By Kurnia · Published November 14, 2026 · Version 1 · 22 min read
Natural gas piping in buildings
the connection from the network, meter and regulator, emergency control valve, pipe routes and ventilation, leak detection, and the limits of the work
Shortly before midnight, a hotel cook smells gas in the service corridor, right under the ceiling where the natural gas pipe runs to the kitchen, and the on-duty technician has to decide within minutes what may and may not be touched. This chapter covers a building’s natural gas installation from the building technician’s side: the properties of natural gas, which is lighter than air and odorized, the gas route from the distribution company’s pipeline to the appliance, the meter and regulator with over-pressure protection and the meter housing, the emergency control valve and its notice, pipe routes through walls, voids, and ventilated sleeves, pipe marking and the line diagram, the kitchen ventilation interlock, leak detection from smell, detectors, and meter readings, the response to a smell of gas, and the division of work. The basis is the guidance of the UK HSE (the L56 code of practice and the catering information sheet), the Minister of Energy and Mineral Resources Regulation on the natural gas business, and official releases of the Ministry of Energy and Mineral Resources on gas networks. Opening, cutting, connecting, and pressure testing gas pipes, and opening or adjusting meters and regulators, are stated as work for gas distribution company staff or licensed installers.
This material involves real hazards. A concept explanation doesn’t replace site procedures, competency, energy isolation, the latest SDS, or a work permit.
Shortly before midnight, a cook pushing a trolley to the hotel kitchen smells gas in the service corridor. The smell is strongest near the ceiling, where the natural gas pipe runs from the meter room outside the building to the main kitchen. The on-duty technician arrives and, out of habit, is already reaching for the switch of the corridor light, which is off. The technician stops just in time. Natural gas is lighter than air, and above the suspended ceiling there is an enclosed space where gas can collect unseen. In the next few minutes the technician has to know where the emergency control valve is, whom to call, who has to leave, and which parts of the system must not be touched at all.
Scope
This chapter covers natural gas installations supplied by pipe to buildings such as hotels, hospitals, laundries, and central kitchens, from the building technician’s side: inspecting, reading, recording, responding to a smell of gas, and reporting.
LPG in cylinders is covered in Chapter 5 · Commercial Kitchens and is not repeated. The gas path inside cooking appliances, appliance supply pressure, and appliance leak testing are in Chapter 1 · Commercial Kitchens on commercial gas cooking equipment, the gas valve of the hood suppression system in Chapter 4 · Commercial Kitchens, fire protection in Chapter 17 · Buildings & Facilities, and non-electrical energy isolation in Chapter 4 · Safety. Flammable limits and gas concentrations are in Chapter 11 · Chemistry on hazardous gases, and confined spaces in Chapter 11 · Safety.
Most of the detailed provisions in this chapter come from UK rules, namely the Gas Safety (Installation and Use) Regulations 1998 and their code of practice, and are written as UK data. The Indonesian regulations that were opened only define natural gas and the distribution pipeline; Indonesian technical rules on customer gas installations were not found in the documents opened. What binds a particular building, therefore, is the agreement with the gas distribution company and the installation drawings from the installer.
This chapter is not a work instruction for gas pipes. Opening, cutting, connecting, relocating, extending, purging, and pressure testing gas pipes, and opening, removing, or adjusting meters and regulators, may only be done by gas distribution company staff or licensed installers. The building technician does not do this work, including in an emergency.
Natural gas: light, odorless at the source, and flammable
Natural gas is a hydrocarbon that is a gas at atmospheric pressure and temperature and is obtained from oil and gas extraction. Its main component is methane. The Ministry of Energy and Mineral Resources explains that natural gas from underground has no smell, while the gas piped to homes smells when it leaks. The smell comes from an odorant added to the gas.
The property that sets natural gas apart from LPG is its density. Methane has a molar mass of 16.04 g/mol, much lighter than air (28.96 g/mol according to Chapter 11 · Chemistry), so leaking gas rises and collects in the upper part of a room, above ceilings, in shafts, and in enclosed voids. A 2015 release of the Ministry of Energy and Mineral Resources states that household natural gas flows at a pressure of about 0.02 bar and is released straight into the air when it leaks, unlike LPG, which settles. The statement “released straight into the air” holds only in open spaces. The HSE code of practice warns that a leak inside a wall or floor cavity is difficult to detect and readily forms an explosive mixture of gas and air.
