By Kurnia · Published November 14, 2026 · Version 1 · 21 min read
Basement car park ventilation
carbon monoxide from vehicles, jet fans and exhaust fans, sensors and controls, smoke control, inspection, and work limits
On the night of a reception at a hotel, a valet attendant near the basement exit ramp complains of dizziness, the carbon monoxide sensor at the ramp reads 85 ppm, and the exhaust fans turn out to be held at low stage by a manual override that someone forgot to release. This chapter covers basement car park ventilation from the building technician’s side: carbon monoxide from vehicles and where it accumulates; the worker threshold limit value under Permenaker 5/2018 compared with British design and exposure limits and with an alarm threshold for United States military facilities; air changes per hour and steady-state concentration; exhaust fans and jet fans; electrochemical sensors and staged control; smoke control during a fire, which follows the fire alarm panel; and inspection, record keeping, and work limits. The design figures come from English building documents and are written as data from that country. This chapter gives no way to switch off, delay, or bypass smoke fan control or carbon monoxide alarms.
This material involves real hazards. A concept explanation doesn’t replace site procedures, competency, energy isolation, the latest SDS, or a work permit.
On a Friday night, after a wedding reception at a hotel, guests’ cars queue to leave a two-level basement with their engines running, held up on the ramp because the parking barrier is slow to open. The valet attendant who has been posted at the foot of the ramp since the afternoon complains of dizziness and nausea. On the building management system screen, the carbon monoxide sensor near the exit ramp reads 85 ppm, while the other sensors on the same level read 10 to 20 ppm. The exhaust fans are turning, but only at low stage: since the morning there has been a manual override, left from replacing a fan belt, that has not been released. The duty technician needs to know why such a high concentration exists only at the ramp, which limit to use when reading 85 ppm, what the fans should be doing, and which part of the system they must not touch.
Scope
This chapter covers basement car park ventilation from the building technician’s side: carbon monoxide from vehicles, concentration limits, ventilation rates, exhaust fans and jet fans, sensors and controls, smoke control during a fire, and inspection. Design figures for ventilation rates and smoke ventilation are taken from building documents for England and are written as data from that country. The technical requirements for car park ventilation in Indonesian building regulations are not quoted by number; as of November 2026 their content cannot yet be confirmed, so the figures for a particular building are read from the approved design documents.
Indoor air quality is covered in Chapter 40. How carbon monoxide binds to hemoglobin, the definition of the threshold limit value, and the time-weighted average are in Chapter 36 · Biology & Microbiology on breathing and workplace air; ppm and steady-state concentration are in Chapter 11 · Chemistry on hazardous gases and ventilation. Fire alarms are in Chapter 19 to Chapter 23, the building management system in Chapter 32, alarms and manual overrides in Chapter 33, VFDs in Chapter 67 · Electrical & Control, and work permits and LOTO in Chapter 76 · Electrical & Control.
Outside the building technician’s authority: changing setpoints, schedules, or the cause and effect matrix; opening control panels, motor terminal boxes, or VFDs; calibrating and replacing sensors; work at height on jet fans without a permit; and testing fire mode. That work belongs to the HVAC and controls contractor, the sensor vendor, an authorized electrician, and the fire protection system contractor together with building management. The building technician reads, inspects, records, reports, and carries out the light maintenance assigned. This chapter gives no way to switch off, delay, or bypass smoke fan control or carbon monoxide alarms, and the building technician does not do so.
Carbon monoxide from vehicles and why basements are different
Carbon monoxide (CO) is a colorless, odorless gas produced by incomplete combustion. The United States EPA lists exhaust from cars, trucks, or buses in attached garages, nearby roads, and parking areas as sources of indoor carbon monoxide, and advises against leaving a car engine idling inside a garage. Symptoms at moderate to high concentrations include headache, dizziness, confusion, and nausea (Chapter 36 · Biology & Microbiology).
In a basement car park, emissions are not spread evenly: cars that have just been started and cars that are queuing release gas in the same place at the same time, so the highest concentrations appear on the ramp, in front of the parking barrier, and in the pickup lane. A basement also gets no help from the wind: air moves only when fans move it, so ventilation that weakens shows up immediately as a rise in concentration at the emission points.
