    Buildings & Facilities · Chapter 38Applied

    By Kurnia · Published November 13, 2026 · Version 1 · 21 min read

    Door frames, doors, and locks

    frame and door leaf materials, hinges and automatic door closers, mechanical locks and master key systems, fire doors, adjustment and maintenance, and the limits of the work

    On a night round in a hotel, the seventh-floor emergency stair door is found wedged open with a rubber wedge, its door closer leaks oil and no longer latches the door, and a contractor reports that the fifth-floor master key has been lost. This chapter covers door frames, doors, and locks from the building technician’s side: frame and door leaf materials and their damage, hinges, how many are needed, and the force they carry, automatic door closers and magnetic hold-open devices, mechanical locks and master key systems with key control, fire doors and exit doors from the inspection side, and adjustment, maintenance, and inspection schedules. The fire door figures come from UK government guidance and the hinge count rule from a United States Department of Defense facility specification, written as data from their countries of origin, because Indonesian rules on fire doors cannot yet be confirmed from an official source. Repairing fire doors, changing exit door hardware, replacing master-keyed cylinders, and electric locks are set out as work for authorized parties; the chapter does not cover how to open a lock without a legitimate key.

    Section you’re reading: Chapter opening

    At 23:40, the night technician of a hotel walks round the seventh floor and finds the emergency stair door wide open, wedged with a rubber wedge by a housekeeping attendant so that the linen trolley can pass easily. When the wedge is removed, the door closes slowly but stops two fingers short of latching, and there are drops of oil on the floor below its door closer. On the same floor, the door of room 712 has been scraping the floor since the afternoon. The next morning the painting contractor reports that the fifth-floor master key it borrowed has been lost. UK government guidance for sleeping accommodation names damaged fire doors and fire doors wedged open as one of the ways fire and smoke spread through a building.

    Those four findings concern different functions: the stair door holds back smoke, the door closer shuts it without relying on people, the door leaf hangs on its hinges, and the master key opens dozens of rooms at once. A technician who understands how each one works can decide which ones may be adjusted on site and which ones are handed over.

    Scope

    This chapter covers door frames, door leaves, hinges, automatic door closers, mechanical locks, master key systems, fire doors, and exit doors from the building technician’s side: inspecting, measuring, tightening, lubricating, adjusting ordinary doors, recording, and reporting. Fire doors and exit doors are covered from the inspection side. Indonesian rules on fire doors and exit door hardware cannot yet be confirmed from an official source as of November 2026, because their text could not be opened from the JDIH of the Ministry of Public Works; ask the building fire protection consultant and the local fire service. The fire door figures in this chapter are UK data, and the hinge count rule is United States specification data.

    Access control, electric locks, card readers, and exit buttons are covered in Chapter 94 · Electrical & Control on door access control. Inspection-level fire protection is in Chapter 17, the fire alarm panel that releases hold-open devices in Chapter 19, and lift keys in Chapter 24 on lifts in buildings. Paint on door frames and doors is covered in Chapter 37 on building paints and coatings, corrosion of steel frames in Chapter 19 · Chemistry on electrochemical corrosion, wall cracks around frames in Chapter 36 on cracks in walls and concrete, forces and moments in Chapter 1 on loads and load paths, and work permits in Chapter 76 · Electrical & Control.

    This chapter does not cover how to open a lock without a legitimate key, how to bypass door closers, hold-open devices, or emergency door hardware, or how to change the program of electric locks. Outside the building technician’s authority: repairing, cutting, planing, or replacing parts of fire doors and their frames, replacing the seals, glazing, or hardware of fire doors, changing exit door hardware, replacing cylinders or changing the arrangement of the master key system, and making new door openings in walls. That work belongs to competent fire door contractors, the locksmith or key system supplier appointed by management, and the fire protection consultant.

    Door frames and door leaves

    The door frame is the fixed frame set into the wall to which the hinges and the strike plate are fitted. The door leaf is the part that swings or slides. Building door frames and door leaves are made of wood, steel, aluminum, or plastic. A wooden door leaf can be a panel door with a frame and infill panels, or a flush door with a frame faced with board on both sides and a hollow or solid core.

