    Thermal insulation of pipes and ducts

    materials and thickness, condensation and dew point, heat loss, outer jacketing, damage and repair, and calculating savings

    The corridor ceiling of a hotel became stained and dripped under the chilled-water pipes after a renovation, although the pipes were not leaking: the insulation fitted was too thin for the humid ceiling air, so its surface was colder than the dew point. This chapter covers thermal insulation of pipes and ducts from the building technician’s side: what insulation does, materials and their conductivity, heat loss from insulated and bare pipes, the dew point from saturation vapor pressure and the thickness that prevents condensation, outer jacketing and vapor retarders, damage, surveys, and repair, and calculating savings with the US Department of Energy tables for bare steam pipe heat loss and valve covers. Old insulation that may contain asbestos is written as a stop condition, on the basis of HSE guidance and Permenaker 3/1985.

    Section you’re reading: Chapter opening

    Three months after the fifth floor of a hotel was renovated, the corridor ceiling began to show brown stains and, in the afternoons, to drip onto the carpet. The technician opened the ceiling panels and found the chilled-water pipes of the fan coil units wet along their whole run, but a pressure test showed no leak. The renovation contractor had replaced the old 25 mm insulation with 13 mm foam, and at two hangers the insulation had been crushed until the pipe showed. The space above the ceiling was connected to the outside air through gaps in the facade wall, so its air was hot and humid. The water came from the air itself, condensing on an insulation surface that was too cold.

    In the same building, the laundry boiler room had the opposite problem. After a steam trap repair, three valves and two flanges were left bare, the room grew hotter, and the boiler burned more fuel for heat lost to the air.

    Scope

    This chapter covers thermal insulation on hot-water, steam, condensate, and chilled-water pipes and on cool-air ducts in buildings, from the side of the technician who inspects, calculates, and reports: what insulation does, materials and thickness, heat loss, the dew point and the thickness that prevents condensation, outer jacketing, damage and repair, and savings. In many Indonesian buildings, thermal insulation is also called isolasi termal.

    The cylindrical conduction formula and the critical radius of insulation are in Chapter 24 · Physics on quantitative heat transfer, and psychrometrics and condensation in rooms in Chapter 16 · Buildings & Facilities on ventilation and air conditioning of laundry rooms and kitchens. Insulation of steam and condensate distribution lines is covered in Chapter 5 · Utilities on steam distribution and condensate, choosing efficiency projects by payback period in Chapter 11 · Utilities on energy efficiency of laundry utilities, and insulation of fan coil unit pipes in Chapter 15. Pipe expansion and supports are in Chapter 9, boilers in Chapter 4 · Utilities on boilers at inspection level, hot surfaces in Chapter 8 · Safety on heat, steam, and hot surfaces, thermography in Chapter 21 · Physics on radiation and thermography, and emissions from energy savings in Chapter 19 on carbon footprint.

    Insulation is installed and replaced by an insulation contractor according to the designer’s specification. Removing old insulation that may contain asbestos is a stop condition until the material has been examined by the competent party. Work on steam or hot-water pipes that are still pressurized or hot follows energy isolation in Chapter 4 · Safety on non-electrical energy isolation, and work above the ceiling follows Chapter 10 · Safety on work at height. US and English data are written as data of those countries.

    What insulation does on pipes and ducts

    Thermal insulation is a layer of low-conductivity material fitted around a pipe, duct, or piece of equipment to slow the flow of heat between its contents and the surrounding air. On hot pipes insulation keeps heat in, and on cold pipes it keeps heat out.

    Insulation has four functions. First, it saves energy: the US Department of Energy (DOE) writes that insulation can typically reduce the energy losses of steam pipes by 90 percent and helps ensure proper steam pressure at equipment. Second, it prevents condensation on pipes and ducts colder than the dew point of the surrounding air. Third, it protects people from burns, because insulation lowers the outer surface temperature of steam pipes. DOE recommends insulating any surface above 120 °F (48.9 °C), including boiler surfaces, steam and condensate pipes, and fittings. Fourth, it keeps the workspace comfortable and reduces the load on the cooling systems that remove heat from that space.