The flammable range of methane is about 5 to 15 percent by volume in air, as recorded in Chapter 11 · Chemistry on hazardous gases. Flammable gas detectors show the concentration as a percentage of the lower flammable limit (% LEL). Because natural gas rises, detector sensors for natural gas are placed high according to the installer’s design, the opposite of LPG detectors, which are placed near the floor.
From the distribution network to the appliance
The Minister of Energy and Mineral Resources Regulation on the natural gas business defines a distribution pipeline as a pipe that carries natural gas from a transmission pipeline or another distribution pipeline to natural gas consumers. The pipeline is owned and operated by the business entity that holds the license for its distribution network area. From the distribution pipeline in the street, the service connection brings gas to the building, usually to a meter room or meter cabinet at the property boundary, and the installation pipework then carries gas inside the building to each appliance.
The UK rules give one example of a clear boundary. The HSE code of practice states that the outlet of the first emergency control downstream of the distribution main marks the boundary between the service pipe and the installation pipework. In Indonesia, the location of the delivery point, the ownership of the meter and regulator, and who maintains each section are set in the agreement with the gas distribution company. The building technician needs a copy of that boundary, because on the distribution company’s side the building technician has no authority, and even on the building side the work on the pipes belongs to the licensed installer.
For multi-story buildings with a large incoming pipe, the UK rules require a valve in a conspicuous and readily accessible position, and a permanent line diagram near the meter showing all installation pipework of 25 mm internal diameter or more, meters, emergency controls, other valves, and pressure test points. The provision applies when the service pipe has an internal diameter of 50 mm or more and branches to several floors, so that emergency services can find and isolate the affected part of the system. A hotel in Indonesia that has no such diagram can request one from the installer as part of the handover documents.
Meter, regulator, and meter housing
Pressure regulator is a device that reduces the gas pressure from the network to a pressure suitable for the installation pipework and appliances, and keeps it steady. The UK rules require every primary meter to have a regulator that prevents the pipework downstream from receiving a higher pressure than it was designed for. Where the normal pressure at the regulator inlet is 75 mbar or more, additional automatic protection is required in case the regulator fails, for example an over-pressure shut-off device or a pressure relief valve. The vent pipe of a relief valve should discharge to open air, away from ignition sources, not into the building. Regulators are also sealed against interference by unauthorized persons.
Gas meter records the volume of gas passing through, usually in cubic meters, as a cumulative figure. For the building technician, the meter is a measuring instrument to be read: the figure on the index is recorded, and the difference between two readings gives the consumption. Opening, removing, or relocating the meter is work for the distribution company.
Meter housings are also regulated in the UK rules. Where a meter is in a box or compartment attached to an outside wall, gas leaking inside it must escape to the outside air and not enter the building or the wall cavity. Cables or pipes passing from the meter box into the building are sleeved and sealed, and the meter box must not be used to store combustible materials, for example cardboard or waste paper. The second prohibition applies to everyone, not only to gas engineers. In buildings with two or more floors above the ground floor, a new meter should not be installed on or under a stairway that is the only escape route in a fire.
The emergency control valve and its notice
Emergency control valve (emergency control) is a valve for shutting off the gas supply in an emergency that is intended for use by the gas consumer. According to HSE guidance, this valve is installed as close as practicable to the point where the pipe enters the building, is readily accessible to all users, and is not in a basement. A valve in a meter room that is always locked and can only be opened by the building owner, the supplier, or the emergency services is not regarded as an emergency control. If the valve is placed in a locked compartment, the occupiers of the building are given keys.
Gas users should know where the emergency control valve serving their part is and what to do in an emergency. In a hotel, this means the valve location is in the emergency procedure, technicians on every shift have seen it, and the way to the valve is not blocked by stored items. The emergency control valve is distinct from the valve in front of a cooking appliance (Chapter 1 · Commercial Kitchens) and the automatic valve of the hood suppression system (Chapter 4 · Commercial Kitchens).
Under the UK rules, a notice is fixed near an emergency control that is not next to the meter, bearing the words “Gas emergency control”, and it gives the steps for a gas escape: shut off the gas supply, immediately call the gas emergency service if gas continues to escape, do not reopen the supply until a competent person has repaired it, the emergency telephone number, and the date the notice was fixed. A similar notice is fixed near the meter. For buildings in Indonesia, the content of that notice can serve as a model: the emergency number written on it is that of the building’s gas distribution company.