    Wood swells and shrinks with its moisture content, so a door that fits in the dry season can rub on its frame in the rainy season; wood whose moisture content reaches 20 percent or more is at high risk from decay fungi and insects. The foot of the frame near wet floors and the outside sill exposed to rain need attention. Steel frames rust from the bottom when the floor is mopped often or water stands at their foot, as covered in Chapter 19 · Chemistry on electrochemical corrosion. On aluminum and plastic, damage is usually at the corner joints and at stripped hinge screw holes.

    A good frame is installed square, meaning its corners are at 90 degrees. The way to check this without special tools is to compare the two diagonals of the frame opening. For an opening of width ww and height hh, the correct diagonal is:

    d=w2+h2d = \sqrt{w^2 + h^2}

    with dd, ww, and hh in millimeters. If the two measured diagonals differ noticeably, the frame is out of square, and the door leaf will rub at one corner and leave a gap at another. A frame that is out of square because its wall is moving or cracked is not a door problem; the wall is inspected according to Chapter 36 on cracks in walls and concrete.

    Ordinary wooden doors give some limited protection against fire, but only a purpose-built fire door tested to a standard provides the necessary protection.

    Hinges and the load of the door leaf

    A hinge is the device that hangs the door leaf on the frame and forms its pivot axis. An ordinary door hinge consists of two metal leaves set into the edge of the door leaf and the frame with a pin in the middle. The United States Department of Defense facility specification for door hardware calls for antifriction-bearing hinges on high-frequency doors, extra-heavy doors, and doors fitted with door closers, and plain-bearing hinges on low-frequency doors up to 900 mm wide without closers.

    The same specification gives a hinge count rule: two hinges for doors 1,500 mm or less in height, plus one hinge for each additional 750 mm of height or fraction thereof. Written as a formula for a door of height HH above 1,500 mm:

    N=2+⌈H−1,500750⌉N = 2 + \left\lceil \frac{H - 1{,}500}{750} \right\rceil

    where NN is the number of hinges, HH the height of the door leaf in mm, and the ceiling brackets mean rounding up. For fire doors, UK guidance states that the number, size, and quality of hinges must be correct, normally a minimum of three hinges, with the manufacturer’s instructions followed closely. On a fire door, the manufacturer’s rules and the door’s test evidence decide, not a general formula.

    The door leaf hangs beside the hinge line, so its weight turns the leaf away from the frame at the top. If the weight of the leaf WW acts at the middle of its width bb, and the vertical distance between the top and bottom hinges is heh_e, the balance of moments about the bottom hinge gives the horizontal force on the top hinge:

    F=W×b2×heF = \frac{W \times b}{2 \times h_e}

    with FF and WW in newtons, bb and heh_e in meters. The top hinge is pulled out of the frame with force FF and the bottom hinge is pushed into the frame with a force of the same size, as covered in Chapter 1 on loads and load paths. That is why the top hinge screws tend to loosen first, and a door that drops on the latch side is checked starting from the top hinge. This formula ignores the force of the door closer and of people hanging on the leaf, so the result is a lower bound.

    Automatic door closers and hold-open devices

    An automatic door closer is a device that stores spring energy when the door is opened and uses an oil damper to control how fast the door closes again. It can be an exposed overhead closer with an arm, a closer concealed in the frame or the door leaf, or a floor spring. The closer size is chosen according to the manufacturer’s printed recommendations. Adjustable closers have speed adjustment valves that are set according to the manufacturer’s manual; drops of oil below a closer usually mean that its damper is leaking, and the closer needs replacing, not adjusting.

    For fire doors, UK guidance calls for every fire door, other than those to locked cupboards and service ducts, to be fitted with a controlled self-closing device that will effectively close the door from any angle; rising butt hinges are not suitable as a closer because they cannot close and latch the door from any angle, and spring hinges are unlikely to be suitable. The check is simple and needs no tools: the door is opened fully and let go, then opened to about 15 degrees and let go; in both cases the door must close fully into its frame, overcoming the resistance of the latch or friction with the floor.