The relative gas density of carbon monoxide compared with air is 0.97. The gas does not settle on the floor like LPG vapor and does not rise to the ceiling; it mixes and is carried by the airflow. United States military facility criteria ask for sensor mounting height to be set according to gas density and the intent to protect occupants, with carbon monoxide detectors generally in the breathing zone, the height at which people breathe the air, and nitrogen dioxide detectors close to the floor.
Concentration limits: for workers, for design, and for alarms
Carbon monoxide figures in a building answer different questions: worker exposure limits, design limits for sizing fans, and setpoints for alarms or fan stages.
| Figure | Meaning | Applies to |
|---|---|---|
| 25 bds (ppm) or 29 mg/m³ | threshold limit value for carbon monoxide, Permenaker 5/2018 | workers in Indonesia, 8 hours a day or 40 hours a week |
| 20 ppm 8 hours; 100 ppm 15 minutes | workplace exposure limits, HSE | workers in Great Britain |
| 30 ppm average over 8 hours; 90 ppm peak over 15 minutes | car park ventilation design limits, Approved Document F | building design in England |
| 35 ppm | second-stage alarm exhaust in vehicle maintenance areas, UFC | United States military facilities |
Permenaker 5/2018 (Minister of Manpower Regulation) on Occupational Safety and Health of the Work Environment sets the threshold limit value (Indonesian nilai ambang batas) for carbon monoxide at 25 parts per million (Indonesian bagian dalam sejuta, bds) or 29 mg/m³, with a notation that biological exposure indices are required; as of November 14, 2026, the regulation is recorded as in force on JDIH Kemnaker. Valet, parking, and security staff who work a whole shift in the basement are protected by this figure. Their exposure is assessed by an occupational safety and health (K3) expert from measurements made according to the regulation, not from a single reading of a wall sensor.
Approved Document F volume 2 for England asks for the ventilation rate of below-ground and enclosed car parks to be designed to limit carbon monoxide to an average of 30 ppm over eight hours and a peak of 90 ppm over 15 minutes, for example by ramps and exits. Designers use these figures to select fans, and they do not replace worker limits. A United States military facility document shows how figures are used in controls: vehicle maintenance areas have standby-stage and alarm-stage exhaust, and the alarm stage is activated when carbon monoxide in the breathing zone exceeds 35 ppm or nitrogen dioxide exceeds 1 ppm, together with audible and visual alarms.
A building’s setpoints are listed in its design documents. A cause and effect matrix is a table that states, for each input such as a carbon monoxide concentration or a fire signal, the output that must occur at fans, dampers, and alarms. The technician uses it to check the system, not to reset its figures.
Ventilation rate and air changes per hour
Air changes per hour is the airflow divided by the room volume:
where is air changes per hour, is the airflow (m³/h), and is the room volume (m³). Approved Document F gives a simpler alternative: a mechanically ventilated basement car park is capable of at least six air changes per hour, and exits and ramps where cars queue inside the building have a local rate of at least ten air changes per hour. The word “capable” matters: the figure is the system capacity, while the everyday speed can be lower when the controls keep the concentration below the design limits.
When the source is constant and the air is well mixed, the concentration reaches a steady state according to the mass balance in Chapter 11 · Chemistry:
where is the steady-state concentration (ppm), is the concentration of the incoming air (ppm), is the carbon monoxide emission rate (m³/h), and is the ventilation airflow (m³/h). The room volume only determines how quickly the steady state is reached. After the source stops, the time to fall from to is
with in hours. Both formulas assume well-mixed air, whereas the concentration on a ramp full of queuing cars can be several times the level average; that is why the local rate and the placement of sensors near the queue matter as much as the total airflow, and these formulas are only for estimating.
Exhaust fans, jet fans, and air paths
A car park exhaust fan is a large fan in a fan room or at the top of an air shaft that draws air from the basement and discharges it outside. Makeup air enters through the ramps, intake shafts, or supply fans. Approved Document B asks for non-domestic kitchens, car parks, and plant rooms to have separate and independent extraction systems, and for the extracted air not to be recirculated.