Pipe routes, sleeves, ventilation, and marking
The route of the gas pipe inside the building is most often disturbed by other work, for example ceiling renovation, partitions, or new cables. The UK rules give several provisions that help the building technician recognize conditions that are not as they should be.
- A pipe passing through a solid wall or floor takes the shortest route, and gas that may leak inside it is prevented from entering the wall or floor cavity.
- Installation pipework is not installed inside the cavity of a cavity wall, except to pass straight through from one side to the other.
- A pipe that is not in a ventilated duct must not be installed in a shaft, duct, or void that is not adequately ventilated.
- A pipe must not be installed in a way that weakens the structure or the fire resistance of any part of the building.
Ventilated sleeve is a gastight protective pipe around a gas pipe that passes through a wall or floor, with one end connected to a safe place, preferably open air. HSE guidance states that the gap between the pipe and the sleeve is sealed with a fire-retardant flexible sealant at one end only, so that a leak cannot accumulate in the gap. A sleeve that is sealed at both ends or missing altogether is a finding to be reported.
Under the UK rules, in non-domestic buildings visible gas pipes must be permanently marked so that they are recognized as gas pipes, and the person responsible for the building keeps the marking legible as long as the pipe is in use. The UK rules also recognize main equipotential bonding, the connection between the grounding point of the electrical installation and the gas installation pipe, which is carried out by a competent person. A loose or corroded bonding clamp is reported to the person responsible for electrical systems; grounding and equipotential bonding are covered in Chapter 29 · Electrical & Control.
Changes to the building can also compromise gas safety without touching the pipe. The UK rules prohibit alterations to a building that affect the safety of gas appliances already installed, for example blocking permanent ventilation openings, replacing fixed ventilation with closable louvers, or fitting an extract fan that pulls flue gases back into the room. Renovation plans around the kitchen, boiler room, or gas pipe route are therefore reviewed with the installer before they start.
Kitchen ventilation, interlocks, and alarms
In commercial kitchens, the gas supply is often linked to the mechanical ventilation system through an interlock. The HSE catering guidance states that the interlock is fitted so that ventilation failure shuts off the gas supply to the appliances, and installing a manual bypass on the interlock system is not permitted. Hoods, makeup air, and kitchen ventilation are covered in Chapter 16 · Buildings & Facilities.
The same guidance states that a carbon monoxide alarm system in the kitchen should give an audible alarm and be interlocked with the gas pipework through a fail-safe automatic shut-off, and restoring the supply requires manual intervention. For the building technician, an interlock that has been bypassed, tied, or disabled is a finding to be reported, not fixed by the technician.
Leak detection
A natural gas leak is recognized from three signs that the building technician can read without opening anything. The first sign is the smell of the odorant. The second sign is a gas detector, fixed or portable, that reads the percentage of the lower flammable limit. The third sign is the meter: if all gas appliances are off and the appliance valves are closed, a meter index that keeps moving means gas is flowing somewhere downstream of the meter.
The leak rate from two meter readings is calculated with:
where is the flow rate (m³/h), and the initial and final meter readings (m³), and the time interval (h). This check is meaningful only if not a single appliance is lit, including pilots, water heaters, and appliances in other rooms served by the same meter.
The HSE code of practice states that a person searching for a gas leak must not use any source of ignition, and that the source of a leak is located by smell, gas detection instruments approved for flammable atmospheres, leak detection fluids, pressure test equipment, or a combination of these. On building pipework, searching for the leak point with detection fluid, instruments, or a pressure test is work for distribution company staff or the installer. Soap solution testing on cooking appliance joints that is part of kitchen duties is covered in Chapter 1 · Commercial Kitchens. Any work that may affect the gastightness of the pipework is followed by a gastightness test by whoever did the work, not by the building technician.
Responding to a smell of gas from the building technician’s side
The steps for responding to a smell of gas from the various official guidance documents meet on a few principles. The Ministry of Energy and Mineral Resources asks gas network users to open the door wide so the gas escapes, keep all sources of fire away, not smoke, and find the valve to shut off the gas source. The HSE asks employers to turn off the supply and immediately call the gas emergency service, evacuate the building if in doubt, and not turn the supply back on until the leak has been dealt with by a competent person.