    Different functions call for different ways of thinking. On hot pipes, the measures of success are heat loss and surface temperature. On cold pipes, the measures are surface temperature against the dew point and an intact vapor retarder, because wet insulation fails at both functions at once.

    Insulation materials and their properties

    Thermal conductivity kk is the rate of heat flow through a material one meter thick per square meter of area for a temperature difference of one kelvin, in W/(m·K). The rate of conduction is proportional to the area, the temperature difference, and kk, and inversely proportional to the thickness. Good insulating materials, such as glass wool, wool, and foam, trap many small pockets of air and take advantage of the low conductivity of air.

    Materialkk, W/(m·K)
    Steel (iron)80
    Water0.6
    Asbestos0.16
    Glass wool, cork0.042
    Air0.023
    Polystyrene foam0.010

    The table values are textbook values at ordinary temperatures. Water is about 14 times a better conductor than glass wool, so wet insulation loses most of its insulating power (Example 6). Asbestos is listed because it was once widely used as pipe and boiler insulation, not because its conductivity is remarkable.

    For steam pipes, DOE names calcium silicate, mineral fiber, fiberglass, perlite, and cellular glass as common materials, and fiberglass and fabric blankets for valves and expansion joints that have to be opened during maintenance. The properties assessed include thermal conductivity, which varies with temperature so that the material’s temperature range must be known, strength under mechanical loads, abrasion resistance, workability, and resistance to water absorption. On chilled-water pipes and cool-air ducts, the material must resist water vapor: closed-cell foam, which does not readily absorb water vapor, or fibrous material wrapped in a vapor retarder. The material chosen must suit the operating temperature, the location, and the building’s fire requirements set by the designer.

    Heat loss and insulation thickness

    For one meter of insulated pipe, the heat flow is calculated from two thermal resistances in series, as in Chapter 24 · Physics:

    q′=Tf−TaRins′+Rout′,Rins′=ln⁡(r2/r1)2πk,Rout′=12πr2hq' = \frac{T_f - T_a}{R'_\text{ins} + R'_\text{out}}, \qquad R'_\text{ins} = \frac{\ln(r_2/r_1)}{2\pi k}, \qquad R'_\text{out} = \frac{1}{2\pi r_2 h}

    where q′q' is the heat flow per meter of pipe (W/m), positive from the contents to the air, TfT_f is the fluid temperature and TaT_a the surrounding air temperature (°C), r1r_1 is the outer radius of the pipe and r2r_2 the outer radius of the insulation (m), kk is the conductivity of the insulation (W/(m·K)), and hh is the combined convection and radiation coefficient at the outer surface (W/(m²·K)). The formula neglects the resistance of the fluid film inside and of the metal pipe wall, which are small compared with the insulation, and assumes steady flow and intact, dry insulation. For a bare pipe, q′=2πr1h(Tf−Ta)q' = 2\pi r_1 h (T_f - T_a). On a cold pipe, Tf<TaT_f < T_a and q′q' is negative, meaning that heat flows into the pipe; this chapter writes only its magnitude.

    Because the insulation resistance grows with the logarithm of the radius, each added thickness brings a smaller benefit. The thickness fitted is therefore chosen by the designer from cost, space, condensation, and surface temperature. The coefficient hh in still indoor air is on the order of a few to ten W/(m²·K) and changes with surface temperature, color, and air movement. This chapter uses a fixed value as an example figure; for decisions, the value is taken from the designer’s or manufacturer’s data.

    Condensation, dew point, and the thickness that prevents condensation

    The dew point is the temperature at which air cooled without changing its water vapor content reaches 100 percent relative humidity. The water vapor pressure in air is pv=ϕ psat(Ta)p_v = \phi \, p_\text{sat}(T_a), with ϕ\phi the relative humidity as a fraction, and the dew point is the temperature at which the saturation vapor pressure of water equals pvp_v. According to the physics textbook table, the saturation vapor pressure of water is 1.19 kPa at 10 °C, 1.69 kPa at 15 °C, 2.33 kPa at 20 °C, 3.17 kPa at 25 °C, and 4.24 kPa at 30 °C. Between two rows of the table, the dew point is estimated by linear interpolation, which is accurate enough for a 5 °C interval.

