing and carrying away the gas discharged from the patient’s breathing circuit during anesthesia. In operating rooms, intensive care rooms, and emergency rooms, medical gas and medical vacuum must be delivered through the installation system.

    Medical compressed air is clean, dry air for patients and breathing equipment, whereas instrument air drives medical equipment such as air-powered surgical tools. The regulation states that the two are different systems, so their copper pipe networks and outlet points must be kept distinct.

    Supply sources: cylinders, liquid oxygen, concentrators, and compressors

    A medical gas central supply may contain gas cylinders, liquid oxygen vessels, or an oxygen generator, plus manifolds, medical compressed air and instrument air systems, a vacuum system, and a BSGA system. An on-site oxygen plant depends on a reliable electricity supply, so WHO considers backup cylinders to remain best practice.

    Pressure swing adsorption (PSA) is a process that passes compressed air through a molecular sieve so that nitrogen is retained and oxygen is collected at a known purity. The WHO specification for PSA plants calls for an oxygen output of 93 percent plus or minus 3, an alarm when the oxygen concentration falls below 90 percent, an output pressure of 300 to 600 kPa with an alarm below 3 bar, an alarm when the backup source takes over, and an alarm for a dryer dew point above 3 °C. Permenkes 4/2016 defines an oxygen concentrator as a machine that separates oxygen from air with an output of at least 90 percent, and sets oxygen from liquid oxygen or from the manufacturer at more than 99.5 percent.

    According to the regulation’s annex, the medical air central supply contains two oil-free compressors, two aftercoolers, two dryers, two air filters, two bacterial or carbon filters, one tank painted green with an automatic condensate drain and a safety valve, a dew point monitor, a CO monitor, and a panel with a motor fault alarm. The vacuum central supply contains two pumps, one tank painted yellow, and two bacterial filters. The paired arrangement allows one unit to be serviced while the other keeps serving.

    Manifolds and the arrangement of the central supply room

    A manifold is a set of equipment that reduces medical gas pressure from the high cylinder pressure, about 2,200 psi, to a low pressure, about 55 psi. There are three types. A fully automatic manifold changes over to the other side by itself when one side runs out. A semi-automatic manifold also changes over by itself, but its indicator lever has to be moved by hand. A manual manifold requires the header bar valve on the exhausted side to be closed and the valve on the other side to be opened. All three are fitted with a header bar, a safety valve, a pressure indicator, and pigtails to suit the number of cylinders. On a manual manifold such as the one in the opening case, a low pressure alarm means the changeover is already late, so the schedule for checking the gauges and the designated staff member are part of the system.

    The central supply room must not be used to store other items. The valve of a cylinder that is not connected to the pipework is always closed, even when the cylinder is empty, and a header bar valve that is empty or connected to empty cylinders is also closed. Every cylinder is marked as full or empty and secured to a permanent structure. Labels must not be damaged, altered, or removed, and connecting fittings must not be modified. WHO adds that cylinders are disconnected from the manifold and fitted with a valve protection cap before being moved, and are then carried on a purpose-made trolley.

    Pipework, valves, and zones

    The building technician reads the pipework requirements in the annex of Permenkes 4/2016 as a handover checklist, not as a work method.

    • Pipes of copper with a purity of about 99 percent or of stainless steel, with a certificate of origin and a certificate of manufacture.
    • Pipes clean of metal filings and oil, flushed with nitrogen, and labeled according to their gas.
    • Steel hangers no more than 2.5 m apart; pipes inside walls protected by PVC conduit.
    • Joints silver-brazed while nitrogen flows through the pipe, with copper fittings.
    • The whole network pressure-tested at no less than 1.5 times the working pressure for 24 hours with nitrogen after installation, and the whole installation leak-tested.

    The network is fitted with one main valve at the central supply, one distribution valve in each area of use, at least one zone valve according to the division of the installation, a main pressure gauge at the central supply and on every main distribution line, and at least one emergency valve in every surgical room and intensive care room.

