Skip to content

Search ARSTEMA

Type a chapter, term, symptom, or tool.

    Fluids & Thermal · Chapter 25Quantitative

    By Kurnia · Published November 15, 2026 · Version 1 · 21 min read

    Humidity control in storerooms and archive rooms

    relative humidity and dew point, refrigerant and desiccant dehumidifiers, capacity and condensate disposal, mold, and monitoring

    The medical records archive room of a hospital smells musty every Monday morning and its folders are cockled, although two new dehumidifiers have been installed: the air conditioning is switched off at night, humid outdoor air leaks in, and the tanks of both units are full before midnight. This chapter covers humidity control in storerooms and archive rooms from the building technician’s side: relative humidity, dew point, and humidity ratio with a table of saturation vapor pressure and density, humidity targets according to EPA and the US National Park Service, the moisture load from infiltration in liters per day, refrigerant and desiccant dehumidifiers and silica gel, label capacity in pints per day and its test conditions under the US Department of Energy test procedure, condensate disposal, mold on stored materials, and monitoring with calibrated data loggers. Work on the refrigerant circuit and handling of wet or moldy records are written as limits of authority.

    Section you’re reading: Chapter opening

    The medical records archive room of a hospital is on the ground floor, with one outside wall facing a garden. To save electricity, its air conditioning is switched off from 17.00 to 07.00 and over the whole weekend. After the rainy season, the medical records staff report that the folders on the bottom shelves are cockled, some files have brown spots, and the room smells musty every Monday morning. Two portable dehumidifiers were bought, but every morning both units have stopped with the tank-full light on, and the hygrometer reads 78 percent at 25 °C, although in the daytime with the air conditioning on it reads 55 percent.

    The technician has to answer with numbers: how much water comes in each day, what capacity the dehumidifiers have at the conditions of that room, where the condensate goes, and how to prove that the humidity is under control.

    Scope

    This chapter covers humidity control in storage rooms whose contents are sensitive to damp: dry goods and hotel supply storerooms, office archive rooms, and paper medical records rooms in hospitals. Humidity targets from US agencies are written as data of that country. The provisions of the National Archives of the Republic of Indonesia (ANRI) on archive storage facilities could not be opened for this chapter as of November 2026, so their numbers are not given; the records manager confirms them with the archives unit of their institution.

    Psychrometrics and the ventilation moisture balance are in Chapter 16 · Buildings & Facilities on ventilation and air conditioning of laundry rooms and kitchens, and the dew point from partial pressure in Chapter 15 · Physics on ideal gases. The biology and cleanup of mold are in Chapter 9 · Biology & Microbiology on mold in buildings, the vapor compression cycle in Chapter 25 · Physics, and the limits of refrigerant work in Chapter 9 · Utilities on commercial refrigeration. Insulation that prevents condensation is in Chapter 24, AC condensate lines in Chapter 14, and data loggers in Chapter 12 · Systems, Diagrams & Diagnosis.

    This chapter contains no steps for opening, charging, or repairing the refrigerant circuit of a dehumidifier; that work belongs to a qualified refrigeration technician. Handling wet or moldy records is the authority of the records manager and a conservator.

    Relative humidity, dew point, and humidity ratio

    Relative humidity is the ratio of the amount of water vapor in the air to the amount of water vapor at saturation at the same temperature. The physics textbook defines it as the ratio of vapor density to saturation vapor density, and because water vapor behaves like an ideal gas, that ratio equals the ratio of vapor pressures:

    ϕ=ρvρsat(T)=pvpsat(T)\phi = \frac{\rho_v}{\rho_\text{sat}(T)} = \frac{p_v}{p_\text{sat}(T)}

    where ϕ\phi is the relative humidity as a fraction, ρv\rho_v the water vapor density (g/m³), pvp_v the water vapor pressure (kPa), and TT the air temperature (°C). Vapor density is the mass of water vapor per cubic meter of air. This chapter uses vapor density to calculate the mass of water and vapor pressure to calculate the dew point.