    The outer surface of the insulation on a cold pipe does not sweat as long as its temperature is above the dew point. That surface temperature is obtained from the heat flow and the outer resistance:

    Ts=Ta−q′Rout′T_s = T_a - q' R'_\text{out}

    where TsT_s is the outer surface temperature of the insulation (°C) and q′q' is the magnitude of the heat flow per meter. The anti-condensation insulation is the smallest thickness that makes TsT_s higher than the dew point plus a safety margin set by the designer; this chapter uses a margin of 1 K as an example figure. The most humid and hottest air that can occur where the pipe runs sets the thickness, not average conditions (Examples 1 and 2).

    On a rectangular air duct, the duct wall is taken as flat, and the outer surface temperature of the insulation becomes

    Ts=Ta−Ta−Tut/k+1/h⋅1hT_s = T_a - \frac{T_a - T_u}{t/k + 1/h} \cdot \frac{1}{h}

    where TuT_u is the air temperature inside the duct (°C) and tt is the insulation thickness (m), with the same assumptions as the pipe formula.

    Insulation on a cold pipe whose surface temperature is above the dew point can still get wet from the inside. Water vapor moves from the humid air through the material toward the cold pipe surface and condenses there unless it is stopped. A vapor retarder is a layer on the outside of cold-pipe insulation that keeps water vapor from entering the insulation. A vapor retarder torn at one point lets water in, the insulation gets wet, its conductivity rises, its surface gets colder, and condensation spreads (Example 6).

    Outer jacketing and vapor retarders

    Jacketing is a protective layer over the insulation, for example thin metal sheet or plastic, that protects the insulation from impact, foot traffic, sunlight, and water. Outdoors, the jacket joints are lapped like roof tiles, with the upper part covering the lower part, so that rainwater runs off and does not enter the insulation. On cold pipes, the jacket is fitted without damaging the vapor retarder, and every joint, end, and penetration is sealed tight.

    Insulation is often damaged at hangers and supports. Insulation squeezed by a clamp becomes thin, and on cold pipes a metal clamp touching the pipe becomes a thermal bridge that sweats. Supports for cold pipes use load-bearing insulated inserts, and supports and pipe expansion are covered in Chapter 9.

    A shiny metal jacket surface radiates less heat than a dull surface, so its outer coefficient hh is smaller. On hot pipes, the result is slightly lower heat loss but a higher surface temperature. On cold pipes, the smaller hh lowers the surface temperature and increases the risk of condensation. The anti-condensation thickness is therefore calculated with the hh that matches the jacket.

    Valves, flanges, and steam traps that have to be opened during maintenance are given removable insulation jackets. DOE describes removable and reusable insulating pads with noncombustible inner and outer covers that resist tearing, resist oil and water, and are held by wire or buckled straps. Steam traps are insulated according to the trap manufacturer’s directions so that they keep working properly. DOE also notes that a 6-inch gate valve may have more than 6 square feet of surface area radiating heat.

    Damage, surveys, and repair

    DOE notes that insulation is often damaged or removed and never replaced during steam system repairs, and that damaged or wet insulation should be repaired or replaced immediately. Sources of moisture are eliminated before the insulation is replaced, for example leaking valves, external pipe leaks, tube leaks, or leaks from nearby equipment. New insulation over a water source that has not been repaired will get wet again.

    An insulation survey is done by walking the pipe and duct routes and recording, for each run: the fluid and its temperature, the pipe diameter, the bare or damaged length, the number of bare valves and flanges, the parts that are wet, crushed, or without jacketing, and stains or drips beneath. Infrared thermometers and thermal cameras speed up the survey because bare or wet runs appear hotter or colder than their surroundings, with the caveat that readings on shiny metal need emissivity correction as in Chapter 21 · Physics. The survey results become a repair list ordered by savings, by the risk of condensation over electrical equipment and guest ceilings, and by the risk of burns.

    Asbestos-containing insulation. In Great Britain, HSE writes that asbestos insulation is mostly found on heating systems, for example around boilers, calorifiers, and pipework; that the material is fibrous and flakes and powders easily; and that on pipes it is often covered with a protective coating or paint of any color, which makes it harder to identify. Residues of insulation can also be found on brickwork and inside ducts. According to HSE, most work on asbestos insulation is high risk and must be done by an HSE-licensed contractor, because disturbing that insulation releases fibers very easily into the air that is breathed.

