    Buildings & Facilities · Chapter 50Applied

    By Kurnia · Published November 15, 2026 · Version 1 · 21 min read

    Building glass and windows

    annealed, tempered, and laminated glass, cracks and spontaneous breakage, safety film, seals and frames, opening windows, and work limits

    At two in the morning, the glass shower door in a hotel room shatters by itself into small granules, and the next morning housekeeping finds that a room window on the same floor can be pushed wide open because its opening restrictor is missing. This chapter covers glass and windows from the building technician’s side: the difference between annealed, tempered, and laminated glass and how each breaks, glass in impact zones, impact cracks, thermal cracks, and spontaneous breakage of tempered glass, safety film and its limits, seals, setting blocks, and frames, opening windows together with opening restrictors and cleaning from inside, and the division of work with the glazing contractor. Approved Document K for England, HSE guidance, a United States government glazing specification, and the report of the UK construction products regulator are written as data from those countries. This chapter gives no steps for replacing large glass or facade glass; that work belongs to a glazing contractor with suitable equipment and access.

    Section you’re reading: Chapter opening

    At two in the morning, a guest on the ninth floor of a hotel calls the front desk: the glass shower door broke with a loud bang without being touched, and the floor is covered with small glass granules with blunt edges. The duty technician moves the guest and locks the room. The next morning housekeeping reports two things from the same floor: the window of a family room can be pushed wide open because its opening restrictor was not refitted after a hinge repair, and the double glazing in a corner room is fogged between its two panes. The technician has to decide what they can resolve themselves, which rooms must not be sold, and which work goes to the glazing contractor.

    Scope

    This chapter covers glass and windows in hotels, hospitals, and public buildings from the building technician’s side: types of glass and how they break, glass that people may strike, cracks and spontaneous breakage, safety film, seals and frames, opening windows, and work limits. This chapter is learning material, not a work instruction for installing or replacing glass. Approved Document K for England, HSE guidance, a United States government glazing specification, and the report of the UK construction products regulator are written as data from those countries. The requirements for safety glass and windows in Indonesian building regulations are not cited; as of November 2026 their content could not be confirmed, so the requirements for a particular building are read from its approved design documents.

    Doors and fire doors with their glass are in Chapter 38 on frames, doors, and locks, frame painting in Chapter 37 on building paints and coatings, and fragile glass roofs in Chapter 35 on roofs and waterproofing. Cleaning glass from outside the building is in Chapter 47 on gondolas and facade access, work at height in Chapter 10 · Safety, lifting loads in Chapter 9 · Safety, and personal protective equipment in Chapter 5 · Safety.

    Removing, installing, cutting, or replacing large glass, facade glass, roof glass, and overhead glass, applying film to glass in impact zones, renewing external seals at height, and repairing frames or hinges of upper-floor windows are work for a competent glazing contractor or window contractor with suitable lifting equipment and access. The building technician inspects, records, sets up barriers, locks windows whose restrictors are damaged, cleans glass from inside within safe reach, maintains drainage holes and internal seals that can be reached from the floor, and reports.

    Annealed, tempered, and laminated glass

    Annealed glass is sheet glass that is cooled slowly during manufacture so that it holds almost no stress; it can be cut on site, but it breaks into large, sharp, pointed pieces. Tempered glass (toughened glass) is glass that is heated and then cooled rapidly so that its surfaces are in compression and the middle of its thickness is in tension; it is stronger, it is made to the size of its opening because it cannot be cut afterward, and when it breaks the whole pane disintegrates into small granules. Laminated glass is two or more layers of glass bonded with a plastic interlayer; its fragments stay attached to the interlayer.

    UK workplace regulations describe laminated and tempered glass that meets the safety glass standard as glass that breaks without large, sharp pieces. Approved Document K judges safe breakage from an impact test: the glass breaks with only a small opening and small detached particles, disintegrates into small particles, or breaks into separate pieces that are not sharp or pointed. Laminated glass usually shows the first behavior and tempered glass the second.

    Heat-strengthened glass sits between annealed and tempered glass. The United States government glazing specification recommends it, or tempered glass where safety glazing is required, for tinted heat-absorbing glass at risk of cracking from heat. Tempered glass sold in the UK must carry a permanent mark with the manufacturer’s name or trademark and the standard number. In any building, the mark in the corner of the glass is the first clue to its type. Glass without a legible mark is recorded as “type unknown,” because tempered and laminated glass can look exactly like annealed glass until they break.

