    Buildings & Facilities · Chapter 43Applied

    By Kurnia · Published November 15, 2026 · Version 1 · 18 min read

    Hotel lobby automatic doors

    automatic sliding and revolving doors, motion sensors and safety sensors, crushing and impact hazards, emergency modes and escape routes, daily checks, and work limits

    On a busy afternoon at a hotel, the automatic sliding lobby door closes onto the shoulder of an elderly guest walking with a mobility aid, because the window of the safety sensor is covered by a decorative sticker, and at the revolving door next to it a child pushes a wing until the door jerks to a stop. This chapter covers lobby automatic doors from the building technician’s side: how automatic sliding and revolving doors are built, the difference between the motion sensor that opens the door and the safety sensor that protects people, crushing, shearing, and impact hazards together with leaf energy and wing speed, glazing and its manifestation, doors on escape routes and how they behave in a power failure, daily checks, and work limits. HSE guidance and the English Approved Documents are written as data from that country, and Permenaker 12/2015 is used for the division of electrical work. This chapter gives no way to bypass safety sensors or to change emergency modes and night locks; adjustment, repair, and program changes belong to a competent door contractor.

    High-risk material

    This material involves real hazards. A concept explanation doesn’t replace site procedures, competency, energy isolation, the latest SDS, or a work permit.

    Section you’re reading: Chapter opening

    On a Saturday afternoon, two tour buses arrive at a hotel at the same time, and the lobby fills with guests dragging suitcases. An elderly guest walking slowly with a mobility aid is passing through the main automatic sliding door when both glass leaves start to close. The leading edge strikes the guest’s shoulder and traps the mobility aid before the door opens again; the guest nearly falls. The duty technician finds the sensor window above the threshold covered by a holiday decoration sticker, and the bell desk attendant mentions that last week someone asked the vendor to speed up the door so that less cool air escapes from the lobby. At the revolving door next to it, a child pushes a wing faster than it turns until the door jerks to a stop. The technician needs to decide which door stays automatic, which is taken out of use, whom to call, and what they must not touch.

    Scope

    This chapter covers automatic sliding doors and automatic revolving doors at the lobby entrances of hotels, hospitals, and public buildings from the building technician’s side: how the doors and their operators are built, motion sensors and safety sensors, crushing, shearing, and impact hazards, glazing, doors on escape routes and their behavior in a power failure, daily checks, records, and work limits. This chapter is learning material for recognizing dangerous conditions, not a work instruction for adjusting or repairing doors. HSE guidance, the British workplace regulations, and the Approved Documents for England are written as data from that country. The requirements for automatic doors in Indonesian building regulations are not quoted; as of November 2026 their content cannot yet be confirmed, so the requirements for a particular building are read from the approved design documents. For electrical work, Permenaker 12/2015 (Minister of Manpower Regulation) on electrical occupational safety and health (K3) at the workplace is used, which as of November 14, 2026 is recorded as in force in the JDIH Kemnaker database.

    Frames, door leaves, hinges, door closers, locks, and fire doors are in Chapter 38. Card readers and electric locks are in Chapter 94 · Electrical & Control on door access control, categories and performance levels of safety control systems in Chapter 70 · Electrical & Control on functional safety of machinery, and gates and parking barriers in Chapter 18 · Mechanical & Mechatronics on automatic gates. The fire alarm panel is in Chapter 19, emergency lighting and exit signs in Chapter 106 · Electrical & Control, photoelectric sensors in Chapter 59 · Electrical & Control, LOTO and work permits in Chapter 76 · Electrical & Control, and work at height in Chapter 10 · Safety.

    Work outside the building technician’s authority: adjusting speed, force, hold-open time, and sensor detection fields; installing, moving, or replacing sensors; changing programs, emergency modes, night locks, and the connection to the fire alarm panel; opening the operator cover; and repairing motors, belts, tracks, and controllers. All of that belongs to a competent door contractor, and the electrical circuit belongs to an authorized electrician. The building technician does not cover, bridge, remove, or reduce the sensitivity of safety sensors under any circumstances. The technician inspects and tests function according to the user instructions, cleans the outside, removes obstructions, keeps records, takes the door out of automatic use when designated to do so, directs guests to another door, and reports.