    DOE also asks for a check for asbestos before old insulation is removed. In Indonesia, Permenaker (Minister of Manpower Regulation) PER.03/MEN/1985 on occupational safety and health in the use of asbestos is listed as in force in JDIH Kemnaker as of November 2026; the regulation requires the employer to provide personal protective equipment, to inform workers about the hazards and safe work methods, and to control asbestos dust in workplace air. For the technician, old insulation of unknown material in an old building is not cut, stripped, or brushed, and examination of the material is handed to the competent party.

    Calculating savings

    For bare steam pipes, DOE gives a table of heat loss per 100 feet of pipe per year.

    Pipe diameter (in.)15 psig150 psig300 psig600 psig
    1140285375495
    2235480630840
    44158501,1201,500
    87401,5402,0302,725
    121,0552,2002,9103,920

    The figures are in MMBtu per year per 100 ft, for horizontal steel pipe, ambient air at 75 °F (23.9 °C), no wind, and 8,760 hours per year. One MMBtu equals one million Btu or 1.055 GJ, and 100 ft equals 30.48 m. The fuel saving from insulation is calculated with

    Efuel=ηins QbareηboilerE_\text{fuel} = \frac{\eta_\text{ins} \, Q_\text{bare}}{\eta_\text{boiler}}

    where EfuelE_\text{fuel} is the fuel energy saved per year, QbareQ_\text{bare} is the annual heat loss of the bare pipe in the same unit, ηins\eta_\text{ins} is the fraction of the loss cut by the insulation, and ηboiler\eta_\text{boiler} is the boiler efficiency. The DOE example uses insulation that cuts 90 percent of the loss and a boiler with 80 percent efficiency. The result is multiplied by the price of fuel energy to obtain the annual cost. The table is made for continuous operation; if the pipe is hot only part of the time, the result is multiplied by the fraction of operating hours.

    For valves, DOE gives the savings from a 1-inch insulating pad on a 150-pound-class flanged valve, with ambient air at 65 °F and no wind; for a 4-inch valve the saving is 2,300 Btu/h at 300 °F and 3,400 Btu/h at 400 °F, and for a 6-inch valve 3,300 and 5,800 Btu/h. One Btu/h equals 0.2931 W. For chilled-water pipes, the heat kept out is saved at the chiller, so the electricity saved equals that heat divided by the chiller COP. The savings are then compared with the repair cost as a payback period as in Chapter 11 · Utilities, and the emissions are calculated as in Chapter 19.

    Worked example

    The numbers in the examples below are practice numbers unless their origin is stated. A chilled-water pipe with an outside diameter of 60 mm (r1=0.030r_1 = 0.030 m) carries water at 7 °C in a ceiling space at 30 °C, with h=6h = 6 W/(m²·K) and foam insulation with k=0.035k = 0.035 W/(m·K).

    Example 1: dew point of the ceiling air. Ceiling air at 30 °C with 75 percent relative humidity has pv=0.75×4.24=3.18p_v = 0.75 \times 4.24 = 3.18 kPa. That value is just above 3.17 kPa at 25 °C, so the dew point is 25+5×(3.18−3.17)/(4.24−3.17)=25.025 + 5 \times (3.18 - 3.17)/(4.24 - 3.17) = 25.0 °C. A bare pipe with a surface at about 7 °C, far below 25 °C, will certainly sweat. With a 1 K margin, the insulation surface must be at least 26.0 °C.