    Temperature (°C)Saturation vapor pressure (kPa)Saturation vapor density (g/m³)
    101.199.40
    151.6912.8
    202.3317.2
    253.1723.0
    304.2430.4

    Dew point is the temperature at which air cooled without changing its water vapor content reaches a relative humidity of 100 percent. The dew point is estimated as the temperature at which psatp_\text{sat} equals pvp_v, by linear interpolation between two rows of the table as in Chapter 24. Humidity ratio is the mass of water vapor per kilogram of dry air, ω=0.622 pv/(p−pv)\omega = 0.622\,p_v/(p - p_v) with pp the total air pressure; Chapter 16 · Buildings & Facilities calls it kelembapan spesifik (specific humidity).

    Relative humidity determines how much water paper, cardboard, and wood absorb, while the dew point determines which surfaces get wet. As long as no water is added or removed, the humidity ratio and dew point stay the same, while relative humidity changes with temperature: in a closed space, a rise in temperature lowers relative humidity and a drop in temperature raises it. A storeroom without air conditioning that cools down at night can therefore rise to high humidity without a single gram of added water (Example 2).

    Humidity targets for storerooms and archives

    For indoor spaces in general, the US Environmental Protection Agency (EPA) recommends keeping relative humidity below 60 percent, ideally 30 to 50 percent, if possible. For air-conditioned buildings in humid weather, the EPA moisture control guidance asks for the indoor dew point to be kept below 55 °F (12.8 °C), for example a maximum of 50 percent at 75 °F (23.9 °C), so that supply air ducts and chilled-water pipes do not condense.

    For collections of paper, wood, leather, and textiles, the US National Park Service (NPS) gives a setpoint of 45 to 55 percent with fluctuations ideally not exceeding plus or minus 5 percent, and in climates with distinct seasons an annual range of 40 to 60 percent. Relative humidity is not allowed to rise as high as 65 percent because mold might develop, and below 35 percent some materials such as bone and shell may become brittle and crack. Set point is the value held by a controller or a work plan, and fluctuation is the size of the rise and fall of the measured value around it.

    Hygroscopic material is material that absorbs and releases water vapor from the air until it reaches its equilibrium moisture content, the moisture content in balance with the humidity of the surrounding air. According to NPS, that equilibrium is slow and can take days or weeks. For that reason the paper in an archive room that was damp overnight keeps releasing water for hours after the air conditioning is switched on in the morning, and repeated rises and falls in humidity make it swell and shrink.

    Chapter 40 · Buildings & Facilities on indoor air quality records a humidity range of 40 to 60 percent in the Indonesian indoor air quality standard. A practical target for storerooms and archives in a tropical climate is a stable relative humidity below 60 percent, with the setpoint agreed with the records manager; high-value archives need an air conditioning design from a designer.

    Where the water comes from: the moisture load of a storage room

    Moisture load is the rate at which water enters the room air and has to be removed to hold the humidity at the target, in kg per hour or liters per day; one kilogram of water is about one liter. According to EPA, during the cooling season the largest sources of humidity in commercial buildings are ventilation air, makeup air, and outdoor air that infiltrates through gaps in the building enclosure. Other sources are walls below ground level, leaks, floor mopping, and goods that arrive damp.

    For a closed room that receives outdoor air only through gaps, the infiltration load is calculated with

    m˙w=n V (ρv,out−ρv,in)\dot{m}_w = n \, V \, (\rho_{v,\text{out}} - \rho_{v,\text{in}})

    where m˙w\dot{m}_w is the rate of water vapor coming in (g/h), nn the number of air changes per hour from infiltration, VV the room volume (m³), and ρv\rho_v the vapor density of the outdoor and indoor air (g/m³), each equal to ϕ ρsat(T)\phi \, \rho_\text{sat}(T). The formula assumes that the air coming in and going out has the same volume and mixes evenly; the error is small compared with the uncertainty in nn, which can only be estimated from observation or measurement. The daily load in liters is m˙w×24/1000\dot{m}_w \times 24/1000.

    According to EPA, ventilation air only dries a room when the outdoor dew point is lower than the indoor dew point, and dehumidification equipment is sized from the peak outdoor dew point, not from the peak sensible heat. In a humid tropical climate, the dew point of night air is generally above the target dew point of an archive room, so opening storeroom windows at night adds water (Exercise 2).

    The first step is therefore to reduce the water coming in: sealing gaps in doors and walls, repairing roof and pipe leaks, and not leaving storeroom doors open. NPS writes that a dehumidifier is not used as a permanent corrective measure; the reason the air is damp is found and the source of water is removed. Example 5 shows that sealing gaps is often cheaper than adding units.