    Glass in impact zones

    Approved Document K requires glass that people moving in or about the building are likely to contact to break in a way unlikely to cause injury, to resist impact without breaking, or to be protected from impact. The greatest risk lies in glass in doors and side panels between the floor and shoulder height near handles, and in low glass in walls, where children are most vulnerable; an impact between waist and shoulder can be followed by a fall through the glass.

    A critical location is the part of the glazing that the rules require to be safe against impact. Approved Document K sets two zones: in door leaves and side panels within 300 mm of the door edge, glass between the floor and 1,500 mm; in walls and windows, glass between the floor and 800 mm. In a critical location there are three options: glass that breaks safely according to an impact test class, glass that is strong enough, or a permanent screen that prevents a 75 mm sphere from touching the glass. Annealed glass is considered strong enough if its thickness suits the size of a pane supported on all four edges: 8 mm up to 1.10 m by 1.10 m, 10 mm up to 2.25 m by 2.25 m, 12 mm up to 4.50 m by 3.0 m, and 15 mm for any size.

    UK workplace regulations agree: particular attention to glass in doors and side panels at shoulder height or below, and to glass in windows and walls at waist height or below, except narrow panes up to 250 mm wide. Instead of safety materials, glass can be protected by a screen or barrier that keeps people from touching it, and that barrier is made hard to climb when the glass is at height.

    The building’s glass register separates glass in critical locations, records its type from the mark, and flags glass of unknown type for assessment by the contractor. A broken pane in a critical location is not replaced with whatever annealed glass is at hand, even when it is small. Large areas of clear glass are also given manifestation between 850 and 1,000 mm and between 1,400 and 1,600 mm.

    Cracks and spontaneous breakage

    An impact crack starts from the point struck by an object. A thermal crack starts at the edge, because the middle of the pane heated by the sun expands while the edge hidden in the frame stays cool and is pulled into tension. An edge crack starts from an edge chipped during installation or an edge pressing against the frame or a bolt. The origin of the crack is recorded and photographed before the glass is touched.

    The size of the thermal stress is estimated with a simple model:

    σ=E α ΔT\sigma = E \, \alpha \, \Delta T

    where σ\sigma is the tensile stress at the edge (Pa), EE is the Young’s modulus of the glass (Pa), α\alpha is the coefficient of linear expansion (1/°C), and ΔT\Delta T is the temperature difference between the middle of the glass and its edge (°C). For ordinary glass, EE is about 70 GPa and α\alpha about 9×10−69 \times 10^{-6} per °C. The model assumes the edge is fully restrained, so it only shows the magnitude; what matters is that the stress rises in proportion to the temperature difference.

    The United States government glazing specification lists conditions that raise the risk of thermal breakage: building orientation, unusual glass shapes, large panes, indoor shading devices, heating outlets, and shadows from trees, structures, or exterior shading that cover part of the glass. The National Park Service guidance on wooden windows also asks for the glass to be removed or protected from sudden temperature change when frame paint is stripped with heat.

    Spontaneous breakage is the breaking of tempered glass without any visible impact or load, as in the opening case. One known cause is a nickel sulfide inclusion, a very small particle inside the glass that can change and slowly expand after the glass is installed; because the middle of tempered glass is in tension, a crack from that particle runs through the whole pane. Heat soaking heats tempered glass at the factory so that more of the glass containing inclusions breaks before it is shipped. The UK construction products regulator recorded reports that glass marketed as heat soaked tempered glass compliant with BS EN 14179-2 suffered far more nickel sulfide-related breakages than expected, and that no post-production test can determine whether glass has been heat soaked, so production records are the only evidence.

    Other causes that look similar are edges damaged during installation and glass in direct contact with the frame; the United States glazing specification calls for rubber or silicone setting blocks and forbids forcing or twisting insulating glass units during setting. The technician records the circumstances and hands the investigation to the contractor and the glass supplier.

    Safety film

    Safety film is a thin adhesive plastic sheet applied to glass to hold the fragments so that they do not scatter. For health and social care premises, HSE states that where assessment identifies a risk of people falling against or through glazing, the options include suitable safety film, replacement with safety glass, or barriers; glass doors and patio windows use tempered or safety glass or are covered with protective safety film.