    Automatic sliding and revolving doors

    An automatic sliding door is a door whose leaves move in a straight line parallel to the wall, driven by a door operator, an assembly of motor, toothed belt, roller carriages, track, and controller mounted in a box above the threshold. In a lobby, two leaves usually open to the left and right beside fixed glass panels. Approved Document M for England regards a powered door, whether manually controlled or automatically operated by sensors, as the most satisfactory solution for most people, and notes that an automatic sliding door is particularly beneficial because it avoids the risks of automatic swing doors.

    An automatic revolving door is a door with three or four wings that turn on a central shaft inside a glass drum, driven by a motor at a fixed speed. This door holds back the wind, but it has danger points between the wings and the drum wall. Approved Document M does not consider revolving doors accessible: they create difficulties and a risk of injury for people with assistance dogs, people with visual or mobility impairments, and people with children or pushchairs, so an accessible door is provided next to them and signed.

    A program selector is a keyed switch that sets how the door works, for example automatic two-way, exit only, fixed open, or locked. The choice of program affects safety and escape routes, so its key is held by people designated by management.

    A moving leaf stores kinetic energy:

    E=12mv2E = \tfrac{1}{2} m v^2

    where EE is kinetic energy (J), mm the mass of the leaf (kg), and vv the leaf speed (m/s). If the leaf is stopped by a person’s body over a compression distance ss (m), the average force is roughly

    F=EsF = \frac{E}{s}

    with FF in newtons. This model is rough because it ignores the motor’s push, but it shows that speed appears as a square, so speeding up a door raises the hazard quickly.

    Motion sensors and safety sensors

    A motion sensor, or activation sensor, is a sensor, usually microwave, that detects a person moving toward the door and commands the door to open. A presence sensor is a safety sensor, usually active infrared, that detects a person or object standing still in the threshold area and holds the door open or stops it. A guest who stops in the threshold is not seen by the motion sensor; the presence sensor protects them.

    Approved Document M asks that activation, safety features, and the time allowed for entry and exit be considered for people who cannot react quickly. Powered entrance doors are judged satisfactory if their sensors are set so that the doors open early enough and stay open long enough for safe entry and exit, and if they have a safety stop that is activated when the doors begin to close while a person is passing through. If each leaf travels a width bb (m) at speed vdv_\text{d} (m/s), its opening time is

    tb=bvdt_\text{b} = \frac{b}{v_\text{d}}

    and the motion sensor needs to detect a person walking at speed vov_\text{o} (m/s) at least

    d=vo tbd = v_\text{o} \, t_\text{b}

    from the door line. This calculation ignores leaf acceleration and reaction time, so the result is a lower bound.

    The British workplace regulations require powered doors to have suitable and effective features to prevent injury by trapping any person. The Approved Code of Practice gives examples of such features: a sensitive edge or other detector that stops or reverses the movement when obstructed, a device that limits the closing force so that it is not enough to cause injury, or a control that must be held during the whole closing movement, which is suitable only where the risk is low and the movement slow. Approved Document K asks powered doors to have safety features to prevent injury to people who are struck or trapped, a readily identifiable and accessible stop switch, and the ability to open manually or automatically in a power failure when necessary for health or safety.

    Two HSE lessons about powered gates apply in the lobby. First, safety comes from the combination of components and the way they are connected: a category 2 controller produces only a category 2 system even if other components are higher, and a good system does not just stop when it meets an obstruction but also backs off a short distance so that a person is not held. Second, where the technology permits, the safety function is checked before each movement. A controller that monitors its sensors refuses to run automatically when a sensor fails, but a sensor covered by a sticker is not always read as failed.

    Crushing, shearing, and impact hazards

    HSE writes that much of its advice on powered gates also applies, to some extent, to pedestrian doors, and the hazards are the same: being hit by moving parts, crushed between fixed and moving parts, trapped, caught on moving parts, and electrocuted. On a sliding door, a crushing point lies between the leading edges of the two leaves where they meet and between a leaf and the frame; a shear gap lies between a moving leaf and the fixed glass panel or wall it passes, where children’s fingers and hands can be drawn in.

    On a revolving door, the greatest hazard is at the wing edge passing the end of the drum wall, where feet, hands, or suitcase wheels are trapped, and at the heels of a person slower than the wing behind them. The speed of a point on a wing is proportional to its distance from the shaft:

    v=ωr,ω=2πn60v = \omega r, \qquad \omega = \frac{2\pi n}{60}

    where vv is the speed of the point (m/s), ω\omega the angular speed (rad/s), rr the distance of that point from the shaft (m), and nn the rotational speed (revolutions per minute). The wing tip moves fastest.