    Refrigerant and desiccant dehumidifiers

    A dehumidifier is a device that removes water vapor from the air of a room. According to NPS, air is dehumidified either by refrigeration or by a desiccant.

    A refrigerant dehumidifier works like a refrigerator: air passes over a coil colder than its dew point, the water vapor condenses, and the saturated air is then reheated so that its relative humidity drops. In a portable unit, the reheating takes place in the condenser that the same air passes through, following the vapor compression cycle in Chapter 25 · Physics, and the electrical energy and the latent heat of the condensed water end up as heat in the room. In a cold room, the coil can frost and the unit has to defrost it, a possibility discussed by DOE when setting a low-temperature test condition.

    A desiccant dehumidifier passes air through a moisture-absorbing material, for example lithium chloride, and in a separate step hot air is blown over that material to dry it again. Desiccant is a material that absorbs water vapor from the air, and regeneration is drying the desiccant again with heat. The hot, humid regeneration air is discharged outdoors through a duct, so part of the water leaves as vapor rather than as liquid condensate, as DOE notes for combined refrigerant-desiccant dehumidifiers. Desiccants suit cold rooms or very dry targets, but need regeneration heat.

    Desiccants are also used without a machine. Silica gel can absorb up to 40 percent of its weight in water, but it can only maintain a microenvironment, the air inside a closed enclosure separated from the room air, when the enclosure is well sealed. For hybrid gels, museums commonly use one quarter to one half pound of gel per cubic foot of space, in containers less than two inches thick so that the surface area is large.

    The building technician cleans the filter and coil according to the manual and records performance; oil stains, a hissing sound, or a coil that is not cold are handed to a refrigeration technician, as in the limits in Chapter 9 · Utilities and Chapter 14.

    Capacity in liters per day

    Dehumidifier capacity is the mass of water a device removes in 24 hours at specified test conditions. In the United States, capacity is stated in pints per day, and efficiency as the energy factor, the liters of water removed per kWh of electricity. The test procedure of the US Department of Energy (DOE) uses a factor of 0.473 to convert pints per day to liters per day.

    The label value only applies at its test conditions. The older test standard used 80 °F (26.7 °C) and 60 percent relative humidity. The 2015 DOE test procedure lowered the test temperature for portable dehumidifiers to 65 °F (18.3 °C) at 60 percent, and for whole-home dehumidifiers to 73 °F (22.8 °C), noting that at the lower temperature a device extracts less condensate and so its measured capacity is lower. Testing at a DOE national laboratory also showed that the water removal rate and energy factor change with the temperature and humidity of the inlet air, so capacity in the room is read from the manufacturer’s table.

    The number of units is calculated from the moisture load:

    N≥m˙dayf Clabel,D=m˙dayN f ClabelN \ge \frac{\dot{m}_\text{day}}{f \, C_\text{label}}, \qquad D = \frac{\dot{m}_\text{day}}{N \, f \, C_\text{label}}

    where NN is the number of units, m˙day\dot{m}_\text{day} the moisture load (L/day), ClabelC_\text{label} the label capacity (L/day), ff the capacity factor at room conditions from manufacturer data, and DD the duty cycle. Duty cycle is the fraction of time the device has to run to remove that load. A duty cycle above about 80 percent leaves little reserve; this limit is an example number, not a standard. Daily energy is approximately E=m˙day/EFE = \dot{m}_\text{day}/EF, with EFEF the energy factor (L/kWh).

    NPS asks for the size and number of dehumidifiers to be selected with a mechanical engineer from the size of the space, the air exchange rate, the difference between inside and outside conditions, and the number of people using the room, with the air well circulated, using fans if needed.

    Condensate disposal and installation

    Condensate is the water that condenses on the coil and is collected by the dehumidifier. A portable unit holds it in a tank and stops when the tank is full, or drains it through a hose. In the opening case, the 4 liter tanks are full before midnight (Example 6).

    For continuous operation, condensate drains by gravity to a trapped floor drain, or is pumped by a condensate pump when the discharge point is higher than the unit outlet. The hose is laid falling without upward loops, is not kinked or stepped on, its end is not submerged, and its route does not pass over archive shelves. Hose slope and diameter are read from the manual, and condensate lines and their traps are covered in Chapter 14.