Polluted air is carried to the exhaust fans through a network of ducts with distributed intake grilles, or by jet fans. A jet fan is a small axial fan hung below the slab above that blows a high-velocity jet of air; the jet drags the surrounding air along so that the mass of air in a parking aisle moves toward the exhaust point. A jet fan does not remove air itself. If the exhaust fans stop, jet fans only stir the polluted air, so the control sequence makes sure the exhaust fans run before or together with the jet fans. Banners or racks in front of a jet fan cut the jet and leave dead zones where gas accumulates.
Fans are generally driven through VFDs. For the same fan and ductwork, airflow and power follow the fan affinity laws:
where is rotational speed, is airflow, and is shaft power. These relationships are ideal; motor and VFD losses and the manufacturer’s minimum speed make the real savings smaller. Bearing vibration and noise are read as in Chapter 4 · Mechanical & Mechatronics, and belts as in Chapter 6 · Mechanical & Mechatronics.
Carbon monoxide sensors and control logic
Fixed carbon monoxide sensors in car parks are generally electrochemical: the gas diffuses into the cell, reacts at the electrodes, and the current produced is proportional to the concentration. EPA notes electrochemical and infrared instruments for measuring carbon monoxide. Electrochemical cells have a limited life and their readings drift. A bump test is a brief application of test gas to confirm that the sensor responds and that the fan stage or alarm changes; calibration is the adjustment of the reading against a reference gas according to the manufacturer’s procedure. United States military facility criteria ask for detectors to be listed to a standard, installed according to the manufacturer’s instructions, spread out rather than grouped in one place, and to trigger audible and visual alarms.
The usual control is staged. At the base stage, the fans run at the design minimum speed. When a sensor exceeds the first setpoint, the fans in that zone step up to the middle stage; when it exceeds the second setpoint, the fans go to full speed and an alarm appears. In the military document mentioned above, the system reverts by itself to the standby stage after the space has been purged and the concentration has dropped below the alarm-stage setpoint. The stage used when a sensor fails or loses communication is set by the design, usually a safe state, meaning faster fans.
In the building management system (Chapter 32), a car park zone has points for the concentration at each sensor, the fan run and speed commands, run status from a differential pressure switch or auxiliary contact, and VFD fault status. A run command is not the same as proof of running: a fan with a broken belt appears to be running if the system reads only the command. A manual override like the one in the opening case locks the output at one value and switches off the automatic response to carbon monoxide; that is why every override is recorded, given a time limit, and released when the work is finished.
Smoke control during a fire
Smoke ventilation in a basement does not extinguish the fire; its purpose is to remove smoke and heat so that occupants can get out and firefighters can reach the source of the fire. Approved Document B for England asks for car parks that are not naturally ventilated to use mechanical ventilation that is independent of any other ventilation system, other than the car park’s own day-to-day ventilation system, and designed to operate at 10 air changes per hour during a fire.
The system runs in two parts. Each part is capable of extracting 50 percent of that rate, can operate alone or together with the other, and has an independent power supply that keeps working if the main supply fails; half of the outlets are at high level and half at low level, and the ductwork is fire resistant. For that reason the failure of one fan, one VFD, or the standby supply connection from the generator (Chapter 36 · Electrical & Control) is an impairment of the fire protection system, not only an HVAC fault. Under fire conditions, the building’s ventilation and air conditioning also need to be compatible with the smoke control system.
When the fire alarm panel declares a fire in a car park zone, the cause and effect matrix moves the fans into fire mode, the state defined by the designer for a fire: certain exhaust fans run at full speed, jet fans run, stop, or reverse according to the zone scenario, and carbon monoxide control, schedules, and overrides from the operator station no longer apply. This mode follows the fire alarm panel (Chapter 19) and the firefighter control panel where there is one. The building technician does not switch off, delay, reset, change the speed or direction of, or take the fans out of fire mode; they record what they see and report to the person responsible for fire safety and the firefighters. Fire mode tests are carried out on a schedule by the fire protection system contractor together with building management, like the alarm tests in Chapter 23.
Inspection, record keeping, and light maintenance
Inspection answers two questions: is the air really moving toward the exhaust points, and are the monitoring devices still telling the truth. A checklist that can be assigned:
- All sensor readings are reasonable and comparable with one another; a sensor that reads zero continuously or never changes is recorded as suspected faulty.
- The status of the exhaust fans and jet fans matches the stage called for by the concentration, and the proof of running matches the command.