    An automatic door hold-open device holds a fire door open in normal use and releases it when there is a sign of fire. UK guidance calls for the device to release the door when smoke is detected, when the alarm is operated manually, when the alarm system fails, or when the power fails, and the door must still be able to be closed by hand. When checking a door held by a magnet, its closer is tested with the test button where provided, not by pulling the door from its magnet. The link between hold-open devices and the alarm panel is the domain of the fire alarm contractor, as covered in Chapter 19 on fire alarm panels.

    Mechanical locks and master key systems

    The latch is a beveled bolt pushed by a spring that enters the strike plate in the frame when the door closes and is withdrawn by the handle. The deadbolt is a square-ended bolt that moves only when turned with a key or a thumb turn. A mortise lock is fitted into a pocket in the edge of the door leaf and usually holds both the latch and the deadbolt in one case. The cylinder is the part of the lock that takes the key and turns only when the cuts of the key match the arrangement inside it.

    A master key system is an arrangement of cylinders that can be opened by their own key and by the keys of the levels above. In hotels the arrangement is usually three levels: the room key opens one room, the floor master key opens all rooms on one floor for housekeeping, and the grand master key opens all rooms. The United States Department of Defense facility specification for door hardware warns against requiring higher levels of master keying than necessary, because each level decreases the security of the locks.

    Key control is the records and rules that make sure the holder of every key is known. The same specification calls for keys to be stamped with a key control symbol, for room numbers not to be placed on keys, and for file and duplicate keys to be tagged and kept in a key cabinet. In a building, that control means a master key handover book signed each time a key is borrowed and returned, a recorded number of duplicates, and a ban on copying keys anywhere other than through the appointed locksmith. A lost master key means that every cylinder below it has to be treated as unsafe until its cylinder is replaced or its arrangement is changed by the locksmith or key system supplier appointed by management.

    Electric locks, access cards, and exit buttons are covered in Chapter 94 · Electrical & Control on door access control. This chapter does not cover how to open a lock without a legitimate key. If an occupant is locked out, the door is opened by a legitimate key holder according to the management procedure, or by a locksmith with written authorization from management.

    Fire doors and exit doors

    A fire door is an assembly of door leaf, frame, hinges, closer, and seals tested to hold back fire and smoke for a set time. UK guidance classifies fire doors by duration, for example E30 or FD30S for 30 minutes; the suffix S means the door is fitted with smoke seals. The gap between a timber fire door leaf and its frame is 2 to 4 mm, and that gap is normally protected by an intumescent strip, a strip that expands when exposed to heat and closes the gap. The UK fire door inspection guidance states that the gap must never be more than 4 mm, except at the bottom of the door, where it is kept as small as practicable without the door snagging on the floor.

    That inspection guidance also gives a list that building technicians can use without tools:

    • There is no damage to the door leaf, the frame, or the surrounding wall, for example split wood, damaged glazing, a warped leaf, or a hole where a lock has been removed, and no alteration that could reduce its fire resistance.
    • The hinges have no obvious defects, for example missing or loose screws.
    • Intumescent strips and smoke seals, if present, are undamaged, touch the edge of the leaf or the frame, and have not been painted over during decorating.
    • The gap between the leaf and the frame is not too large.
    • The self-closing device closes the door fully from any angle.

    Fire doors fitted with self-closing devices carry a sign reading fire door keep shut on both sides, and fire doors to cupboards or ducts that do not close by themselves because they are always locked carry a sign reading keep locked on the outside. A door wedged open cannot hold back smoke, even when all its parts are intact.

    An exit door is a door that people pass through to reach a place of safety in an emergency. UK guidance for sleeping accommodation states that doors on escape routes and final exit doors should normally open in the direction of travel and be quickly and easily openable without a key, preferably with only one fastening. Buildings visited by people who are not familiar with them use panic exit bars, while areas used only by staff familiar with the building may use push pads or lever handles; electromechanical locking devices on exit doors are normally unacceptable unless they have a manual means of opening such as a push bar. The electric lock mode on exit doors is set by the fire protection consultant, as Chapter 94 · Electrical & Control on door access control makes clear.