    Annealed glass with film does not automatically meet the safe breakage class for a critical location; that class is set by testing, so film for a critical location is chosen with a supplier who can show test results for that combination of glass and film. Dark or heat-reflective film raises the temperature of the glass, much like tinted heat-absorbing glass at risk of thermal cracking, so such film on large sunlit glass is assessed first with the glass supplier.

    The technician inspects for peeling edges, bubbles, and deep scratches; film peeling on glass in an impact zone is reported as lost protection. Film installation is left to the film contractor, and film is no reason to delay replacing glass that is already cracked.

    Seals, setting blocks, and frames

    Glass sits in a frame of aluminum, wood, or plastic, held by a glazing bead or putty, and separated from the frame by setting blocks. The gap between glass and frame is closed by a glazing gasket or a sealant that cures in place. The United States glazing specification calls for continuous gaskets that stay watertight as the building moves and materials expand, and for frames receiving laminated glass to be weeped to the outside. Blocked drainage holes are easy to clean from inside.

    An insulating glass unit is two panes of glass separated by an air or gas space sealed tightly along its edges. Fog or a film on its inner surfaces means the hermetic seal has failed; the same specification places this defect under warranty and calls for the unit to be replaced with a new one. That fog cannot be cleaned off and is not fixed by adding silicone from outside.

    The National Park Service guidance names moisture as the main cause of decay in wooden windows. The inspection looks for water entering around the frame, joints that need sealing, glazing putty that is cracked, loose, or missing, and back putty that keeps condensation from running into the joints. The sill is checked to slope outward, and paint that blisters or peels shows where water gets in. Worn weatherstripping on the sash gaps adds air leakage and is replaced as part of the repair.

    Internal seals on small windows that can be reached from the floor can be renewed by the technician with materials approved by the window supplier; external seals on upper floors, structural sealant on facade glass, and glass that has shifted off its setting blocks are work for the contractor.

    Opening windows

    Opening windows include side-hung casements, top-hung windows, sliding windows, and pivot windows that turn on a central axis. Approved Document K requires window controls to be no higher than 1,900 mm above the floor when unobstructed, or 1,700 mm when obstructed by furniture no more than 900 mm high, with a horizontal reach of no more than 600 mm. Leaves that project more than 100 mm into a route for people below a height of 2 m are marked with a barrier or a change in floor surface.

    To prevent falls, Approved Document K requires opening limiters or guarding on windows above ground floor level that a person could fall through, with a guarding height of 800 mm at opening windows. UK workplace regulations require devices that prevent a window from opening too far where there is a danger of falling, and the bottom edge of opening windows is normally at least 800 mm above the floor unless there is a barrier.

    A window restrictor is a device that limits how far a window leaf can open. The HSE information sheet for health and social care asks for restrictors that limit the opening to 100 mm or less, are strong enough to withstand the force of a person determined to open them, and are secured with tamper-proof fittings that cannot be removed with everyday objects such as cutlery, only with a special tool or key; restricted hinges that can be overridden without tools are not suitable. The sheet also asks for the frames to which restrictors are fitted to be strong enough, for maintenance that ensures safety fittings have not deteriorated through wear or tampering, and for staff trained to report defects. An HSE safety alert from 2012 describes a fatal incident in which window side-stays fitted with plastic spacers failed.

    That guidance was written for care services, but hotel rooms are also occupied by children. The gap of a casement window is calculated from the leaf width and the opening angle:

    g=2wsin⁡(θ2)g = 2 w \sin\left(\frac{\theta}{2}\right)

    where gg is the gap at the edge of the leaf farthest from the hinge (m), ww is the leaf width (m), and θ\theta is the opening angle (degrees). On a sliding window, the gap equals the sliding distance.

    Approved Document K illustrates safe reaches for cleaning the outside of glass from inside, for example a side reach through the opening within an 850 mm radius, and requires windows that reverse for cleaning to have a mechanism holding them in the reversed position. HSE asks for work at height to be avoided where reasonably practicable, for example with telescopic water-fed poles or by cleaning from inside. Staff do not lean out or stand on the sill. A restrictor released with a special key for cleaning is re-engaged before the room is used, and who holds the key is set in the housekeeping procedure.