    For doors and gates primarily for vehicular use, HSE notes that the revised European standards keep the force limits, basically 400 N for crushing and 1,400 N for impact, and asks that forces be as low as possible and verified by testing after installation where force limitation is the primary means of safety. The limits for pedestrian doors are in other standards that are not quoted here; the 400 N figure is used in this chapter only as a comparison of magnitude. Any limit is a maximum, not a target, and measuring it requires force measuring equipment and a competent person.

    Lobby doors are almost always glazed, so impact hazards also come from glass that cannot be seen. The British workplace regulations require transparent surfaces in doors to be of safety material or protected, and to be marked where necessary to make them apparent. Approved Document K asks for glass doors and glazed screens to carry manifestation, that is, markings at two heights, between 850 and 1,000 mm and between 1,400 and 1,600 mm above the floor, that contrast with the background seen through the glass from inside and outside, in the form of a logo or sign at least 150 mm high or a band at least 50 mm high. Sliding doors also need a stop at the end of the track so that the leaf does not come off the track, and a retaining rail that prevents the leaf from falling if the suspension or rollers leave the track.

    Emergency modes, power failure, and escape routes

    The lobby door is often also the final exit during an evacuation, so its behavior in a fire and in a power failure is set by the designer. Approved Document B for England asks that revolving doors, automatic doors, and turnstiles placed across escape routes meet one of two conditions. Under the first, they are automatic doors of the required width whose failsafe system provides outward opening from any open position, or that have a monitored failsafe system to open the doors if the utility electricity supply fails, or that failsafe to the open position if the power fails. Under the second, non-automatic swing doors of the required width are provided immediately adjacent. Fail-safe means that a failure of power or of a component leaves the door in a state that is safe for people leaving.

    The British workplace regulations require powered doors to be operable by hand where necessary for safety, unless they open automatically if the power fails. The Approved Code of Practice adds that tools needed for manual opening are readily available at all times, and that the person opening the door is not put at risk if the power is restored while the door is being opened. Approved Document M asks that powered entrance doors revert to manual control or fail safe in the open position in a power failure.

    The required width is calculated from the number of people. Approved Document B gives minimum widths of escape routes and exits: 750 mm for at most 60 people, 850 mm for 110 people, 1,050 mm for 220 people, and 5 mm per person for more than 220 people. A revolving door is not counted as exit width unless it meets the conditions above, so what is counted is usually the fail-safe automatic sliding door and the swing door next to it.

    For the building technician, there are three consequences. First, a night lock is a program that locks the automatic door outside busy hours; that program, and also a bolt on the side swing door, can turn a valid escape route into a dead end, so the decision belongs to building management together with the person responsible for fire safety. Second, the connection between the door and the fire alarm panel (Chapter 19) is tested by the door contractor together with the alarm contractor, and the technician does not change, delay, or disconnect it. Third, this chapter gives no steps for activating, overriding, or switching off an emergency mode; the technician records whether the door behaves as the user instructions state during scheduled tests.

    Daily checks and records

    The British workplace guidance includes powered doors among the examples of equipment that require a system of maintenance. HSE adds that users should know how to switch the machine off or put it into a safe condition promptly in the event of danger or malfunction. Daily checks follow the user instructions for that door, before the lobby gets busy, and generally cover:

    1. The movement area of the leaves and wings is free of advertising boards, folded mats, trolleys, and pots; nothing is in front of the sensor window.
    2. The sliding door opens when a person approaches, stays open while a test object stands still in the threshold, and stops or opens again when the test object is in the path of a closing leaf, according to the user instructions. Tests use a test object, not a person’s body.
    3. The revolving door stops when tested with a test object according to the user instructions, and the stop button is easy to reach.
    4. The leaves are not tilted, do not rub or make noise, the glass is not cracked, the manifestation is intact, and the brushes and edge rubbers are not torn.
    5. The accessible side door is not locked while the building is occupied, and its direction sign is readable.
    6. The status light or display on the program selector shows no fault.

    The results are recorded with the date, name, and action: passed, cleaned, reported, or taken out of use. The same record holds contractor visits and the settings they changed, so that the speed-up in the opening case can be traced. Cleaning the sensor window is light maintenance; adjusting the sensor angle is not.

    Work limits, changes, and electrical work

    Anyone working on powered doors and gates is responsible for what they do and for leaving the equipment in a safe condition, which may include switching it off and isolating the power if it has to be left unsafe; substantial modifications may require reassessment. HSE also warns that disconnecting safety devices while still live can create significant uncontrolled crushing hazards, and that doors found to be dangerous are taken out of use until all safety concerns have been addressed.