    Adjustment, maintenance, and inspection schedules

    Light maintenance of ordinary doors is the building technician’s work: tightening hinge screws and replacing missing ones, replacing stripped screws with longer screws that suit the hinge size, lubricating hinges and latches with the lubricant the manufacturer recommends, moving the strike plate so that the latch enters without force, and adjusting the closer speed according to its manual. An ordinary door that scrapes the floor has its hinges checked first, because a leaf that drops on the latch side can be caused by a loose top hinge rather than a swollen leaf.

    Fire doors are treated differently. Their inspection is simple and can be done by maintenance staff, but when a door needs repair or replacement, that work is done by a competent contractor as soon as reasonably practicable. Planing the bottom of a fire door leaf, adding holes for locks or hooks, or replacing the hinges with other hinges can change the door’s test result, so it is not done by the technician.

    UK guidance for sleeping accommodation gives an example schedule that is not intended to be prescriptive:

    IntervalDoor check
    Dailydoors on escape routes swing freely, close fully, and are in good repair; security devices on exit doors work
    Monthlyfire doors are in good working order and close correctly, frames and seals are intact
    Annualall fire separation and compartmentation is inspected and repaired

    For apartment buildings in England whose top storey is more than 11 m above ground, the 2022 fire safety regulations require fire doors in communal areas to be checked at least every 3 months, and best endeavors to check flat entrance doors at least every 12 months. Hotels in Indonesia can use that schedule as a comparison until the local rules are confirmed. Each inspection is recorded with the door number, the finding, and its follow-up.

    Worked example

    The numbers in the examples below are practice numbers, unless their origin is stated.

    Example 1: number of hinges. A hotel room door 2,100 mm high needs N=2+⌈(2,100−1,500)/750⌉=2+⌈0.8⌉=3N = 2 + \lceil (2{,}100 - 1{,}500)/750 \rceil = 2 + \lceil 0.8 \rceil = 3 hinges under the United States specification rule. A function room door 2,400 mm high needs N=2+⌈900/750⌉=2+⌈1.2⌉=4N = 2 + \lceil 900/750 \rceil = 2 + \lceil 1.2 \rceil = 4 hinges. If that room door is a fire door, the count of three hinges matches the usual figure in UK guidance, but the number and type of hinges used are still those from the door manufacturer.

    Example 2: force on the top hinge. A fire door leaf has a mass of 60 kg, a width of 0.9 m, and a distance of 1.8 m from the top hinge to the bottom hinge. Its weight is W=60×9.81=588.6W = 60 \times 9.81 = 588.6 N, and the pull on the top hinge is F=588.6×0.9/(2×1.8)=147.2F = 588.6 \times 0.9/(2 \times 1.8) = 147.2 N. An ordinary room door leaf of 30 kg with the same dimensions gives F=294.3×0.9/3.6=73.6F = 294.3 \times 0.9/3.6 = 73.6 N. A door twice as heavy puts twice the force on its top hinge screws.

    Example 3: an out-of-square frame. The frame opening of room door 712 measures 900 mm by 2,100 mm. The correct diagonal is d=9002+2,1002=2,284.7d = \sqrt{900^2 + 2{,}100^2} = 2{,}284.7 mm. The technician measures the two diagonals as 2,291 mm and 2,278 mm, a difference of 2,291−2,278=132{,}291 - 2{,}278 = 13 mm. That difference explains why the door rubs at one bottom corner. Before planing that ordinary door, the technician checks the top hinge screws and the wall around the frame, because a frame that has changed shape can come from a moving wall.

    Example 4: fire door gaps. The technician measures the gap of the seventh-floor stair door at seven points: hinge side 3, 3, and 4 mm, head 5 mm, latch side 3 and 6 mm, and bottom 9 mm. Compared with the 4 mm limit in the UK guidance, two points exceed the limit, the head at 5 mm and the latch side at 6 mm. The bottom gap is judged separately, because that guidance asks only for the bottom gap to be as small as practicable without snagging on the floor. This door is reported for repair by a fire door contractor; its leaf is not planed and the gaps are not filled with whatever material is at hand.

    Example 5: workload of the monthly inspection. A ten-story hotel has on each floor two stair doors, one corridor subdivision door, and one riser room door, so there are 10×4=4010 \times 4 = 40 fire doors. If one door is checked in 3 minutes, the monthly inspection takes 40×3=12040 \times 3 = 120 minutes, that is 2 hours, and in a year 12×2=2412 \times 2 = 24 hours. That inspection is scheduled as fixed work, not as spare time.