    Example 2: 13 mm versus 25 mm insulation. For 13 mm, r2=0.043r_2 = 0.043 m, Rins′=ln⁡(0.043/0.030)/(2π×0.035)=1.637R'_\text{ins} = \ln(0.043/0.030)/(2\pi \times 0.035) = 1.637 K·m/W, Rout′=1/(2π×0.043×6)=0.617R'_\text{out} = 1/(2\pi \times 0.043 \times 6) = 0.617 K·m/W, q′=23/(1.637+0.617)=10.2q' = 23/(1.637 + 0.617) = 10.2 W/m, and Ts=30−10.2×0.617=23.7T_s = 30 - 10.2 \times 0.617 = 23.7 °C. That surface is below the dew point of 25.0 °C, so the insulation sweats as in the opening case. For 25 mm, r2=0.055r_2 = 0.055 m, Rins′=2.756R'_\text{ins} = 2.756, Rout′=0.482R'_\text{out} = 0.482, q′=23/(2.756+0.482)=7.10q' = 23/(2.756 + 0.482) = 7.10 W/m, and Ts=30−7.10×0.482=26.6T_s = 30 - 7.10 \times 0.482 = 26.6 °C, meeting the 26.0 °C requirement. A 19 mm thickness gives Ts=25.5T_s = 25.5 °C, only 0.5 K above the dew point, so it does not meet the safety margin.

    Example 3: heat gain and chiller electricity. The bare pipe gains 2π×0.030×6×23=26.02\pi \times 0.030 \times 6 \times 23 = 26.0 W/m of sensible heat, plus latent heat from the water that condenses. With 25 mm insulation, the heat gain is 7.10 W/m. For 40 m of pipe, the difference is (26.0−7.10)×40=756(26.0 - 7.10) \times 40 = 756 W, or 756×8,760/1000=6,623756 \times 8{,}760/1000 = 6{,}623 kWh of heat per year. With a chiller COP of 3, the electricity saved is 6,623/3=2,2086{,}623/3 = 2{,}208 kWh per year. Condensation on the bare pipe adds further load on the chiller, so this figure is a lower bound.

    Example 4: a laundry steam pipe survey with the DOE table. The survey found 30 m of 2-inch pipe and 12 m of 1-inch pipe at 150 psig, and 20 m of 4-inch pipe at 15 psig, all bare and in continuous operation. Their heat losses are 480×30/30.48=472.4480 \times 30/30.48 = 472.4, 285×12/30.48=112.2285 \times 12/30.48 = 112.2, and 415×20/30.48=272.3415 \times 20/30.48 = 272.3 MMBtu per year, a total of 856.9 MMBtu. The fuel saving is 0.9×856.9/0.8=964.00.9 \times 856.9/0.8 = 964.0 MMBtu, that is, 964.0×1.055=1,017964.0 \times 1.055 = 1{,}017 GJ per year. At a fuel energy price of IDR 300,000 per GJ, the value is about IDR 305 million per year. Boiler rooms in Indonesia are usually hotter than 23.9 °C, so the actual loss is slightly smaller than the table figure.

    Example 5: jackets for six 4-inch valves. The steam at the valves is about 350 °F (176.7 °C). Interpolating the DOE table for a 4-inch valve gives 2,300+(350−300)/(400−300)×(3,400−2,300)=2,8502{,}300 + (350 - 300)/(400 - 300) \times (3{,}400 - 2{,}300) = 2{,}850 Btu/h, that is, 2,850×0.2931=8352{,}850 \times 0.2931 = 835 W per valve. Six valves save 5.01 kW. Over 6,000 operating hours per year, the heat is 5.01×6,000=30,0605.01 \times 6{,}000 = 30{,}060 kWh, and the fuel is 30,060/0.8=37,57530{,}060/0.8 = 37{,}575 kWh, that is, 37,575×0.0036=135.337{,}575 \times 0.0036 = 135.3 GJ or about IDR 40.6 million per year. If the six jackets cost IDR 24 million, the payback period is 24/40.6=0.5924/40.6 = 0.59 years, about seven months.

    Example 6: wet insulation. The vapor retarder of the 25 mm insulation tears at a hanger, water gets in, and its effective conductivity rises from 0.035 to 0.15 W/(m·K). Rins′=ln⁡(0.055/0.030)/(2π×0.15)=0.643R'_\text{ins} = \ln(0.055/0.030)/(2\pi \times 0.15) = 0.643 K·m/W, q′=23/(0.643+0.482)=20.4q' = 23/(0.643 + 0.482) = 20.4 W/m, and Ts=30−20.4×0.482=20.2T_s = 30 - 20.4 \times 0.482 = 20.2 °C. The surface is now 4.8 K below the dew point, the heat gain is almost three times as large, and the condensing water wets the neighboring insulation. The repair replaces the whole wet run and restores the vapor retarder rather than patching the surface.