    Speeding up the door, shortening the hold-open time, narrowing the sensor field, or changing the night lock program alters the level of safety and the escape route, even if it is done with a few buttons. Such requests are handed to the door contractor, who reassesses them together with building management and the person responsible for fire safety. Cool air escaping through the lobby door is dealt with by design, for example a vestibule between two doors or an air curtain.

    The door operator is electrical equipment. Permenaker 12/2015 states that planning, installation, modification, and maintenance are carried out by an Ahli K3 bidang Listrik (electrical occupational safety and health expert), and installation and maintenance may be carried out by a Teknisi K3 Listrik (licensed electrical safety technician), either within the company or at a PJK3 (occupational safety and health services company). An operator box with water ingress, stripped cables, or a burning smell is reported and is not opened by the building technician; opening it also requires access for work at height according to Chapter 10 · Safety and energy isolation according to Chapter 76 · Electrical & Control.

    Worked example

    The figures in the examples below are practice figures unless their origin is stated.

    Example 1: leaf energy at two speeds. One glass leaf of a sliding door has a mass of 70 kg. At 0.5 m/s its energy is E=0.5×70×0.52=8.75E = 0.5 \times 70 \times 0.5^2 = 8.75 J, and at 0.3 m/s its energy is E=0.5×70×0.32=3.15E = 0.5 \times 70 \times 0.3^2 = 3.15 J. Reducing the speed by 40 percent reduces the energy to 3.15/8.75=0.363.15/8.75 = 0.36 times the original. The speed setting is decided by the door contractor from a risk assessment, not from complaints about cool air.

    Example 2: rough force when the leaf is held by a body. If the energy of the leaf in Example 1 is absorbed by a shoulder and clothing compressed by 20 mm, the average force is F=8.75/0.02=438F = 8.75/0.02 = 438 N at 0.5 m/s and F=3.15/0.02=158F = 3.15/0.02 = 158 N at 0.3 m/s. The first figure is above the 400 N comparison, not counting the motor’s push, and explains why a door whose sensor is covered is not run automatically.

    Example 3: detection distance and opening time. Each leaf of a two-leaf door travels 0.8 m at 0.5 m/s, so tb=0.8/0.5=1.6t_\text{b} = 0.8/0.5 = 1.6 s. A guest walking briskly at 1.4 m/s needs to be detected at least d=1.4×1.6=2.24d = 1.4 \times 1.6 = 2.24 m from the door line. If the motion sensor field reaches only 1.5 m, the guest arrives at the door line after 1.5/1.4=1.071.5/1.4 = 1.07 s, when each leaf has opened only 1.07×0.5=0.5361.07 \times 0.5 = 0.536 m, so the opening is 2×0.536=1.072 \times 0.536 = 1.07 m out of 1.6 m. A guest with a wide suitcase can brush a leaf that is still moving; this finding is reported to the contractor.

    Example 4: a slow guest and the presence sensor. A guest with a mobility aid walks at 0.5 m/s and has to cross a threshold area 1.2 m deep, so they need 1.2/0.5=2.41.2/0.5 = 2.4 s. The hold-open time after the motion sensor stops seeing movement is set to 2.0 s. If the presence sensor is covered by a sticker, the door starts to close when the guest has covered only 0.5×2.0=1.00.5 \times 2.0 = 1.0 m and still has 1.2−1.0=0.21.2 - 1.0 = 0.2 m in the path of the leaves, as in the opening case. With a working presence sensor, the door stays open while the guest is in the threshold. The action: the sticker is removed, the door is tested with a test object, and the event is reported; the hold-open time is not adjusted by the technician.

    Example 5: wing speed of a revolving door. A four-wing revolving door has a diameter of 3.6 m, so r=1.8r = 1.8 m, and turns at 4 revolutions per minute. Its angular speed is ω=2π×4/60=0.419\omega = 2\pi \times 4/60 = 0.419 rad/s, and the wing tip moves at 0.419×1.8=0.7540.419 \times 1.8 = 0.754 m/s. One revolution takes 60/4=1560/4 = 15 s, so one compartment between two wings passes the opening in 15/4=3.7515/4 = 3.75 s. A guest walking at 0.5 m/s near the drum wall is slower than the wing behind them, and their heels can be struck. The answer is an accessible side door that is signed.