    NPS warns that portable dehumidifiers need routine emptying of their tanks, monitoring to prevent water damage and electrical fires, and regular cleaning. This means the unit is plugged into a sound outlet, is inspected as portable electrical equipment under Chapter 114 · Electrical & Control, and its pan is cleaned so it does not become slimy. On desiccant dehumidifiers, the regeneration air duct to the outside of the building is checked just as carefully, because regeneration air discharged into the ceiling brings back the water just removed.

    Mold and stored materials

    Mold needs organic material, so cellulose-based materials such as cotton, linen, paper, and wood, and protein materials such as leather and parchment, are particularly susceptible. Mold stains and weakens paper and textiles, and its first sign is often a musty odor. NPS writes that spores are less likely to germinate at a relative humidity of 45 to 55 percent, asks for relative humidity always to be kept below 65 percent, and states that portable dehumidifiers are necessary when relative humidity rises above 65 percent; these conditions only reduce the potential for growth, they do not eliminate it.

    Records placed against an outside wall or the floor often grow mold first because those surfaces are colder, as calculated in Chapter 9 · Biology & Microbiology. NPS asks for collection materials to be stored at least four inches (about 10 cm) above the floor and not directly against outside walls. When materials get wet from a leak, EPA writes that materials dried within 24 to 48 hours will, in most cases, not grow mold.

    When mold is already visible, the technician does not clean the records. NPS asks for the affected object to be sealed in polyethylene, not touched, moved to an isolated space dried with a dehumidifier, and handled together with a conservator. The technician lowers the humidity, stops the water source, and prepares the humidity data.

    Monitoring and data loggers

    Monitoring shows the condition of the room all the time, not only when the technician visits. NPS asks for data loggers to be placed in several locations and at several heights, including inside selected storage cabinets, away from windows, vents, and sources of heat or light, with one logger outside the building if possible, and for the data to be reviewed monthly together with a record of events such as roof leaks or recalibration. In the opening case, loggers in the shelf aisle, on a bottom shelf near the outside wall, and outside the building already show the night-time pattern.

    According to NPS, a sampling interval of every 20 to 30 minutes is generally recommended for long-term monitoring, the battery should last a full year, and data is downloaded before the memory is full. Electronic sensors need recalibration; manufacturer recommendations range from 6 months to 3 years, with most advocating annual calibration, and new units can be checked with small chambers containing saturated salt solutions. Hygrometers and hygrothermographs are recommended to be calibrated at least every three months, preferably monthly, against a psychrometer or electronic hygrometer. Calibration traceability is covered in Chapter 61 · Electrical & Control.

    Alarm limits are set according to the target, for example a high alarm at 60 percent and an urgent alarm at 65 percent, with a time delay so that a door opened briefly does not flood the alarms, as in Chapter 33 · Buildings & Facilities on BMS alarms. Every alarm is recorded together with the action taken.

    Worked example

    The numbers in the examples below are practice numbers unless their origin is stated. The archive room in the opening case measures 6 m by 8 m by 3 m, which is 144 m³, and saturation values are taken from the table above.

    Example 1: morning conditions in the archive room. At 25 °C and 78 percent, pv=0.78×3.17=2.47p_v = 0.78 \times 3.17 = 2.47 kPa, so the dew point is 20+5×(2.47−2.33)/(3.17−2.33)=20.820 + 5 \times (2.47 - 2.33)/(3.17 - 2.33) = 20.8 °C and the humidity ratio is ω=0.622×2.47/(101.3−2.47)=0.0155\omega = 0.622 \times 2.47/(101.3 - 2.47) = 0.0155 kg/kg. The vapor density is 0.78×23.0=17.90.78 \times 23.0 = 17.9 g/m³. To drop to 50 percent, which is 0.50×23.0=11.50.50 \times 23.0 = 11.5 g/m³, the air only has to lose 144×(17.9−11.5)=922144 \times (17.9 - 11.5) = 922 g, less than one liter. Yet both tanks fill every night, so most of the water comes from outdoor air and from paper releasing its moisture.