The HSE code of practice adds that doors and windows are opened, all sources of ignition including the use of electrical equipment are avoided, and the emergency control is closed except where that would be dangerous, for example where it would require entering an enclosed space that smells of gas; in that situation the building is evacuated. For the building technician, these principles are arranged into the following sequence:
- Do not switch on or off any switch, plug, light, fan, or electrical appliance in the area that smells of gas, and do not make a flame.
- Open doors and windows to the outside air if this can be done without going further into the area that smells of gas.
- Get people out of the area and keep others from entering.
- Close the emergency control valve if it is outside the area that smells of gas or can be reached without danger; do not enter an enclosed space, shaft, or meter room that smells of gas to reach it.
- From outside the area that smells of gas, call the gas distribution company’s emergency number shown on the notice near the meter, and the fire service if the smell is strong or spreading.
- Do not reopen the supply after the smell has gone; the supply is reopened by distribution company staff or the installer after the cause has been repaired.
Isolating the building’s electricity, if needed, is done from a panel well outside the area that smells of gas, by a designated person under the emergency procedure, on the same principle as for LPG in Chapter 5 · Commercial Kitchens.
Division of work
In the UK, work on gas fittings in shops, restaurants, schools, and hospitals must be carried out by a Gas Safe registered engineer qualified for that work, and it is illegal for anyone else to do it. The HSE catering guidance adds that annual inspections are a reasonable minimum frequency for appliances, flues, pipework, and safety devices, with repairs as necessary. That figure is UK data and is used for comparison.
In buildings in Indonesia, the division is written in the agreement with the distribution company and the installer’s documents. This chapter uses the following division. The gas distribution company is responsible for the distribution pipeline, the service connection, and the meter and regulator it owns, and responds to emergency calls. The licensed installer installs, alters, extends, relocates, pressure tests, and purges the installation pipework, and installs appliances. The building technician reads the meter and records consumption, visually inspects pipe routes, sleeves, markings, ventilation, and meter housings, keeps access to the emergency control valve clear, makes sure the notice is in place, responds to a smell of gas in the sequence above, and reports.
Worked example
The figures in the examples below are practice figures unless their origin is stated.
Example 1: natural gas rises, LPG sinks. The ratio of the molar mass of methane to that of air is , while for propane it is . Leaking natural gas rises to ceilings and shafts, so checks by smell and detector are directed at the upper part of the room. For LPG, the figure explains the ventilation near the floor (Chapter 5 · Commercial Kitchens).
Example 2: the space above the corridor ceiling. The space above the service corridor ceiling measures 12 m by 2 m with a height of 0.6 m and has a volume of m³. At the lower limit of methane, 5 percent, the space reaches a flammable concentration with m³ of gas. A leak of 0.1 m³/h without ventilation reaches that amount in hours if the gas is evenly mixed. Because the gas rises and forms a layer, the concentration at the top reaches the lower limit sooner.
Example 3: a meter that keeps turning. After the kitchen closes, all appliances and appliance valves are turned off at 23:00, and the meter reads 4,817.325 m³. At 05:00 the meter reads 4,817.925 m³. The difference is 0.600 m³ in 6 hours, so m³/h, which is m³ a day. With a heating value for pure methane of about 37.1 MJ/m³ (Example 5), the lost gas is equivalent to MJ, about 24.7 kWh a day. This finding is reported to the distribution company; finding the leak point is not the building technician’s task.
Example 4: reading a detector. A portable detector in the corridor shows 20 percent LEL. With the lower limit of methane at 5 percent by volume, the concentration is percent by volume, which is 10,000 ppm. If the hotel procedure sets evacuation at 10 percent LEL, the threshold is percent by volume, and the reading of 20 percent LEL is already twice that threshold.
Example 5: kitchen gas demand. The heat of combustion of methane, 890.3 kJ/mol from Chapter 12 · Chemistry, and the molar volume of 0.0240 m³/mol at 20 °C from Chapter 15 · Physics give kJ/m³, about 37.1 MJ/m³. A wok burner with a heat input of 30 kW needs m³/h. Eight wok burners and two 20 kW boiling burners lit at the same time need m³/h, more than the capacity of 25 m³/h on the meter plate. Adding appliances is therefore evaluated by the installer and the distribution company before installation.