    A zone valve is a valve that shuts off the gas flow to one part of the network, for example one ward. Closing it stops gas to all patients in that zone at once, so a zone valve is used in an emergency such as a fire, or for work planned together with the clinical unit with a replacement supply ready. A zone valve found closed without a record is reported to the person responsible for the IGVM, not changed by oneself.

    Alarms and working pressure

    Permenkes 4/2016 names three types of alarm. The local alarm monitors the air compressors, vacuum pumps, the BSGA system, and the instrument air system. The master alarm monitors the supply source, the reserve source, and the main line pressure, and is placed in the workroom of the IGVM maintenance staff. The area alarm is installed in particular areas, for example a nurses’ station, for continuous surveillance.

    Annex I of that regulation gives the standard working outlet pressures as follows.

    Gas or systemWorking outlet pressure
    Oxygen, nitrous oxide, nitrogen, carbon dioxide, helium, argon, medical compressed air4 to 5 bar
    Instrument air7 to 9 bar
    Medical vacuum and BSGAhighest suction at the service unit minus 600 mmHg

    Field pressure gauges generally show gauge pressure, that is, the pressure above the local atmospheric pressure. Gas calculations use absolute pressure:

    pabs=pgauge+patmp_\text{abs} = p_\text{gauge} + p_\text{atm}

    with patmp_\text{atm} about 1.013 bar at sea level. Vacuum is written as a negative gauge pressure. Units in the central supply room are a mix of psi, bar, mmHg, and kPa; the conversions are 1 psi = 6.895 kPa = 0.06895 bar, 1 bar = 100 kPa, and 1 mmHg = 0.1333 kPa (Examples 1 and 4).

    A low pressure alarm can come from an exhausted manifold side, a failed regulator, a closed valve, a leak, or a surge in demand; a high pressure alarm usually points to a failed regulator. The technician reads the central and line pressure gauges, compares them with the records, reports, and does not change the regulator setting or the alarm thresholds. Alarm thresholds are not written in this regulation; their values are in the installation’s design documents.

    Outlets and inlets in patient rooms

    A medical gas outlet is the connection point on a wall, ceiling, or ceiling pendant where medical equipment draws gas; for vacuum it is called an inlet. The regulation’s annex governs their position. Wall outlets are installed 140 to 150 cm above the floor, to the right of the patient’s head for one bed, or midway between two beds when serving two. A ceiling pendant weighs about 100 kg, so it is hung from a strong structure.

    Outlets must seal themselves tightly when not in use and open when equipment is connected. Their installation order is fixed: oxygen, nitrous oxide, medical compressed air, instrument air, medical vacuum, carbon dioxide, nitrogen, then BSGA. Every outlet and inlet has a different name, color, thread size, or pin index hole, so that the plug for one gas does not fit the outlet of another gas. Every room with more than one type of outlet is cross-connection tested, and every point is tested for flow and pressure.

    A cross-connection test is a test that proves that each outlet actually delivers the gas written on its label. Wrong connections between pipes cannot be seen from outside the wall, so a new or relocated outlet is not used before it has been cross-connection tested by an authorized party. WHO also prohibits improvised adapters and plastic tape on regulators.

    Purity, colors, and labels

    Annex I of Permenkes 4/2016 sets quality requirements for each gas. Some that technicians read most often:

    GasKey requirements
    Oxygen from liquid oxygen or from the manufacturerO₂ more than 99.5 percent; CO less than 5 ppm; moisture less than 25 ppm
    Nitrous oxideN₂O more than 99.0 percent; CO less than 10 ppm; moisture less than 65 ppm
    Medical compressed airO₂ 21 plus or minus 1 percent; CO less than 1 ppm; moisture less than 25 ppm; oil no more than 5 mg/m³
    Instrument airas for medical compressed air, plus a pressure dew point no higher than minus 10 °C

    Oxygen 93 is oxygen produced from air with a molecular sieve. The European Pharmacopoeia and the United States Pharmacopeia cited by WHO set its concentration at 90 to 96 percent by volume, the remainder being mainly argon and nitrogen. That concentration is not compared with the 99.5 percent limit for liquid oxygen. Purity is demonstrated by the supplier’s quality certificate, the plant logbook, or an on-site analyzer.

