    Fluids & Thermal · Chapter 19Applied

    By Kurnia · Published November 10, 2026 · Version 1 · 20 min read

    The carbon footprint of engineering work in hotels and laundries

    emissions from electricity, LPG, and diesel, emission factors, refrigerants and global warming potential, refrigerant leakage, the Kigali Amendment, and calculating emissions

    The management of a hotel with its own laundry asks the chief engineer to prepare a monthly carbon footprint report, and the consultant’s spreadsheet turns out to use an electricity emission factor with no year and to leave out the refrigerant added to the VRF system. This chapter explains carbon dioxide equivalent, emissions from burning LPG and diesel worked out from stoichiometry, electricity emissions and where grid emission factors come from, the global warming potential of refrigerants and the editions of those values, estimating leakage from charging records, the Kigali Amendment and the HFC phase-down schedule for Indonesia, and how to prepare a building emissions report that can be checked. The chapter does not permit refrigerant to be handled by anyone without the required competency.

    Section you’re reading: Chapter opening

    A hotel with its own laundry has been asked by a partner travel agency to send a monthly carbon footprint report. The chief engineer collects the electricity bills, the records of LPG cylinder use for the kitchen and the laundry dryers, the diesel purchases for the generator set, and the air conditioning contractor’s logbook. A spreadsheet from a consultant already exists, but its electricity emission factor names no year and no grid system, its refrigerant global warming potential values name no edition, and the 6 kg of R-410A added to the VRF system over the year is not counted at all. The manager asks which part is largest and which step matters most. The answer is in Example 6.

    Scope

    This chapter covers how to calculate greenhouse gas emissions from the use of electricity, LPG, and diesel and from refrigerant leakage in hotels and laundries. The mechanism of the greenhouse effect and the evidence for climate change are in Chapter 49 · Biology & Microbiology on the greenhouse effect and climate change. The refrigeration cycle is covered in Chapter 25 · Physics, commercial refrigeration in Chapter 9 · Utilities, room air conditioners and the limits of refrigerant work in Chapter 14, heat pumps in Chapter 13, energy efficiency of laundry utilities in Chapter 11 · Utilities, measuring energy savings in Chapter 15 · Data & Measurement, LPG in Chapter 5 · Commercial Kitchens, and the energy of electric heating appliances in Chapter 97 · Electrical & Control. This chapter does not permit anyone without a competency certificate to open, charge, or dispose of refrigerant; the limits of that work follow Chapter 14.

    Carbon footprint and carbon dioxide equivalent

    A building’s carbon footprint is the amount of greenhouse gas emissions caused by the building’s activities over one period, expressed as a mass of carbon dioxide equivalent. There are two kinds of emissions. Direct emissions are released on site, for example from burning LPG in the kitchen and dryers, diesel in the generator set, and refrigerant leaking from air conditioners or refrigerated cabinets. Indirect emissions occur elsewhere because of the building’s activities, for example at the power plants that generate the electricity the building buys.

    Greenhouse gases differ in strength. Global warming potential (GWP) is the ratio of the warming caused by 1 kg of a gas to the warming caused by 1 kg of carbon dioxide over a given time span, usually 100 years. The GWP of carbon dioxide is therefore 1. Carbon dioxide equivalent (CO₂e) is the mass of carbon dioxide that causes the same warming as a given mass of another gas:

    E=A×FE,ECO2e=mgas×GWPE = A \times FE, \qquad E_{\text{CO}_2\text{e}} = m_{\text{gas}} \times \text{GWP}

    where EE is the emission (kg CO₂ or kg CO₂e), AA the activity data such as kWh of electricity, kg of LPG, or liters of diesel, FEFE the emission factor in kg CO₂ per unit of activity, mgasm_{\text{gas}} the mass of gas released to the air (kg), and GWP is dimensionless. An emission factor is the mass of greenhouse gas released per unit of activity. This formula assumes that the emission factor is constant over the period and that the activity data are measured. The result is no more accurate than the activity data and emission factor used, so both are written down together with their source and year.

    Good activity data come from documents that can be checked again: the bills or main meter for electricity, the purchase and weighing records for LPG cylinders, the tank filling records for diesel, and the contractor’s refrigerant logbook. Technicians do not open live panels to read figures; meter readings follow the procedure in Chapter 76 · Electrical & Control on safe work. Missing data are not replaced with guesses but are written up as a gap in the report.

    Emissions from burning LPG and diesel

    Complete combustion converts all the carbon in a fuel into carbon dioxide. The mass of carbon dioxide can therefore be calculated from the balanced reaction equation using stoichiometry. For propane:

    C3H8+5 O2⟶3 CO2+4 H2O\text{C}_3\text{H}_8 + 5\,\text{O}_2 \longrightarrow 3\,\text{CO}_2 + 4\,\text{H}_2\text{O}

    This equation shows that one mole of propane produces three moles of carbon dioxide. With atomic masses of 12.01 for C, 1.008 for H, and 16.00 g/mol for O, the molar mass of propane is 44.09 g/mol and that of carbon dioxide 44.01 g/mol, so each kilogram of propane produces 3×44.01/44.09=2.9943 \times 44.01 / 44.09 = 2.994 kg of carbon dioxide. For butane, 2 C4H10+13 O2⟶8 CO2+10 H2O2\,\text{C}_4\text{H}_{10} + 13\,\text{O}_2 \longrightarrow 8\,\text{CO}_2 + 10\,\text{H}_2\text{O}, so each kilogram of butane produces 4×44.01/58.12=3.0294 \times 44.01 / 58.12 = 3.029 kg of carbon dioxide. LPG is a mixture of propane and butane whose proportions depend on the supplier, so its factor lies between those two figures.