    Broken glass and the division of work

    Broken glass is handled in the same order every time: keep people away, set up a barrier, record, and hand over. Tempered granules held in the frame can fall without warning, and cracked laminated glass can sag out of the frame, so the area below and in front of it is cleared. For upper-floor glass, the area on the ground below is also cleared; HSE asks for members of the public to be kept out of the area directly below work at height so that they are not struck by falling objects. Granules on the floor are swept up wearing cut-resistant gloves and eye protection.

    The mass of a glass pane is calculated with

    m=ρ A tm = \rho \, A \, t

    where mm is the mass (kg), ρ\rho is the density of glass, about 2,600 kg/m³, AA is the pane area (m²), and tt is the glass thickness (m). Glass door or wall panes weigh tens to hundreds of kilograms, are fragile, and have sharp edges, so removing and installing them requires glass lifting equipment, several trained people, and a lifting plan, while facade glass and upper-floor windows also require external access. The technician’s record contains the date, location, size, glass type and mark, critical location or not, suspected cause, photos, and temporary action, so that patterns such as several tempered panes from the same delivery breaking spontaneously can be seen.

    Worked example

    The numbers in the examples below are practice numbers unless their origin is stated.

    Example 1: checking critical locations. A hotel restaurant door is flanked by fixed glass panels. Panel A is right beside the door edge, with glass from 100 to 2,100 mm above the floor; the part 1,500−100=1,4001{,}500 - 100 = 1{,}400 mm high lies in the door critical zone. Panel B is 1.2 m from the door edge, so the wall rule applies; its glass starts at 900 mm, above the 800 mm limit, so it is not in a critical zone. Window C has a 500 mm sill, so the glass 800−500=300800 - 500 = 300 mm high at its bottom lies in the critical zone.

    Example 2: annealed glass thickness in a shop front. A shop front pane of annealed glass 2.0 m by 2.0 m and 10 mm thick meets the 10 mm limit for panes up to 2.25 m by 2.25 m. The pane next to it is 2.4 m by 2.0 m and also 10 mm thick; its 2.4 m width exceeds 2.25 m, so the pane falls in the 12 mm group (up to 4.50 m by 3.0 m). The second pane is recorded as not meeting the strong glass option, and the contractor assesses its replacement.

    Example 3: thermal stress and curtains. The middle of a sunlit room window is 20 °C hotter than its edge, so σ=70×109×9×10−6×20=12.6×106\sigma = 70 \times 10^{9} \times 9 \times 10^{-6} \times 20 = 12.6 \times 10^{6} Pa, that is, 12.6 MPa. After heavy curtains are hung tight against the glass, the temperature difference rises to 40 °C and σ=70×109×9×10−6×40=25.2×106\sigma = 70 \times 10^{9} \times 9 \times 10^{-6} \times 40 = 25.2 \times 10^{6} Pa, that is, 25.2 MPa, twice the original. Curtains touching the glass and dark film are therefore reported to the glass supplier.

    Example 4: casement gap and restrictor. The leaf of a family room window on the ninth floor is 0.6 m wide. For the gap to be no more than 100 mm, sin⁡(θ/2)=0.1/1.2=0.0833\sin(\theta/2) = 0.1/1.2 = 0.0833, so θ/2=4.78∘\theta/2 = 4.78^\circ and θ=9.56∘\theta = 9.56^\circ. Without a restrictor, the window opens to 25° and g=2×0.6×sin⁡12.5∘=1.2×0.2164=0.260g = 2 \times 0.6 \times \sin 12.5^\circ = 1.2 \times 0.2164 = 0.260 m, that is, 260 mm, more than two and a half times the limit. The window is locked shut, the room is not sold, and the restrictor is refitted by a designated person with parts from the window supplier.

    Example 5: pane mass and work limits. A glass wall pane 1.5 m by 2.4 m and 10 mm thick has an area of 3.6 m², so m=2,600×3.6×0.010=93.6m = 2{,}600 \times 3.6 \times 0.010 = 93.6 kg. If it is replaced with laminated glass of two 6 mm layers, the glass mass is 2,600×3.6×0.012=112.32{,}600 \times 3.6 \times 0.012 = 112.3 kg, not counting the interlayer. A small pane of 0.5 m² and 6 mm thickness is only 2,600×0.5×0.006=7.82{,}600 \times 0.5 \times 0.006 = 7.8 kg. A pane of 90 to 110 kg that is fragile and sharp-edged is work for a glazing contractor with lifting equipment.