    Medical gas cylinders in Indonesia are painted differently according to the gas: oxygen white, dinitrogen oxide dark blue, carbon dioxide gray, nitrogen black, argon green, and helium brown. Their valve threads also differ: oxygen, compressed air, and nitrogen have internal threads, while nitrous oxide and carbon dioxide have external threads. Cylinders must carry a valid test certificate and be sealed.

    According to WHO, the label is the primary means of identifying a cylinder’s contents and the color is only a guide. The ISO 32 standard marks oxygen white, whereas United States convention marks it green; medical air is black and white under ISO and yellow under United States convention. The technician reads the label, not the paint.

    Oxygen and fire in the central supply room

    Oxygen does not burn, but it strongly supports combustion. According to WHO, all materials that burn in air will burn vigorously in oxygen, and oil and grease can burn almost explosively when they meet oxygen. For that reason the regulation requires oxygen and nitrous oxide to be kept away from oil, lubricants, grease, and flammable materials, and the cylinder temperature to be kept from exceeding 52 °C.

    Oxygen enrichment is a rise in the oxygen concentration of room air above the normal level of about 21 percent, usually because of a leak in a poorly ventilated room. Chapter 11 · Safety on confined spaces notes that many procedures accept oxygen between about 19.5 and 23.5 percent by volume. Oxygen-enriched air makes clothing and other materials ignite more easily (Example 5).

    The medical gas central supply room must be easy to reach for cylinder delivery vehicles, away from activities that could cause explosions or fires, safe from heat and oil, permanent, and well ventilated. Its minimum size is 4 m by 6 m by 3 m for two types of gas, 6 m by 8 m by 3 m for three types, and 8 m by 10 m by 3 m for more than four types. A concentrator central supply room requires a door that can be opened from inside and opens outward, entry only by authorized persons, a temperature not above 40 °C when near an incinerator or boiler room, a minimum distance of 3 m from a public road, and no smoking signs on the door.

    WHO adds that fire extinguishers are kept nearby, oxygen cylinders are kept several meters from heat sources, open flames, and electrical devices, and nearby electrical devices are checked to make sure they do not spark.

    Testing, certificates, and the limits of technician work

    The medical gas and medical vacuum installation must be tested and inspected before it is operated for the first time, and then periodically at least once every three years. That testing is carried out by an authorized testing institution. An installation that passes is given a certificate of fitness for operation (Indonesian sertifikat laik operasi) by the authorized agency, while one that has not yet passed is given a statement or recommendation for repair within a set period.

    The same regulation requires medical gas and medical vacuum to be operated by health care facility staff who are competent in that field, or by a competent party appointed for the purpose, in accordance with the regulation and standard operating procedures. Periodic maintenance of cylinders is carried out by the gas supplier, for example every 5 to 10 years. The division of work can be summarized as follows.

    WorkWho does it
    Reading pressure gauges and alarm panels, recording, keeping the central supply room in order, reportingbuilding technician
    Changing cylinders and changing over the manifoldcompetent staff designated under hospital procedure
    Installing, modifying, cutting, or joining pipework, outlets, regulators, and alarmscompetent installer, under a work permit
    Pressure testing, cross-connection testing, flow and pressure testing, quality testing, and the certificate of fitness for operationauthorized testing institution
    Closing a zone valve or main valvestaff designated in the emergency procedure or in a work plan approved by the clinical unit

    Work permits and energy control are covered in Chapter 76 · Electrical & Control on safe work and Chapter 4 · Safety on non-electrical energy isolation. For medical gas, cutting off the supply means cutting off patients.

    Worked example

    The numbers in the examples below are practice numbers, unless their origin is stated.

    Example 1: reading the units in the central supply room. The description of the manifold gives a high pressure of about 2,200 psi and a low pressure of about 55 psi. In bar, 2,200×0.06895=151.72{,}200 \times 0.06895 = 151.7 bar and 55×0.06895=3.7955 \times 0.06895 = 3.79 bar. The working pressure range of 4 to 5 bar in Annex I equals 4/0.06895=58.04/0.06895 = 58.0 psi to 5/0.06895=72.55/0.06895 = 72.5 psi. The 55 psi figure in the manifold description is slightly below that range. The technician does not adjust the regulator on the basis of this calculation; they ask the person responsible for the IGVM for the design set pressure.