    Example 6: a lost floor master key. An eight-story hotel with 30 rooms per floor has 8×30=2408 \times 30 = 240 room cylinders. A three-level arrangement needs 240 room key types, 8 floor master key types, and 1 grand master key, that is 240+8+1=249240 + 8 + 1 = 249 key types. The lost fifth-floor master key makes the 30 room cylinders on that floor unsafe. If the locksmith needs 15 minutes per cylinder, the work takes 30×15=45030 \times 15 = 450 minutes, that is 7.5 hours. If the grand master key is lost, all 240 cylinders are affected, that is 240×15=3,600240 \times 15 = 3{,}600 minutes or 60 working hours. That is why the number and holders of grand master keys are kept as few as possible.

    Stop conditions

    1. A fire door or exit door is found wedged, tied open, or with its closer detached from its arm: remove the wedge or tie if the door can close by itself, record the location, and report to the building management and the fire safety officer; do not fit a homemade hold-open device.
    2. A fire door does not close fully from every angle, does not latch, or its closer is dripping oil: put up a defect tag, report, and hand the repair over to a competent fire door contractor; do not remove the closer and do not adjust it outside the manufacturer’s manual.
    3. A fire door gap is more than 4 mm at the sides or head, an intumescent strip or smoke seal is damaged or painted over, the door leaf is cracked or warped, the glazing is damaged, or there is a hole where a lock was removed: do not plane, cut, or patch it yourself; hand it over to a competent fire door contractor.
    4. An exit door is locked from inside, needs a key or code to get out, is blocked by goods, or its push bar does not open the door: report at once to the building management and the fire safety officer, remove the obstructing goods, and do not alter or bypass the door hardware; electric locks are dealt with according to Chapter 94 · Electrical & Control on door access control.
    5. A magnetic hold-open device does not release the door when the test button is pressed or when the alarm sounds: close the door by hand if it is safe, report to the fire alarm contractor, and record the finding according to Chapter 19 on fire alarm panels.
    6. A master key or grand master key is lost, or there is an unrecorded duplicate: report to management and security the same day; replacing cylinders or changing the key arrangement is done by the appointed locksmith or key system supplier, and the technician does not copy keys.
    7. The technician is asked to open a locked door without a legitimate key, or without authorization from management and the occupant: refuse; the door is opened by a legitimate key holder according to the management procedure, or by a locksmith with written authorization from management.
    8. The frame is cracked, has come loose from the wall, or the wall around it is cracked, or there is a request to make a new door opening in a fire-resisting wall: stop the door work and report to the building management; the wall is inspected according to Chapter 36 on cracks in walls and concrete, and a new opening in a fire-resisting wall is decided by the fire protection consultant.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    Wedging the stair door open for a moment does no harm.

    Why is it wrong?

    Fire and smoke do not wait for the wedge to be removed. A fire door works only when it is closed at the time of a fire, and a wedged door is one of the ways smoke spreads named in UK guidance.

    Common misconception

    A thick wooden door is the same as a fire door.

    Why is it wrong?

    Fire resistance is the test result of the whole door assembly, including the frame, hinges, seals, and closer. An ordinary wooden door gives only limited protection.

    Common misconception

    Spring hinges are enough as the closer of a fire door.

    Why is it wrong?

    The closer of a fire door has to be able to close and latch the door from any angle. Rising butt hinges are not suitable for that, and spring hinges are unlikely to be suitable.

    Common misconception

    A door that scrapes the floor only needs its bottom planed.

    Why is it wrong?

    On an ordinary door, the cause can be a loose top hinge or an out-of-square frame, as Examples 2 and 3 show. On a fire door, planing the leaf can change its test result.

    Common misconception

    The more master key levels, the more convenient.

    Why is it wrong?

    Every master key level decreases the security of all cylinders below it, and a lost master key forces many cylinders to be replaced, as calculated in Example 6.