    Example 2: a storeroom without air conditioning at night. A hotel supply storeroom with a metal roof is at 30 °C and 60 percent in the late afternoon: pv=0.60×4.24=2.54p_v = 0.60 \times 4.24 = 2.54 kPa. At night its temperature drops to 25 °C with no added water, so its relative humidity becomes 2.54/3.17=802.54/3.17 = 80 percent, above the NPS limit of 65 percent. The dew point stays at 20+5×(2.54−2.33)/(3.17−2.33)=21.320 + 5 \times (2.54 - 2.33)/(3.17 - 2.33) = 21.3 °C, so a roof colder than 21.3 °C condenses water that can drip onto the cartons.

    Example 3: infiltration load in liters per day. With the air conditioning off, outdoor air at 25 °C and 90 percent infiltrates at about 1 air change per hour, while the indoor target is 25 °C and 50 percent. ρv,out=0.90×23.0=20.7\rho_{v,\text{out}} = 0.90 \times 23.0 = 20.7 g/m³ and ρv,in=11.5\rho_{v,\text{in}} = 11.5 g/m³, so m˙w=1×144×(20.7−11.5)=1,325\dot{m}_w = 1 \times 144 \times (20.7 - 11.5) = 1{,}325 g/h, or 1.325×24=31.81.325 \times 24 = 31.8 kg, about 31.8 L per day.

    Example 4: choosing the number of units. The label states 50 pints per day at 65 °F and 60 percent, which is 50×0.473=23.750 \times 0.473 = 23.7 L/day. The manufacturer’s table gives f=0.9f = 0.9 for 25 °C and 50 percent, so the capacity in this room is 0.9×23.7=21.30.9 \times 23.7 = 21.3 L/day and one unit is not enough. Two units give 42.6 L/day with a duty cycle of 31.8/42.6=7531.8/42.6 = 75 percent. The number of units in the opening case is sufficient; what is wrong is the condensate disposal (Example 6).

    Example 5: energy, and sealing gaps first. With an energy factor of 1.8 L/kWh, the daily energy is 31.8/1.8=17.731.8/1.8 = 17.7 kWh, an average of 17.7/24=0.7417.7/24 = 0.74 kW that becomes heat in the room. A month is 17.7×30=53117.7 \times 30 = 531 kWh, about Rp796,500 at a tariff of Rp1,500 per kWh. If the gaps are sealed so that infiltration drops to 0.4 air changes per hour, the load is 0.4×144×9.2=5300.4 \times 144 \times 9.2 = 530 g/h, which is 12.7 L/day, and the energy is 12.7/1.8=7.112.7/1.8 = 7.1 kWh/day. The saving is (17.7−7.1)×30=318(17.7 - 7.1) \times 30 = 318 kWh a month, about Rp477,000, and one unit is enough at a duty cycle of 12.7/21.3=6012.7/21.3 = 60 percent.

    Example 6: full tanks and a drain hose. Each unit removes 31.8/2=15.931.8/2 = 15.9 L/day, which is 15.9/24=0.6615.9/24 = 0.66 L/h, so a 4 L tank is full in 4/0.66=6.14/0.66 = 6.1 hours. A unit switched on at 17.00 stops at about 23.00, and the room is not dehumidified for 8 hours until 07.00. The fix is a hose to a trapped floor drain 6 m away: the hose outlet on the unit is 0.25 m above the floor, and with an example slope of 1 percent its end drops 0.01×6=0.060.01 \times 6 = 0.06 m, still 0.25−0.06=0.190.25 - 0.06 = 0.19 m above the floor. A discharge point at sink height needs a condensate pump.

    Stop conditions

    1. Water from the tank, condensate hose, air conditioner, or a leak is pooling near an outlet, a cable, or a running unit: do not touch a wet plug or cable; an electrician disconnects the circuit at the panel, and the water source is repaired before the unit is switched on again.
    2. The dehumidifier smells burnt, its cable or plug is hot, or the unit is plugged in through stacked extension cords: stop using it; the designated person inspects it as portable electrical equipment under Chapter 114 · Electrical & Control.
    3. The unit runs but its coil is not cold and produces no water, there is a hissing sound, or there is an oil stain on the piping: do not open the casing or the refrigerant circuit; the repair is handed to a qualified refrigeration technician.
    4. Records, cartons, or shelves are wet from a flood or a leak: do not heat, separate the sheets of, or move wet records without direction; the records manager together with a conservator takes over the records, while the technician stops the water source and dries the room.
    5. Mold is visible on records, cartons, or walls, or workers complain of breathlessness and allergy in the room: do not brush, shake, or vacuum the patches; cover the affected material with plastic, restrict access, and handle it under Chapter 9 · Biology & Microbiology together with the occupational safety and health (K3) officer or the infection prevention team.
    6. The regeneration air duct of a desiccant dehumidifier is blocked, detached, or discharging hot air into the ceiling or the room: switch the unit off; the supplier or the air conditioning contractor repairs it.
    7. The archive room humidity stays above 65 percent for more than a day even though the dehumidifiers are running with correct drainage: report to the chief engineer and the records manager; an air conditioning designer assesses the water source and the system.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    A dehumidifier solves the damp problem.