    Example 2: how long one side of the manifold lasts. One side of the manifold holds 5 cylinders, each equivalent to 6,000 L of oxygen at atmospheric pressure, so 5×6,000=30,0005 \times 6{,}000 = 30{,}000 L. If the average demand of the whole network is 50 L/min, one side lasts 30,000/50=60030{,}000/50 = 600 minutes, that is, 10 hours. At the night check, the gauge on the active side shows 50 bar out of 150 bar. Assuming the contents are proportional to pressure (Boyle’s law, Chapter 15 · Physics on ideal gases), about 50/150×30,000=10,00050/150 \times 30{,}000 = 10{,}000 L remain, enough for 10,000/50=20010{,}000/50 = 200 minutes, about 3 hours 20 minutes. On a manual manifold, this figure determines when the designated staff member has to be present.

    Example 3: a pressure test that drops because of temperature. The installer’s report records a pressure test of the oxygen network at 1.5×5=7.51.5 \times 5 = 7.5 bar gauge for 24 hours. At the start of the test during the day the pipe temperature is 30 °C, so the absolute pressure is 7.5+1.013=8.5137.5 + 1.013 = 8.513 bar. If at night the pipe temperature falls to 25 °C with no leak, Gay-Lussac’s law gives

    p2=8.513×298.15303.15=8.373 barp_2 = 8.513 \times \frac{298.15}{303.15} = 8.373 \ \text{bar}

    or 7.36 bar gauge. The pressure falls by 0.14 bar, about 1.9 percent of the test pressure, with no leak at all. That is why pressure test results are judged together with the temperature record.

    Example 4: reading vacuum. A highest suction of minus 600 mmHg means 600×0.1333=80.0600 \times 0.1333 = 80.0 kPa below atmospheric. Its absolute pressure is 101.3−80.0=21.3101.3 - 80.0 = 21.3 kPa. An inlet gauge showing minus 0.5 bar, that is, minus 50 kPa, is equivalent to 50/0.1333=37550/0.1333 = 375 mmHg below atmospheric, weaker than the highest limit, which is indeed an upper limit, not a target for every inlet.

    Example 5: an oxygen leak in a closed cylinder store. A store 4 m by 5 m by 3 m has a volume of 60 m³. A joint leaks 10 L/min (q=0.01q = 0.01 m³/min) for 8 hours without ventilation. Assuming the air is perfectly mixed and the air leaving through gaps equals the oxygen entering, the oxygen concentration follows

    C(t)=1−(1−C0) e−qt/VC(t) = 1 - (1 - C_0)\,e^{-qt/V}

    with C0=0.21C_0 = 0.21, t=480t = 480 minutes, and V=60V = 60 m³. The exponent is qt/V=0.01×480/60=0.08qt/V = 0.01 \times 480/60 = 0.08, so C=1−0.79×e−0.08=1−0.79×0.9231=0.271C = 1 - 0.79 \times e^{-0.08} = 1 - 0.79 \times 0.9231 = 0.271, that is, 27.1 percent, above 23.5 percent. If the store is ventilated at 2 air changes per hour, that is, Q=2Q = 2 m³/min, the steady-state concentration is (0.01+2×0.21)/2.01=0.214(0.01 + 2 \times 0.21)/2.01 = 0.214, that is, 21.4 percent. Ventilation of the cylinder room makes a large difference.

    Example 6: checking a planned central supply room and pipe route. A hospital will use three types of gas in a central supply room 5 m by 7 m. Its area is 5×7=355 \times 7 = 35 m², whereas the minimum size for three types of gas is 6×8=486 \times 8 = 48 m², so it is 13 m² short. A pipe route along a corridor 37 m long requires at least ⌈37/2.5⌉=⌈14.8⌉=15\lceil 37/2.5 \rceil = \lceil 14.8 \rceil = 15 spans, that is, 16 hangers including both ends. A sample outlet installed 145 cm above the floor is within the range of 140 to 150 cm.