    Example 6: exit width and the night lock. An event in the ballroom is attended by 300 people, and their escape route passes through the lobby. According to the Approved Document B table, more than 220 people require 5 mm per person, that is, 300×5=1,500300 \times 5 = 1{,}500 mm. The revolving door is not counted. The double swing door next to it, with two leaves of 850 mm each, gives 2×850=1,7002 \times 850 = 1{,}700 mm, which is enough. If one leaf is bolted for the night lock, 850 mm remains, which under the same table serves at most 110 people. This finding is reported to the person responsible for fire safety before the event; the width for the building itself is read from its design documents.

    Stop conditions

    1. A person is trapped, struck, or falls at the sliding or revolving door: stop the door with the stop switch designated in the user instructions, help the injured person and call the P3K (first aid) officer or medical staff, put up barriers, direct guests to another door, and do not run it automatically again until the door contractor has inspected it; report to the duty engineer and management.
    2. A safety sensor is covered, dirty, or damaged, or the door does not stop and open again when tested with a test object according to the user instructions: the designated person stops automatic use according to the user instructions; direct guests to the side door, and call the door contractor.
    3. There is a request to speed up the door, shorten the hold-open time, narrow or switch off a sensor, or change the emergency mode and night lock: refuse and report to the chief engineer; changes only by the door contractor after reassessment together with building management and the person responsible for fire safety.
    4. A leaf is tilted, has come off the track, rubs heavily, the retaining rail or end stop is damaged, or the glass is cracked or broken: stop use, put up barriers around the movement area, and call the door contractor.
    5. A door on an escape route does not open on a fire alarm or in a power failure, or the side door is locked while the building is occupied: report immediately to the person responsible for fire safety; the technician does not dismantle the operator or change the program.
    6. The operator box has water ingress, stripped cables, a burning smell, or a shock is felt when touching the frame: do not open the operator box; power is disconnected at the panel by the designated person and the work is handed to an authorized electrician.
    7. The revolving door does not stop when tested with a test object according to the user instructions, the stop button does not work, or children are playing inside the drum: stop use of the revolving door, direct guests to the side door, and call the door contractor.
    8. The work would require opening the operator cover above the threshold: postpone it until the contractor or an authorized technician arrives with energy isolation, LOTO, a work permit, and suitable access for work at height.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    The sensor that opens the door also protects people.

    Why is it wrong?

    The motion sensor responds only to movement and does not see a person who stops in the threshold. A person standing still is protected by the presence sensor and the safety features on the leaf, and both are tested separately.

    Common misconception

    A door that closes faster saves more, so it may be sped up.

    Why is it wrong?

    Leaf energy rises with the square of speed, and a short hold-open time traps slow guests. Loss of cool air is dealt with by entrance design, not by speed settings.

    Common misconception

    A revolving door suits every guest.

    Why is it wrong?

    Approved Document M does not consider revolving doors accessible and asks for an accessible door immediately next to them. Guests with wheelchairs, mobility aids, pushchairs, or large suitcases are directed to that door.

    Common misconception

    A bolt on the side door is no problem because the revolving door is still there.

    Why is it wrong?

    A revolving door is not counted as an escape route unless it meets special conditions, so a locked side door can close a valid escape route.

    Common misconception

    If the door stops when it touches a person, the door is safe.

    Why is it wrong?

    A door that stops only after touching a person means its sensor did not detect that person first. The force at contact depends on speed and settings, and can only be proven by measurement by the contractor.

    Chapter 38 on frames, doors, and locks covers door closers and fire doors, and Chapter 18 · Mechanical & Mechatronics on automatic gates covers crushing hazards and manual release on vehicle gates. Chapter 70 · Electrical & Control on functional safety of machinery explains categories of safety control systems, Chapter 59 · Electrical & Control on discrete sensors explains photoelectric sensors, Chapter 94 · Electrical & Control on access control covers card readers that open doors, and Chapter 19 and Chapter 106 · Electrical & Control cover fire alarms and exit signs on escape routes.

    Exercises and worked solutions

    The figures in the exercises are for practice.

    Try to answer first, then open the worked solution.

    1. One leaf of a sliding door with a mass of 90 kg moves at 0.4 m/s. What is its energy, and what is the rough average force if it is absorbed over a compression of 15 mm?

      Check my answer
      See the worked solution

      The energy is 0.5×90×0.42=7.20.5 \times 90 \times 0.4^2 = 7.2 J, and the average force is 7.2/0.015=4807.2/0.015 = 480 N. This rough figure shows that a heavy leaf held by a body can press with a large force, so the sensors and the speed setting are checked by the contractor.