Example 6: reading pressure. A household network pressure of about 0.02 bar according to the Ministry of Energy and Mineral Resources release equals mbar, which is Pa or a water column of m. The figure of 20 mbar is below the 75 mbar threshold at which the UK rules require additional protection in case the regulator fails. A building supplied at 1 bar, or 1,000 mbar, is above that threshold; the over-pressure protection at its regulator station is inspected by the distribution company, not adjusted by the building technician.
Stop conditions
- There is a smell of gas or a gas detector alarms: do not switch electrical switches or appliances on or off and do not make a flame; open doors and windows if it is safe, get people out, close the emergency control valve only if it can be reached without danger, then from outside the area call the gas distribution company and the fire service.
- The smell of gas comes from an enclosed space, shaft, meter room, basement, or ceiling void that would have to be entered: do not enter; clear the surrounding area and wait for distribution company staff or the fire service (Chapter 11 · Safety on confined spaces).
- The meter keeps moving although all appliances and appliance valves are closed: do not search for the leak point by opening joints or with a flame; record the readings and report to the distribution company.
- A gas pipe is dented, badly corroded, scraped by a tool, without a sleeve where it passes through a wall, in a void without ventilation, or covered by a new ceiling without access: stop the renovation work near it and hand it over to a licensed installer and the distribution company.
- A hiss is heard from the regulator or the relief valve vent pipe, or the flames of all appliances suddenly become too large or too small: do not touch or adjust the regulator; clear the area if gas can be smelled and call the distribution company.
- The ventilation and gas interlock or the automatic shut-off of the carbon monoxide alarm has been bypassed, tied, or disabled: do not use the gas appliances until the installer or ventilation contractor restores it.
- There is a request to cut, connect, relocate, or extend a gas pipe, open the meter, or add a gas appliance: refuse and hand it over to a licensed installer and the distribution company.
Common misinterpretations
Guess what’s wrong first, then open the explanation.
Common misconception
Natural gas is lighter than air, so a leak will always clear by itself.
Why is it wrong?
In an open space natural gas rises and dilutes, but above ceilings, in shafts, and in wall cavities it collects and can reach the lower flammable limit without being smelled below.
Common misconception
If there is a smell of gas, just switch off the electrical panel in that room.
Why is it wrong?
Operating a switch or breaker in an area that smells of gas can create a spark. Isolation, if needed, is done from a panel well outside the area that smells of gas by a designated person.
Common misconception
The smell has gone, so the emergency control valve can be opened again.
Why is it wrong?
The supply is not reopened until the cause of the leak has been repaired by a competent person. A smell that goes away after the valve is closed actually indicates that the leak is downstream of the valve.
Common misconception
A natural gas detector is installed near the floor like an LPG detector.
Why is it wrong?
Natural gas is lighter than air, so its sensor is placed high according to the installer’s design; a detector near the floor reads too late.
Common misconception
The meter and regulator are on hotel property, so the hotel technician may adjust them.
Why is it wrong?
The meter and regulator are sealed and usually belong to the distribution company. The building technician reads the meter figures and does not open or adjust either of them.
Links to other chapters
Chapter 5 · Commercial Kitchens on LPG in hotel kitchens and stores covers a gas that is heavier than air, whose behavior is the opposite of the natural gas in this chapter. Chapter 1 · Commercial Kitchens on commercial gas cooking equipment covers the gas path inside appliances and appliance leak testing, and Chapter 4 · Commercial Kitchens on kitchen hood suppression covers the gas valve that closes when the suppression system operates. Chapter 15 · Physics on ideal gases, Chapter 11 · Chemistry on hazardous gases, and Chapter 12 · Chemistry on thermochemistry give the molar volume, flammable limits, and heat of combustion used in Examples 2 to 5. Kitchen ventilation is in Chapter 16 · Buildings & Facilities, equipotential bonding in Chapter 29 · Electrical & Control, fire protection in Chapter 17 · Buildings & Facilities, non-electrical energy isolation in Chapter 4 · Safety, and confined spaces in Chapter 11 · Safety.
Exercises and worked solutions
Try to answer first, then open the worked solution.
At night all appliances and appliance valves are already closed, but the meter keeps moving: 2,310.40 m³ at 22:00 and 2,310.64 m³ at 02:00. What is the flow rate, and what does the technician do?