    Stop conditions

    1. A low or high pressure alarm is showing on an area panel or the master panel: immediately inform the clinical unit served by that zone and the person responsible for the IGVM; do not change the regulator setting or the alarm thresholds; the manifold is operated only by staff designated under hospital procedure.
    2. Fire, smoke, a burning smell, or heat in the central supply room or near oxygen cylinders: leave the room, follow the hospital fire procedure, and inform the fire department and the clinical unit; the main valve or a zone valve is closed only by staff designated in the emergency procedure.
    3. A request has been made to close a zone valve, emergency valve, or main valve for maintenance: postpone until the person responsible for the IGVM and the head of the clinical unit have approved a work plan with a replacement supply ready.
    4. The work involves cutting, brazing, joining, or modifying pipework, outlets, manifolds, regulators, or alarms, including ceiling work near medical gas pipework: hand it over to a competent installer under a work permit; that part is not used before it has been declared fit by an authorized testing institution.
    5. An outlet whose gas type is in doubt, a missing label, a plug for one gas that fits the outlet of another gas, an improvised adapter, or plastic tape on a regulator: stop using that outlet or equipment, tag it, and report it to the person responsible for the IGVM for cross-connection testing.
    6. A cylinder without a readable label, with a damaged seal, an expired test certificate, oil on it, or exposure to heat: do not use or connect it; segregate it, tag it, and return it to the supplier.
    7. The dew point or CO monitor of the medical compressed air is in alarm, or the plant oxygen analyzer shows a concentration below 90 percent: report to the person responsible for the IGVM and the clinical unit; changeover to the backup source is carried out by designated staff under the procedure.
    8. The certificate of fitness for operation has expired or the periodic test is more than three years overdue: report to facility management so that testing by an authorized testing institution is scheduled.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    The cylinder color is enough to identify its contents.

    Why is it wrong?

    The label is the primary means of identification and the color is only a guide. Oxygen is white under ISO but green under United States convention, and argon in Indonesia is painted green.

    Common misconception

    Medical compressed air and instrument air can share a pipe because both are air.

    Why is it wrong?

    The regulation states that they are different systems with distinct pipes and outlets, and their working pressures also differ, 4 to 5 bar versus 7 to 9 bar.

    Common misconception

    A test pressure that drops slightly is always a sign of a leak.

    Why is it wrong?

    A fall in pipe temperature alone can lower the pressure by about 0.14 bar overnight (Example 3). The pressure test is judged by the tester together with the temperature record.

    Common misconception

    A zone valve is an ordinary service valve that the technician may close.

    Why is it wrong?

    A zone valve cuts off gas to all outlets in that zone. Closing it is part of the emergency procedure or of a work plan approved by the clinical unit.

    Common misconception

    Oxygen does not burn, so it adds no fire hazard.

    Why is it wrong?

    Oxygen makes other materials burn far more fiercely, and oil and grease can burn almost explosively.

    The medical air central supply works on the same principles as industrial compressed air in Chapter 7 · Utilities, and the calculation of cylinder contents and the effect of temperature use the gas laws in Chapter 15 · Physics. Oxygen concentration in enclosed rooms relates to Chapter 11 · Safety on confined spaces. Compressors, vacuum pumps, and alarm panels need the power supply covered in Chapter 102 · Electrical & Control on electrical systems in medical rooms, and the periodic test schedule becomes part of Chapter 31 on hospital facility management.

    Exercises and worked solutions

    The numbers in the exercises are for practice.

    Try to answer first, then open the worked solution.

    1. The high-pressure gauge of a manifold shows 1,800 psi. How many bar is that, and what percentage of 2,200 psi?

      Check my answer
      See the worked solution

      The pressure is 1,800×0.06895=124.11{,}800 \times 0.06895 = 124.1 bar, that is, 1,800/2,200=821{,}800/2{,}200 = 82 percent of the high pressure stated in the regulation. Assuming the contents are proportional to pressure, that side is still about four-fifths full.