    2. The decoration team sticks a sticker on the glass right in front of the lobby door sensor window. What is wrong, and what does the technician do?

      Check my answer
      See the worked solution

      A sticker in front of the sensor window can blind the presence sensor without the controller treating it as failed, so the door can close onto a person. The technician removes the sticker, tests the door with a test object according to the user instructions, records the event, and asks the decoration team not to stick anything in the sensor area.

    3. A revolving door with a diameter of 3.0 m turns at 4 revolutions per minute. What is the speed of its wing tips?

      Check my answer
      See the worked solution

      The angular speed is 2π×4/60=0.4192\pi \times 4/60 = 0.419 rad/s, and the wing tip at a radius of 1.5 m moves at 0.419×1.5=0.6280.419 \times 1.5 = 0.628 m/s. A guest walking slower than that near the drum wall can be struck by the wing behind them, so the side door is still needed.

    4. The night manager wants to bolt the side swing door and leave only the revolving door open after 23:00. What is the technician’s answer?

      Check my answer
      See the worked solution

      A revolving door is not counted as an escape route unless it meets special conditions, so bolting the side door can close a valid escape route while guests are still in the building. The technician does not decide this; they report it to the chief engineer and the person responsible for fire safety for assessment against the design documents.

    5. The power fails and the sliding lobby door stops half open. What should happen according to the British guidance, and what does the technician do?

      Check my answer
      See the worked solution

      The British guidance asks that powered doors on escape routes open automatically or can be opened by hand in a power failure, with tools readily available, and that entrance doors revert to manual control or fail safe open. The technician directs guests to the side door, calls the designated person according to the user instructions, does not open the operator box, and reports the door’s behavior to the contractor.

    6. Each leaf travels 0.75 m at 0.5 m/s. What is the minimum detection distance for a guest walking at 1.2 m/s?

      Check my answer
      See the worked solution

      The opening time is 0.75/0.5=1.50.75/0.5 = 1.5 s, so the minimum detection distance is 1.2×1.5=1.81.2 \times 1.5 = 1.8 m. This calculation ignores leaf acceleration and reaction time, so the real distance needed is larger and is set by the contractor.

    References

    External sources

    • Workplace health, safety and welfare. Workplace (Health, Safety and Welfare) Regulations 1992. Approved Code of Practice and guidance, L24 (Second edition)hse.gov.uk
    • Approved Document K: Protection from falling, collision and impact, 2013 editionassets.publishing.service.gov.uk
    • Approved Document M: Access to and use of buildings, Volume 2: Buildings other than dwellingsassets.publishing.service.gov.uk
    • Approved Document B (fire safety) volume 2: Buildings other than dwellings, 2019 edition incorporating 2020, 2022, 2025 and 2026 amendments collated with 2029 amendmentsassets.publishing.service.gov.uk
    • The basicshse.gov.uk
    • Ensuring powered doors and gates are safehse.gov.uk
    • Revision of Standards for Powered Doors, Gates and Barriershse.gov.uk
    • Peraturan Menteri Ketenagakerjaan Nomor 12 Tahun 2015 tentang Keselamatan dan Kesehatan Kerja Listrik di Tempat Kerjajdih.kemnaker.go.id

    Revision history

    DateVersionChange
    November 15, 20261First published

    How to cite

    Kurnia (2026). Hotel lobby automatic doors: automatic sliding and revolving doors, motion sensors and safety sensors, crushing and impact hazards, emergency modes and escape routes, daily checks, and work limits. ARSTEMA Academy. Revised November 15, 2026. arstema.com/en/academy/konsep/pintu-otomatis-lobi-hotel-pintu-geser-dan-pintu-putar-otomatis-sensor-gerak-dan-sensor-keselamatan-bahaya-jepit-dan-benturan-mode-darurat-dan-jalur-keluar-pemeriksaan-harian-serta-batas-pekerjaan

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated

    Safety limits still apply. This quiz tests reasoning; it doesn’t authorize mixing, adjusting, dismantling, live measurement, or field action.

    1

    One leaf of a sliding door with a mass of 90 kg moves at 0.4 m/s. What is its energy, and what is the rough average force if it is absorbed over a compression of 15 mm?

    2

    The decoration team sticks a sticker on the glass right in front of the lobby door sensor window. What is wrong, and what does the technician do?

    3

    A revolving door with a diameter of 3.0 m turns at 4 revolutions per minute. What is the speed of its wing tips?