Check my answer
See the worked solution
The difference is 0.24 m³ in 4 hours, so m³/h, which is 60 liters per hour. Because all appliances are off, the flow is a leak downstream of the meter, so the technician records the readings, checks for smell in the upper part of the room without any source of ignition, and reports to the distribution company to find the leak point.
Why can a valve in a meter room that is always locked, with the key held only by the distribution company, not be relied on as the building’s emergency control valve?
Check my answer
See the worked solution
An emergency control valve should be readily accessible to gas users in an emergency, whereas a valve in a locked room can only be opened by the distribution company or the emergency services. In the first few minutes of a leak, a valve that the occupiers cannot reach is of no use, so the building needs an accessible emergency control valve or keys held by the occupiers.
The void above a kitchen ceiling measures 6 m by 4 m by 0.5 m. What volume of natural gas brings the whole space to the lower flammable limit?
Check my answer
See the worked solution
The volume is m³, and at the lower limit of 5 percent it takes m³ of natural gas. Because the gas rises and does not mix evenly, the upper layer of the space can reach the lower limit with a smaller amount of gas.
A renovation contractor blocks a permanent ventilation opening in a gas boiler room to make the room quieter. What is the problem, and who must be involved?
Check my answer
See the worked solution
Blocking permanent ventilation can cause incomplete combustion and raise carbon monoxide, and the UK rules prohibit building alterations that affect the safety of gas appliances already installed. The work is stopped and assessed with the gas installer before the ventilation is changed.
A detector shows 6 percent LEL in the corridor. What is that in percent by volume and ppm, and is the evacuation threshold of 10 percent LEL exceeded?
Check my answer
See the worked solution
The concentration is percent by volume, which is 3,000 ppm, below the threshold of 10 percent LEL. Although the threshold is not exceeded, the reading shows that gas is present, so its source is searched for by authorized personnel and the reading is monitored while avoiding sources of ignition.
A staff member finds an unmarked gas pipe in the service passage after the wall has been repainted. Why does this need to be reported?
Check my answer
See the worked solution
In non-domestic buildings, visible gas pipes should be permanently marked and the person responsible for the building keeps the marking legible. Without the marking, other workers may take the pipe for a water pipe or an empty duct and drill into or cut it, so the marking is restored by the designated party.
References
External sources
- Peraturan Menteri Energi dan Sumber Daya Mineral Nomor 4 Tahun 2018 tentang Pengusahaan Gas Bumi pada Kegiatan Usaha Hilir Minyak dan Gas Bumijdih.esdm.go.id
- Tips Wamen ESDM Agar Aman Pakai Jargas di Rumahesdm.go.id
- Dengan Tekanan 0,02 bar, Gas Bumi untuk Rumah Tangga Aman Digunakanesdm.go.id
- Safety in the installation and use of gas systems and appliances: Gas Safety (Installation and Use) Regulations 1998 as amended, Approved Code of Practice and guidance, L56 (Fifth edition)hse.gov.uk
- Gas safety in catering and hospitalityhse.gov.uk
- Gas safety for employershse.gov.uk
Revision history
| Date | Version | Change |
|---|---|---|
| November 14, 2026 | 1 | First published |
How to cite
Kurnia (2026). Natural gas piping in buildings: the connection from the network, meter and regulator, emergency control valve, pipe routes and ventilation, leak detection, and the limits of the work. ARSTEMA Academy. Revised November 14, 2026. arstema.com/en/academy/konsep/pipa-gas-alam-gedung-sambungan-dari-jaringan-meter-dan-regulator-katup-darurat-jalur-pipa-dan-ventilasi-deteksi-kebocoran-serta-batas-pekerjaan
Self-check · 3 questions
Check your understanding before moving on
Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.
Safety limits still apply. This quiz tests reasoning; it doesn’t authorize mixing, adjusting, dismantling, live measurement, or field action.
At night all appliances and appliance valves are already closed, but the meter keeps moving: 2,310.40 m³ at 22:00 and 2,310.64 m³ at 02:00. What is the flow rate, and what does the technician do?
Why can a valve in a meter room that is always locked, with the key held only by the distribution company, not be relied on as the building’s emergency control valve?
The void above a kitchen ceiling measures 6 m by 4 m by 0.5 m. What volume of natural gas brings the whole space to the lower flammable limit?