- No manual override has been left behind; every override has a name, a reason, and a time limit.
- Ramps, intake shafts, exhaust grilles, and jet fan jets are not obstructed by goods or signs.
- Sensor housings are not covered by plastic, paint, or dust, and are not sprayed with water when the floor is washed.
- The fan room is locked and not used to store goods.
- The bump test and calibration dates of every sensor are still within the vendor’s schedule.
Records contain the highest daily reading per sensor and its time, fan running hours per stage, alarms, overrides, and sensor test results. The trend shows a sensor that slowly reads lower than its neighbors, or a fan that more and more often steps up to full stage because its belt is slipping.
Light maintenance by the building technician is limited to cleaning grilles and the outside of sensor housings, removing obstructions, and inspecting from floor level. Work inside a fan, a motor terminal box, or a VFD panel is done by an authorized technician with LOTO according to Chapter 76 · Electrical & Control. Jet fans above traffic lanes require a work-at-height permit, suitable lifting equipment, and closure of the lane. Bump tests are done by a trained person according to the manufacturer’s procedure, with notice to the operator so that a test alarm is not treated as a real event.
Worked example
The numbers in the examples below are practice numbers, unless their origin is stated.
Example 1: air changes per hour for one level. A basement level 60 m by 40 m with a clear height of 3 m has a volume of m³. Two exhaust fans of 36,000 m³/h each at full speed give m³/h, that is, per hour. The middle stage at 60 percent speed gives m³/h or per hour, and the low stage at 30 percent gives m³/h or per hour. If the building is designed with the alternative of six air changes per hour, its capacity is sufficient, and the low stage is acceptable only as long as carbon monoxide control is working.
Example 2: concentration on the ramp in the opening case. The exit ramp zone, 20 m by 40 m by 3 m, has a volume of 2,400 m³ and is designed with a local rate of 10 per hour, that is, m³/h. Assume the queue releases carbon monoxide at m³/h and the incoming air carries 2 ppm. With the override at low stage, the zone airflow is only m³/h, so ppm, the same as the 85 ppm reading. With the design airflow, ppm. The cause is the override, not the sensor: the building management system supervisor releases the override according to the procedure in Chapter 33, security staff manage the queue so that cars do not wait on the ramp with engines running, and the valet attendant is moved to fresh air and checked by health personnel.
Example 3: exposure of the valet attendant. The valet attendant’s personal detector records 40 ppm for 4 hours, 15 ppm for 2 hours, and 5 ppm for 2 hours. The time-weighted average is ppm, and with the conversion in Chapter 11 · Chemistry at 20 °C, mg/m³, consistent with the pair of 25 bds and 29 mg/m³ in Permenaker 5/2018. The result is exactly equal to the threshold limit value, not below it, and the first four hours are far above it. The assessment belongs to the K3 expert, but the actions are clear before that: the post is moved away from the foot of the ramp, queuing with engines running is reduced, and the fan stage is checked.
Example 4: time to clear a level after the departure rush. After the queue has cleared, the average concentration on the level in Example 1 is 120 ppm, the incoming air is 2 ppm, and the target is 25 ppm. At middle stage h, so h, that is, 16.4 minutes. At low stage h and h, that is, 32.7 minutes. Halving the airflow doubles the clearing time.
Example 5: energy savings from staged control. Each exhaust fan in Example 1 draws 22 kW at full speed. According to the affinity laws, at 60 percent speed its power is kW and at 30 percent kW. If the fans run 6 hours at middle stage and 18 hours at low stage, the daily energy for two fans is kWh, compared with kWh if always at middle stage. The saving is percent in the ideal calculation, and it is valid only if the sensors and controls are working.
Example 6: fire mode capacity. If the level in Example 1 is designed on the basis of Approved Document B, the airflow during a fire is m³/h, that is, m³/s, divided into two parts of 36,000 m³/h each; two fans of 36,000 m³/h meet this. If one fan is dismantled for a bearing repair, what remains is air changes per hour, half the design. This situation is recorded as an impairment of the fire protection system and reported to the person responsible for fire safety before the fan is dismantled, so that substitute measures and the duration of the impairment are decided by those with authority.