    Stop conditions

    1. Old insulation on pipes, boilers, calorifiers, or ducts in an old building is of unknown material, flaking, powdering, or painted over: do not cut, strip, brush, or clean it; close off access to the area, and the chief engineer hands examination of the material to the competent party and removal to a contractor licensed to handle asbestos.
    2. Water is dripping from a pipe or duct onto an electrical panel, electrical equipment, or a light fitting: switch that equipment off through the building procedure if it is safe to do so and report; an authorized electrician inspects the equipment before it is switched back on.
    3. The insulation repair would require opening or cutting a pipe, valve, or flange, or would be done on steam and hot-water pipes that are still pressurized: postpone until energy isolation as in Chapter 4 · Safety, and a mechanical contractor does the work.
    4. A ceiling over a guest area is wet and bulging, or a ceiling panel is heavy with water: the area beneath is closed to guests, and the building management asks a ceiling contractor to inspect it before the panel is opened.
    5. The surface of a bare pipe or valve on a route people use is too hot to touch: put up a barrier and a hot surface sign as in Chapter 8 · Safety until the insulation contractor fits a cover.
    6. Insulation is wet because of a leaking valve, flange, or pipe: do not fit new insulation over it; the leak is first repaired by a piping technician or a mechanical contractor.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    A dripping pipe must be leaking.

    Why is it wrong?

    A chilled-water pipe can be wet because water from the air condenses on a surface colder than the dew point, as in the opening case and Example 2.

    Common misconception

    Slightly thinner insulation makes no difference.

    Why is it wrong?

    On a cold pipe in humid air, a few millimeters decide whether the surface is above or below the dew point. In Example 2, 13 mm sweats and 25 mm does not.

    Common misconception

    Wet insulation is still insulation.

    Why is it wrong?

    Water is about 14 times a better conductor than glass wool. In Example 6, wet insulation makes the heat gain almost three times as large and lowers the surface below the dew point.

    Common misconception

    The thicker the insulation, the greater the saving, in proportion to the thickness.

    Why is it wrong?

    Resistance grows with the logarithm of the radius, so the first layer gives the largest saving and each addition gives less.

    Common misconception

    Small valves and flanges do not need insulation.

    Why is it wrong?

    According to DOE, a 6-inch gate valve may have more than 6 square feet of surface area, and the 4-inch valve jackets in Example 5 pay back in about seven months.

    Chapter 24 · Physics on quantitative heat transfer derives the cylindrical conduction formula and critical radius used here, and Chapter 16 · Buildings & Facilities on ventilation and air conditioning of rooms gives psychrometrics and ways of lowering the dew point of room air. Chapter 5 · Utilities on steam distribution and condensate and Chapter 11 · Utilities on energy efficiency of laundry utilities place insulation among other saving projects. Chapter 15 on chilled-water fan coil units covers insulation of supply and drain pipes in hotel rooms, and Chapter 9 on pipe expansion and supports covers the supports where insulation is often damaged.

    Exercises and worked solutions

    The numbers in the exercises are for practice.

    Try to answer first, then open the worked solution.

    1. Ceiling air is at 30 °C with 60 percent relative humidity. What is its dew point, and is the 13 mm insulation in Example 2 enough with a 1 K safety margin?

      Check my answer
      See the worked solution

      The vapor pressure is 0.60×4.24=2.540.60 \times 4.24 = 2.54 kPa, between 2.33 kPa at 20 °C and 3.17 kPa at 25 °C, so the dew point is 20+5×(2.54−2.33)/(3.17−2.33)=21.320 + 5 \times (2.54 - 2.33)/(3.17 - 2.33) = 21.3 °C. The 13 mm insulation gives a surface of 23.7 °C, above 22.3 °C, so it is enough for that air; the same insulation fails in 75 percent air, so the thickness is set by the most humid air that can occur.

    2. Why must the vapor retarder on a chilled-water pipe be intact, even though the outer surface temperature of its insulation is already above the dew point?

      Check my answer
      See the worked solution

      Water vapor passes through the insulation material from the humid air toward the cold pipe surface, and without a vapor retarder it condenses inside the insulation near the pipe. Insulation wet from the inside conducts heat better, its surface gets colder, and condensation spreads as in Example 6.