    Why is it wrong?

    A dehumidifier removes water that has already come in, while the water source still has to be removed. In Example 5, sealing gaps lowers the load from 31.8 to 12.7 L/day.

    Common misconception

    Opening the windows at night dries the storeroom.

    Why is it wrong?

    Ventilation only dries a room when the outdoor dew point is lower than the indoor dew point. Night air with a dew point of about 23 °C carries water into a room whose target dew point is 14 °C.

    Common misconception

    The label capacity is the capacity in my storeroom.

    Why is it wrong?

    Label capacity is measured at test conditions, for example 65 °F and 60 percent, and changes with room temperature and humidity. Capacity in the room is read from the manufacturer’s table, like the factor of 0.9 in Example 4.

    Common misconception

    The drier the safer.

    Why is it wrong?

    Humidity that is too low makes some materials shrink, crack, and become brittle. A good target is stable around its setpoint.

    Common misconception

    The hygrometer reading is always right.

    Why is it wrong?

    Humidity sensors drift. Electronic data loggers are generally recalibrated once a year, and hygrometers at least every three months.

    Chapter 16 · Buildings & Facilities on ventilation and air conditioning of rooms gives psychrometrics and the ventilation moisture balance, and Chapter 9 · Biology & Microbiology on mold in buildings gives surface humidity and how to clean up mold. Refrigerant dehumidifiers use the cycle in Chapter 25 · Physics on the vapor compression cycle and are subject to the limits of refrigerant work in Chapter 9 · Utilities and Chapter 14. The humidity standard is in Chapter 40 · Buildings & Facilities on indoor air quality, and data loggers in Chapter 12 · Systems, Diagrams & Diagnosis.

    Exercises and worked solutions

    The numbers in the exercises are for practice.

    Try to answer first, then open the worked solution.

    1. A storeroom without air conditioning is at 30 °C and 70 percent relative humidity. What are its vapor pressure, dew point, and vapor density, and does it need dehumidifying?

      Check my answer
      See the worked solution

      The vapor pressure is 0.70×4.24=2.970.70 \times 4.24 = 2.97 kPa, so the dew point is 20+5×(2.97−2.33)/(3.17−2.33)=23.820 + 5 \times (2.97 - 2.33)/(3.17 - 2.33) = 23.8 °C, and the vapor density is 0.70×30.4=21.30.70 \times 30.4 = 21.3 g/m³. A relative humidity of 70 percent is above the NPS limit of 65 percent, so the storeroom needs dehumidifying, and surfaces below 23.8 °C condense water.

    2. Night air is at 25 °C and 90 percent. Can ventilation with that air dry an archive room with a target of 25 °C and 50 percent?

      Check my answer
      See the worked solution

      The vapor pressure of the night air is 0.90×3.17=2.850.90 \times 3.17 = 2.85 kPa, so its dew point is 20+5×(2.85−2.33)/(3.17−2.33)=23.120 + 5 \times (2.85 - 2.33)/(3.17 - 2.33) = 23.1 °C. The indoor target has a vapor pressure of 0.50×3.17=1.590.50 \times 3.17 = 1.59 kPa and a dew point of 10+5×(1.59−1.19)/(1.69−1.19)=14.010 + 5 \times (1.59 - 1.19)/(1.69 - 1.19) = 14.0 °C; because the outdoor dew point is higher, ventilation adds water and does not dry the room.

    3. The moisture load of a storeroom is 25 L/day, and a dehumidifier is labeled 35 pints per day with a factor of 0.9. How many units, and what duty cycle?