Stop conditions
- Any sensor reaches the carbon monoxide alarm stage in the cause and effect matrix, or someone in the basement complains of dizziness, headache, nausea, or confusion: move people to fresh air, ask security staff to stop queuing with engines running in that area, report to the duty engineer and the K3 officer, and have anyone with complaints checked by health personnel according to Chapter 36 · Biology & Microbiology.
- A fire alarm is active in a car park zone, or there is smoke or a burning smell in the basement: carry out the emergency response plan; fan control follows the fire alarm panel and the firefighters, and the technician does not switch off, delay, reset, or change the speed or direction of the fans.
- One part of the smoke fans, its VFD, its independent power supply, or its ductwork cannot operate, or a fan fails during a fire mode test: record it as an impairment of the fire protection system and hand it over to the person responsible for fire safety and the fire protection system contractor; do not make temporary connections.
- A sensor indicates a fault, loses communication, reads zero continuously, or differs greatly from a tested portable detector: report to the building management system supervisor; that zone is treated as unmonitored until the vendor tests or replaces the sensor, and the temporary fan settings are decided by the chief engineer according to the design documents.
- The work would require opening a fan, a motor terminal box, a control panel, or a VFD: stop and hand it over to an authorized electrician with energy isolation, LOTO, and a work permit according to Chapter 76 · Electrical & Control.
- A jet fan or sensor at height above a traffic lane needs to be reached: postpone until there is a work-at-height permit, suitable lifting equipment, and closure of the lane by security staff.
- There is a request to change setpoints, schedules, or the cause and effect matrix, to apply an override without a time limit, or to switch off fans to save energy or reduce noise: refuse and report to the chief engineer; changes are made only with the written approval of the designer and building management, and those that concern fire also with the person responsible for the fire protection system.
- The fan room is used to store goods, or ramps, intake shafts, or jet fan jets are obstructed: report to building management and ask the owner to remove the obstruction.
Common misinterpretations
Guess what’s wrong first, then open the explanation.
Common misconception
Carbon monoxide is heavier than air, so its sensors go near the floor.
Why is it wrong?
Its relative gas density is 0.97, so the gas mixes and is carried by the airflow. Carbon monoxide sensors are generally in the breathing zone; the detectors near the floor are for nitrogen dioxide.
Common misconception
Jet fans remove polluted air.
Why is it wrong?
Jet fans only push air toward the exhaust point. Without exhaust fans running, they only stir the polluted air.
Common misconception
The figures 20, 25, 30, and 35 ppm are all the same, so pick one.
Why is it wrong?
These figures are the worker limit in Great Britain, the worker limit in Indonesia, the design limit in England, and an alarm setpoint for United States military facilities. For workers in Indonesia, the Permenaker 5/2018 threshold limit value is used, while a building’s setpoints are read from the cause and effect matrix.
Common misconception
The sensor is not alarming, so the air is safe.
Why is it wrong?
Electrochemical sensors drift and can fail without any sign if they are not tested, and a sensor far from the queue does not see the concentration on the ramp. What can be trusted is a sensor that has passed a bump test and is close to the emission points.
Common misconception
During a fire, the fans should be switched off so the fire gets no air.
Why is it wrong?
Fan behavior during a fire is set by the designer to remove smoke and heat for evacuation and firefighting. Switching off or changing fans outside the fire alarm panel can fill escape routes with smoke.
Links to other chapters
Chapter 36 · Biology & Microbiology explains the effect of carbon monoxide on the body, and Chapter 11 · Chemistry gives the formulas used in Examples 2 to 4. Chapter 40 covers indoor air quality. Chapter 32 and Chapter 33 explain the data points, alarms, and overrides that make up fan control, Chapter 19 to Chapter 23 cover the fire alarm system that takes over the fans, and Chapter 24 · Automotive & Electric Mobility covers electric vehicle charging, which is now also installed in basements.
Exercises and worked solutions
The numbers in the exercises are for practice.
Try to answer first, then open the worked solution.
A basement level 50 m by 30 m with a clear height of 2.8 m is served by a 25,200 m³/h exhaust fan. How many air changes per hour does it give, and is that sufficient if the design uses the alternative of six air changes per hour?
Check my answer
See the worked solution
The volume is m³, so per hour. That capacity exactly meets the alternative of six air changes per hour, but ramps where cars queue still need a higher local rate under the same design basis.