    Chapter 94 · Electrical & Control on door access control continues this chapter into electric locks, card readers, and exit buttons, while Chapter 17 on fire protection and Chapter 19 on fire alarm panels cover the protection systems that fire doors are part of. Chapter 37 on building paints and coatings covers painting door frames and door leaves without covering the seals, and Chapter 1 on loads and load paths explains the moment that the hinges carry.

    Exercises and worked solutions

    The numbers in the questions are used for practice.

    Try to answer first, then open the worked solution.

    1. How many hinges does a door 2,250 mm high need, and a door 2,300 mm high, under the United States specification rule?

      Check my answer
      See the worked solution

      The 2,250 mm door needs 2+⌈750/750⌉=32 + \lceil 750/750 \rceil = 3 hinges, while the 2,300 mm door needs 2+⌈800/750⌉=42 + \lceil 800/750 \rceil = 4 hinges. The words “or fraction thereof” in the rule mean that even 50 mm extra adds one hinge.

    2. A housekeeping attendant wedges the stair door open so that the trolley can pass easily. What does the technician do, and why?

      Check my answer
      See the worked solution

      The technician removes the wedge, makes sure the door closes and latches by itself, records the location, and reports it to the building management. A wedged stair door lets smoke into the stairway that serves as the escape route, and the trolley problem is solved with an automatic hold-open device linked to the alarm, installed by a contractor.

    3. After the corridor is repainted, the strips around the frame of a fire door have been painted too. Why is this a finding?

      Check my answer
      See the worked solution

      Intumescent strips and smoke seals must be intact and free of paint so that they can expand and close the gap in a fire. The finding is reported, and the painted strips are replaced by a competent fire door contractor.

    4. A fire door closes fully when opened wide and let go, but stops short of latching when opened to about 15 degrees. What is the decision?

      Check my answer
      See the worked solution

      The door fails the check, because a fire door closer must close the door fully from any angle, including a small one. The door is tagged as defective and reported, and adjusting or replacing its closer is handed over to the fire door contractor according to the manufacturer’s manual.

    5. The hotel grand master key in Example 6 is lost. Why does copying a new grand master key not solve the problem?

      Check my answer
      See the worked solution

      The lost grand master key can still open all the old cylinders, so a new key changes nothing. All 240 cylinders have to be replaced or rearranged by the appointed locksmith, and the key handover book is reviewed so that the next loss is noticed quickly.

    6. A door leaf has a mass of 45 kg, a width of 1.0 m, and a distance of 1.9 m from the top hinge to the bottom hinge. What is the force on the top hinge?

      Check my answer
      See the worked solution

      The weight is W=45×9.81=441.5W = 45 \times 9.81 = 441.5 N, so F=441.5×1.0/(2×1.9)=116.2F = 441.5 \times 1.0/(2 \times 1.9) = 116.2 N. That force pulls the top hinge out of the frame, so the top hinge screws are checked first when the door starts to drop.

    References

    External sources

    • Fire safety risk assessment: sleeping accommodation (accessible)gov.uk
    • Fire Safety (England) Regulations 2022: fire door guidance (accessible)gov.uk
    • UFGS 08 71 00 Door Hardwarewbdg.org
    • Understanding Traditional and Modern Paints and Stains for Exterior Woodnps.gov

    Revision history

    DateVersionChange
    November 13, 20261First published

    How to cite

    Kurnia (2026). Door frames, doors, and locks: frame and door leaf materials, hinges and automatic door closers, mechanical locks and master key systems, fire doors, adjustment and maintenance, and the limits of the work. ARSTEMA Academy. Revised November 13, 2026. arstema.com/en/academy/konsep/kusen-pintu-dan-kunci-bahan-kusen-dan-daun-pintu-engsel-dan-penutup-pintu-otomatis-kunci-mekanis-dan-sistem-kunci-induk-pintu-tahan-api-penyetelan-dan-perawatan-serta-batas-pekerjaan

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated
    1

    How many hinges does a door 2,250 mm high need, and a door 2,300 mm high, under the United States specification rule?

    2

    A housekeeping attendant wedges the stair door open so that the trolley can pass easily. What does the technician do, and why?

    3

    After the corridor is repainted, the strips around the frame of a fire door have been painted too. Why is this a finding?

    Self-assessment progress0%

    Nearby chapters