    Example 6: internal seal of a room window. The internal seal of a ground-floor room window measuring 1.2 m by 1.5 m is cracked. Its perimeter is 2×(1.2+1.5)=5.42 \times (1.2 + 1.5) = 5.4 m, that is, 540 cm, and an 8 mm by 8 mm joint has a cross section of 0.64 cm², so its volume is 540×0.64=345.6540 \times 0.64 = 345.6 cm³. With 15 percent waste, the requirement is 345.6×1.15=397.4345.6 \times 1.15 = 397.4 mL, that is, two 300 mL cartridges. The technician does this from the floor with materials approved by the window supplier; the external seal of the same window on the ninth floor belongs to the contractor.

    Stop conditions

    1. Glass is cracked or broken in the facade, an upper-floor window, a glass roof, or above a route for people: clear and barrier off the area below and in front of it, including on the ground, do not touch or push the glass, and hand over to the glazing contractor through the duty engineer.
    2. Tempered granules are still held in the frame, or cracked laminated glass is sagging: do not pull, tap, or sweep fragments from the frame; set up a barrier and call the glazing contractor.
    3. A broken pane in a critical location is about to be replaced with annealed glass or glass of unknown type: postpone; the glazing contractor installs glass of the class that matches the design documents.
    4. A window restrictor above ground floor level is missing, damaged, loose, or can be removed without a special tool: lock the window shut, do not sell or occupy the room, and report to the duty engineer; the restrictor is refitted by a designated person with parts from the window supplier.
    5. Window hinges, side-stays, or frames are loose or cracked, or a leaf is tilted so that it could come off: lock it shut if safe, clear the area below, and call the window contractor.
    6. The work calls for removing, installing, cutting, or drilling large glass, facade glass, roof glass, or overhead glass: stop; the work belongs to a glazing contractor with lifting equipment, a lifting plan, and suitable access.
    7. The outside of the glass cannot be cleaned or inspected from inside within safe reach: do not lean out or stand on the sill; the work follows Chapter 10 · Safety on work at height or Chapter 47 on gondolas and facade access.
    8. Safety film on glass in an impact zone is peeling, or there is a request to apply dark film to large sunlit glass: report it; the decision is made together with the film contractor and the glass supplier.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    Glass that breaks by itself must have been hit by someone.

    Why is it wrong?

    Tempered glass can break spontaneously because of a nickel sulfide inclusion or an edge damaged during installation. The circumstances and the origin of the break are recorded, and the investigation is handed to the contractor and the glass supplier.

    Common misconception

    Thick glass is always safe near a door.

    Why is it wrong?

    The thickness of annealed glass only meets the strong glass option if it suits the pane size, and its fragments are still large and sharp. In a critical location, what is needed is a safe breakage class, sufficient strength, or a permanent screen.

    Common misconception

    Safety film turns annealed glass into safety glass.

    Why is it wrong?

    Film holds fragments, but the safe breakage class is set by testing the combination of glass and film. Dark film can also raise thermal stress.

    Common misconception

    Fogged double glazing just needs resealing with silicone from outside.

    Why is it wrong?

    Fog between the two panes means the unit’s hermetic seal has already failed, and the unit is replaced. External silicone does not remove water vapor that is already trapped.

    Common misconception

    Window restrictors only matter in hospitals.

    Why is it wrong?

    The HSE guidance was written for care services, but hotel rooms above ground floor level are also occupied by children and guests unfamiliar with the room, so a missing restrictor means the room is not sold.

    Chapter 38 on frames, doors, and locks covers fire doors and their glass, Chapter 43 on lobby automatic doors covers glass manifestation, and Chapter 36 on cracks in walls and concrete covers sticking windows as a sign of structural cracking. Cleaning glass from outside is in Chapter 47 on gondolas and facade access, while Chapter 10 · Safety and Chapter 9 · Safety cover work at height and lifting loads.

    Exercises and worked solutions

    The numbers in the exercises are for practice.

    Try to answer first, then open the worked solution.

    1. A fixed glass panel is 200 mm from the edge of a meeting room door, and the bottom edge of its glass is 300 mm above the floor. Is the panel in a critical location?

      Check my answer
      See the worked solution

      Yes, because the panel is within 300 mm of the door edge, so glass between the floor and 1,500 mm is in a critical location. The part from 300 to 1,500 mm must break safely, be strong enough, or be protected, so the glass mark is checked.