    3. A 6 m length of 8-inch steam pipe at 150 psig in the boiler room is bare. What is its annual heat loss according to the DOE table, and how much fuel is saved with insulation that cuts 90 percent of the loss and an 80 percent boiler?

      Check my answer
      See the worked solution

      The heat loss is 1,540×6/30.48=303.11{,}540 \times 6/30.48 = 303.1 MMBtu per year. The fuel saved is 0.9×303.1/0.8=341.00.9 \times 303.1/0.8 = 341.0 MMBtu, about 359.8 GJ per year, because every unit of heat not lost does not have to be produced by a boiler that is only 80 percent efficient.

    4. A contractor wants to strip the old painted insulation in the boiler room of an old building and fit new insulation the same day. What does the technician do?

      Check my answer
      See the worked solution

      The technician stops the work, because old painted insulation in the boiler room of an old building is among the places where asbestos insulation is most often found, and stripping it releases fibers into the air. The chief engineer hands examination of the material to the competent party, and removal is done only by a contractor licensed to handle asbestos.

    5. A cool-air duct carrying air at 14 °C runs through a 30 °C ceiling with a dew point of 25.0 °C. With h=6h = 6 W/(m²·K), k=0.035k = 0.035 W/(m·K), and a 1 K safety margin, what is the minimum insulation thickness?

      Check my answer
      See the worked solution

      The surface must be at least 26 °C, so the temperature difference across the outer air layer may be at most 4 K of the total 16 K. From the flat-wall formula, 16/(h t/k+1)≤416/(h\,t/k + 1) \le 4, so h t/k≥3h\,t/k \ge 3 and t≥3k/h=3×0.035/6=0.0175t \ge 3k/h = 3 \times 0.035/6 = 0.0175 m, that is, 17.5 mm; the thickness fitted is the next thicker commercial size.

    6. Increasing the pipe insulation in Example 2 from 25 mm to 40 mm lowers the heat gain from 7.10 to 5.43 W/m. Compare this with the benefit of the first 25 mm and explain what it means.

      Check my answer
      See the worked solution

      From bare to 25 mm, the heat gain falls by 26.0−7.10=18.926.0 - 7.10 = 18.9 W/m, while from 25 mm to 40 mm it falls by only 7.10−5.43=1.677.10 - 5.43 = 1.67 W/m. The first layer gives almost all of the benefit because resistance grows with the logarithm of the radius, so extra thickness is usually worthwhile only when it is needed for condensation or when energy is very expensive.

    References

    External sources

    • Insulate Steam Distribution and Condensate Return Linesenergy.gov
    • Install Removable Insulation on Valves and Fittingsenergy.gov
    • Improving Steam System Performance: A Sourcebook for Industry, Second Editionenergy.gov
    • College Physics 2eopenstax.org
    • Locations of asbestos and taking the right actionhse.gov.uk
    • Peraturan Menteri Tenaga Kerja Nomor PER.03/MEN/1985 tentang Keselamatan dan Kesehatan Kerja Pemakaian Asbesjdih.kemnaker.go.id

    Revision history

    DateVersionChange
    November 14, 20261First published

    How to cite

    Kurnia (2026). Thermal insulation of pipes and ducts: materials and thickness, condensation and dew point, heat loss, outer jacketing, damage and repair, and calculating savings. ARSTEMA Academy. Revised November 14, 2026. arstema.com/en/academy/konsep/insulasi-termal-pipa-dan-saluran-bahan-dan-tebal-kondensasi-dan-titik-embun-rugi-panas-pelapis-luar-kerusakan-dan-perbaikan-serta-menghitung-penghematan

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated
    1

    Ceiling air is at 30 °C with 60 percent relative humidity. What is its dew point, and is the 13 mm insulation in Example 2 enough with a 1 K safety margin?

    2

    Why must the vapor retarder on a chilled-water pipe be intact, even though the outer surface temperature of its insulation is already above the dew point?

    3

    A 6 m length of 8-inch steam pipe at 150 psig in the boiler room is bare. What is its annual heat loss according to the DOE table, and how much fuel is saved with insulation that cuts 90 percent of the loss and an 80 percent boiler?

    Self-assessment progress0%