    2. One side of a manifold holds 6 cylinders, each equivalent to 6,000 L. Average demand is 40 L/min. How many hours does one side last, and what does that mean for a manual manifold?

      Check my answer
      See the worked solution

      The contents are 6×6,000=36,0006 \times 6{,}000 = 36{,}000 L, enough for 36,000/40=90036{,}000/40 = 900 minutes, that is, 15 hours. A manual manifold does not change over by itself, so gauge checks and the presence of the designated staff member are scheduled well before the 15 hours run out.

    3. A vacuum inlet gauge shows minus 400 mmHg. How many kPa below atmospheric is that, and what is its absolute pressure?

      Check my answer
      See the worked solution

      Minus 400 mmHg equals 400×0.1333=53.3400 \times 0.1333 = 53.3 kPa below atmospheric, so the absolute pressure is 101.3−53.3=48.0101.3 - 53.3 = 48.0 kPa. This value is still within the highest limit of 600 mmHg.

    4. A hospital plans five types of medical gas in one central supply room 6 m by 8 m. Does the room meet the minimum size?

      Check my answer
      See the worked solution

      For more than four types of gas, the minimum size is 8 m by 10 m by 3 m, that is, 80 m², whereas the planned room is only 48 m². The room does not meet the requirement, and this finding is reported to the planner before installation.

    5. A nurse asks the technician to make an adapter so that an oxygen flowmeter can be fitted to a medical compressed air outlet because the oxygen outlets are all in use. What is the technician’s answer?

      Check my answer
      See the worked solution

      The technician refuses, because the outlets for each gas are deliberately distinguished by name, color, and thread or pin index so that equipment is not connected to the wrong gas, and improvised adapters are prohibited. The need for an additional outlet is reported to the person responsible for the IGVM.

    6. A renovation contractor relocates one oxygen outlet in a ward and declares the work finished. What must happen before that outlet is used?

      Check my answer
      See the worked solution

      The outlet may not be used until the modified network has been leak- and pressure-tested, the room has been cross-connection tested, and the point has been tested for flow and pressure by an authorized party. The contractor’s statement that the work is finished does not replace testing, because a wrong connection cannot be seen from outside.

    References

    External sources

    • Peraturan Menteri Kesehatan Nomor 4 Tahun 2016 tentang Penggunaan Gas Medik dan Vakum Medik pada Fasilitas Pelayanan Kesehatanjdih.kemkes.go.id
    • WHO-UNICEF technical specifications and guidance for oxygen therapy devicesiris.who.int
    • Technical specifications for Pressure Swing Adsorption (PSA) Oxygen Plants: Interim guidanceiris.who.int
    • Peraturan Menteri Kesehatan Nomor 6 Tahun 2026 tentang Rumah Sakitjdih.kemkes.go.id

    Revision history

    DateVersionChange
    November 11, 20261First published

    How to cite

    Kurnia (2026). Hospital medical gas systems: oxygen, medical compressed air, vacuum, and nitrous oxide, supply sources and manifolds, piping and valve zones, alarms and pressure, outlets, purity testing, and the limits of technician work. ARSTEMA Academy. Revised November 11, 2026. arstema.com/en/academy/konsep/sistem-gas-medis-rumah-sakit-oksigen-udara-tekan-medis-vakum-dan-nitrous-oksida-sumber-pasokan-dan-manifold-pipa-dan-zona-katup-alarm-dan-tekanan-outlet-uji-kemurnian-serta-batas-kerja-teknisi

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated

    Safety limits still apply. This quiz tests reasoning; it doesn’t authorize mixing, adjusting, dismantling, live measurement, or field action.

    1

    The high-pressure gauge of a manifold shows 1,800 psi. How many bar is that, and what percentage of 2,200 psi?

    2

    One side of a manifold holds 6 cylinders, each equivalent to 6,000 L. Average demand is 40 L/min. How many hours does one side last, and what does that mean for a manual manifold?

    3

    A vacuum inlet gauge shows minus 400 mmHg. How many kPa below atmospheric is that, and what is its absolute pressure?

    Self-assessment progress0%