    2. A tempered glass shower door breaks by itself at night without being touched. What does the technician do, and why is the guest not blamed straight away?

      Check my answer
      See the worked solution

      The technician moves the guest, locks the room, does not pull fragments from the frame, and records the time, location, sun exposure, glass mark, and photos of the origin of the break. Tempered glass can break spontaneously because of a nickel sulfide inclusion or an edge damaged during installation, so the cause is investigated by the contractor and the glass supplier.

    3. A sliding window in a family room on the fourth floor can be opened 180 mm because its stop has come off. What is the technician’s decision?

      Check my answer
      See the worked solution

      An opening of 180 mm exceeds the 100 mm limit in the HSE guidance, and the room is above ground floor level. The window is locked shut, the room is not sold, and the stop is refitted by a designated person with parts from the window supplier before the room is used.

    4. The temperature difference between the middle and the edge of a pane is 30 °C. What is the thermal stress according to this chapter’s model, and how many times the stress at a 20 °C difference is it?

      Check my answer
      See the worked solution

      The stress is 70×109×9×10−6×30=18.9×10670 \times 10^{9} \times 9 \times 10^{-6} \times 30 = 18.9 \times 10^{6} Pa, that is, 18.9 MPa. At 20 °C the stress is 12.6 MPa, so a 30 °C difference gives 18.9/12.6=1.518.9/12.6 = 1.5 times, consistent with a model proportional to the temperature difference.

    5. The double glazing in a corner room is fogged between its two panes. What does it mean, and can the technician fix it?

      Check my answer
      See the worked solution

      Fog on the inner surfaces means the hermetic seal at the edge of the unit has failed and water vapor has entered the space between the two panes. The technician cannot clean or patch the unit; the technician records it and asks the contractor to replace the unit, possibly under the supplier’s warranty.

    6. A shop front pane of annealed glass 1.2 m by 2.0 m and 8 mm thick is cracked. What is its mass, does its thickness meet the strong glass option, and who replaces it?

      Check my answer
      See the worked solution

      The mass is 2,600×2.4×0.008=49.92{,}600 \times 2.4 \times 0.008 = 49.9 kg. A thickness of 8 mm is only enough for panes up to 1.10 m by 1.10 m, and this pane is larger, so its replacement is safety glass or thicker annealed glass according to the contractor’s assessment; the replacement is done by the glazing contractor, while the technician sets up a barrier.

    References

    External sources

    • Approved Document K: Protection from falling, collision and impact, 2013 editionassets.publishing.service.gov.uk
    • Workplace health, safety and welfare. Workplace (Health, Safety and Welfare) Regulations 1992. Approved Code of Practice and guidance, L24 (Second edition)hse.gov.uk
    • Falls from windows or balconies in health and social care, HSE information sheet, Health Services Information Sheet No 5hse.gov.uk
    • Avoiding falls from windows or balconies in health and social care premiseshse.gov.uk
    • Risks to vulnerable members of the public from falling from height from windowshse.gov.uk
    • Working at height whilst window cleaninghse.gov.uk
    • UFGS-08 81 00 Glazingwbdg.org
    • Heat Soaked Thermally Toughened Glass: Sector Regulatory Reportgov.uk
    • Preservation Briefs 9: The Repair of Historic Wooden Windowsnps.gov
    • College Physics 2eopenstax.org

    Revision history

    DateVersionChange
    November 15, 20261First published

    How to cite

    Kurnia (2026). Building glass and windows: annealed, tempered, and laminated glass, cracks and spontaneous breakage, safety film, seals and frames, opening windows, and work limits. ARSTEMA Academy. Revised November 15, 2026. arstema.com/en/academy/konsep/kaca-dan-jendela-gedung-kaca-biasa-tempered-dan-laminasi-retak-dan-pecah-spontan-film-pengaman-perapat-dan-bingkai-jendela-yang-dapat-dibuka-serta-batas-pekerjaan

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated
    1

    A fixed glass panel is 200 mm from the edge of a meeting room door, and the bottom edge of its glass is 300 mm above the floor. Is the panel in a critical location?

    2

    A tempered glass shower door breaks by itself at night without being touched. What does the technician do, and why is the guest not blamed straight away?

    3

    A sliding window in a family room on the fourth floor can be opened 180 mm because its stop has come off. What is the technician’s decision?

    Self-assessment progress0%