      Check my answer
      See the worked solution

      The label capacity is 35×0.473=16.635 \times 0.473 = 16.6 L/day and the capacity in the room is 0.9×16.6=14.90.9 \times 16.6 = 14.9 L/day, so one unit is not enough because 25/14.9=1.6825/14.9 = 1.68. Two units give 29.8 L/day with a duty cycle of 25/29.8=8425/29.8 = 84 percent; that is above the example limit of 80 percent, so the gaps in the room are sealed first or a third unit is prepared.

    4. A film archive room is held at 15 °C. Why can a desiccant dehumidifier be more suitable, and what does its installation require?

      Check my answer
      See the worked solution

      At a low room temperature, the coil of a refrigerant dehumidifier works close to freezing, its capacity falls, and the coil can frost. A desiccant dehumidifier does not need a cold coil, but its hot, humid regeneration air must be discharged through a duct to the outside of the room.

    5. A sealed archive cabinet of 1.2 m by 0.5 m by 2.0 m is given hybrid silica gel. How many kilograms of gel?

      Check my answer
      See the worked solution

      The volume is 1.2×0.5×2.0=1.21.2 \times 0.5 \times 2.0 = 1.2 m³, which is 1.2×35.31=42.41.2 \times 35.31 = 42.4 cubic feet. One quarter to one half pound per cubic foot gives 10.6 to 21.2 pounds, which is 10.6×0.4536=4.810.6 \times 0.4536 = 4.8 to 21.2×0.4536=9.621.2 \times 0.4536 = 9.6 kg. The exact amount depends on how well the cabinet is sealed and on the gel manufacturer’s recommendation, and the gel is placed in containers less than two inches (about 5 cm) thick.

    6. A data logger has a memory of 16,000 pairs of readings. How many days does the memory last at a sampling interval of 15 and 30 minutes, and which suits a year?

      Check my answer
      See the worked solution

      At 15 minutes the memory lasts 16,000×15/1440=166.716{,}000 \times 15/1440 = 166.7 days, and at 30 minutes 16,000×30/1440=33316{,}000 \times 30/1440 = 333 days. The 30-minute interval falls within the 20 to 30 minute range recommended by NPS and almost covers a year, but the data is still downloaded every month when it is reviewed.

    References

    External sources

    • College Physics 2eopenstax.org
    • A Brief Guide to Mold, Moisture and Your Homeepa.gov
    • Moisture Control Guidance for Building Design, Construction and Maintenanceepa.gov
    • NPS Museum Handbook, Part I, Chapter 4: Museum Collections Environmentnps.gov
    • Mold: Prevention Of Growth In Museum Collectionsnps.gov
    • Comparing Temperature and Relative Humidity Dataloggers for Museum Monitoringnps.gov
    • Calibration Of Hygrometers And Hygrothermographsnps.gov
    • Using Silica Gel In Microenvironmentsnps.gov
    • Energy Conservation Program: Test Procedures for Dehumidifiersenergy.gov
    • Laboratory Performance Testing of Residential Dehumidifiersenergy.gov

    Revision history

    DateVersionChange
    November 15, 20261First published

    How to cite

    Kurnia (2026). Humidity control in storerooms and archive rooms: relative humidity and dew point, refrigerant and desiccant dehumidifiers, capacity and condensate disposal, mold, and monitoring. ARSTEMA Academy. Revised November 15, 2026. arstema.com/en/academy/konsep/pengendalian-kelembapan-ruang-gudang-dan-arsip-kelembapan-relatif-dan-titik-embun-dehumidifier-refrigerasi-dan-desikan-kapasitas-dan-buangan-kondensat-kapang-serta-pemantauan

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated
    1

    A storeroom without air conditioning is at 30 °C and 70 percent relative humidity. What are its vapor pressure, dew point, and vapor density, and does it need dehumidifying?

    2

    Night air is at 25 °C and 90 percent. Can ventilation with that air dry an archive room with a target of 25 °C and 50 percent?

    3

    The moisture load of a storeroom is 25 L/day, and a dehumidifier is labeled 35 pints per day with a factor of 0.9. How many units, and what duty cycle?

    Self-assessment progress0%

    Nearby chapters

    NextMembaca kurva pompa dan titik operasi

    Reading order by shelf: Fluids & Thermal · Chapter 26.

    Same disciplinePressure, flow rate, and continuity

    Another chapter in Fluids & Thermal.