A technician wants to move a carbon monoxide sensor close to the floor so that it catches gas faster. What is the response?
Check my answer
See the worked solution
The relative gas density of carbon monoxide is 0.97, so the gas mixes with air and does not settle on the floor. The sensor is placed in the breathing zone according to the design, and moving it is a design change decided by the designer, not the technician.
A queue on a ramp releases 0.4 m³/h of carbon monoxide, the incoming air carries 2 ppm, and the local airflow is 16,000 m³/h. What is the steady-state concentration compared with the 90 ppm peak in the English design basis?
Check my answer
See the worked solution
ppm, below the 90 ppm peak in the English design basis. The calculation assumes well-mixed air, so the concentration near exhaust pipes can be higher, and the result is only an estimate to be checked against the sensors.
A parking attendant’s personal detector records 30 ppm for 3 hours and 10 ppm for 5 hours. What is the time-weighted average compared with the Permenaker 5/2018 threshold limit value?
Check my answer
See the worked solution
ppm, below the threshold limit value of 25 bds. Three hours at 30 ppm show that there is a local source to be found, and the final assessment is still made by the K3 expert.
A fire alarm sounds in a car park zone, and a guest asks for the noisy fans to be switched off because they spread the smoke. What does the technician do?
Check my answer
See the worked solution
The technician does not switch off or change the fans, because in fire mode the fans follow the fire alarm panel and the smoke extraction design. They help carry out the emergency response plan, direct guests to the escape routes, and report to the person responsible for fire safety and the firefighters.
The hotel manager proposes switching off the car park fans from 00:00 to 05:00 to save electricity. Why is this proposal not decided by the technician, and what needs to be checked?
Check my answer
See the worked solution
Switching off the fans changes the schedule and control logic, which requires the approval of the designer and building management, and the basement is still used by late-arriving guests and staff on duty. What needs to be checked is whether carbon monoxide control still steps up the fans when a car comes in, and whether the change leaves fire mode untouched.
References
External sources
- Peraturan Menteri Ketenagakerjaan Nomor 5 Tahun 2018 tentang Keselamatan dan Kesehatan Kerja Lingkungan Kerjajdih.kemnaker.go.id
- EH40/2005 Workplace exposure limitshse.gov.uk
- Approved Document F: Volume 2 applies to buildings other than dwellingsassets.publishing.service.gov.uk
- Approved Document B (fire safety) volume 2: Buildings other than dwellings, 2019 edition incorporating 2020, 2022, 2025 and 2026 amendments collated with 2029 amendmentsassets.publishing.service.gov.uk
- NIOSH Pocket Guide to Chemical Hazards - Carbon monoxidecdc.gov
- UFC 3-410-01 Heating, Ventilating, and Air Conditioning Systemswbdg.org
- Carbon Monoxide's Impact on Indoor Air Qualityepa.gov
Revision history
| Date | Version | Change |
|---|---|---|
| November 14, 2026 | 1 | First published |
How to cite
Kurnia (2026). Basement car park ventilation: carbon monoxide from vehicles, jet fans and exhaust fans, sensors and controls, smoke control, inspection, and work limits. ARSTEMA Academy. Revised November 14, 2026. arstema.com/en/academy/konsep/ventilasi-parkir-basement-karbon-monoksida-dari-kendaraan-kipas-jet-dan-kipas-buang-sensor-dan-kendali-pengendalian-asap-pemeriksaan-serta-batas-pekerjaan
Self-check · 3 questions
Check your understanding before moving on
Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.
Safety limits still apply. This quiz tests reasoning; it doesn’t authorize mixing, adjusting, dismantling, live measurement, or field action.
A basement level 50 m by 30 m with a clear height of 2.8 m is served by a 25,200 m³/h exhaust fan. How many air changes per hour does it give, and is that sufficient if the design uses the alternative of six air changes per hour?
A technician wants to move a carbon monoxide sensor close to the floor so that it catches gas faster. What is the response?
A queue on a ramp releases 0.4 m³/h of carbon monoxide, the incoming air carries 2 ppm, and the local airflow is 16,000 m³/h. What is the steady-state concentration compared with the 90 ppm peak in the English design basis?