    For fuels without a single composition, such as diesel, the carbon mass fraction is used:

    mCO2=mfuel×wC×44.0112.01m_{\text{CO}_2} = m_{\text{fuel}} \times w_C \times \frac{44.01}{12.01}

    where mfuelm_{\text{fuel}} is the mass of fuel (kg), wCw_C the carbon mass fraction of the fuel (dimensionless), and 44.01/12.01 = 3.66 the ratio of the mass of carbon dioxide to the mass of carbon. This method is the same as calculating carbon dioxide from gasoline whose carbon mass fraction is known. Diesel is bought in liters, so the mass is calculated from the density. The carbon fraction and density of diesel vary with grade and supplier; the official figures are taken from the supplier’s specification or from an official emission factor table.

    The 2006 IPCC Guidelines for national greenhouse gas inventories contain tables of default emission factors for combustion per unit of energy and tables of the net calorific values of fuels. That method is used when what is known is the energy of the fuel, not its composition: the mass is converted to energy with the calorific value, and the energy is then multiplied by the emission factor. The two methods give close figures when the data are consistent.

    The standard enthalpy of combustion is the enthalpy change when one mole of a substance burns completely under standard conditions. For methane it is −890.8 kJ/mol. This figure allows emissions to be compared per unit of heat energy, which is more useful than per kilogram when a technician compares a gas heater with an electric heater, as in Example 4.

    Incomplete combustion produces carbon monoxide and soot. Its mass of carbon dioxide is slightly smaller, but its hazard is far greater. A yellow flame, soot, or a carbon monoxide alarm is a safety matter, not an emissions-reporting matter, and is handled according to Chapter 25 · Laundry on dryer gas burners and Chapter 1 · Commercial Kitchens on gas cooking equipment.

    Emissions from electricity and where emission factors come from

    Electricity gives off no smoke at the hotel, but the power plants that supply it may burn coal, gas, or oil. Electricity emissions are calculated as the kWh purchased multiplied by the grid emission factor. The grid emission factor is the mass of carbon dioxide per MWh of electricity generated in one interconnected system. In Indonesia, the mitigation action methodology of Kementerian ESDM (Ministry of Energy and Mineral Resources) uses a combined margin emission factor in tons of CO₂ per MWh for a given interconnected system, which is calculated and published by Kementerian ESDM.

    Grid emission factors differ from one system to another and change from year to year as the generation mix changes. The latest official value could not be confirmed as of November 2026, so this chapter uses a sample value of 0.80 kg CO₂/kWh. A real report uses the officially published value for the relevant system and year, and states both. Changing the factor from 0.80 to 0.70 kg CO₂/kWh lowers electricity emissions by 12.5 percent without a single kWh being saved, as in Example 3. A report that compares months or years therefore uses the same factor, or separates the change due to the factor from the change due to consumption.

    The choice of equipment also affects emissions. An electric heating element converts almost all of its electricity into heat, as in Chapter 97 · Electrical & Control on electric heating appliances. A heat pump with a COP of 3.5 delivers 3.5 kWh of heat for every kWh of electricity, as in Chapter 13. A gas heater converts most of the fuel energy into heat, and the rest is lost through the flue gas. The comparison is made per kWh of heat that reaches the water, not per kWh of electricity or per kilogram of fuel.

    Refrigerants and global warming potential

    HFC refrigerants are powerful greenhouse gases. The Kigali Amendment sets a GWP value for each HFC controlled under Annex F of the Montreal Protocol, among them 675 for HFC-32, 1,430 for HFC-134a, 3,500 for HFC-125, and 4,470 for HFC-143a. These values are used to calculate HFC consumption in carbon dioxide equivalent under that agreement. A refrigerant blend is a mixture of two or more refrigerants; its GWP is the weighted average according to the mass fraction of each component. R-410A is a mixture of 50 percent by mass HFC-32 and 50 percent by mass HFC-125, so its GWP is 0.5×675+0.5×3500=2087.50.5 \times 675 + 0.5 \times 3500 = 2087.5, rounded to 2,088.

    GWP values depend on which edition of the IPCC assessment reports is used. For HFC-32 the 100-year value is 675 in the Fourth Assessment Report, 677 in the Fifth, and 771 in the Sixth; for HFC-134a the values are 1,430, 1,300, and 1,530 respectively. The values in Annex F of the Montreal Protocol are the same as those of the Fourth Assessment Report. A good emissions report names the edition used and does not mix editions in one table.

    Hydrocarbon refrigerants and some newer refrigerants have much lower GWPs, but they are flammable or mildly flammable. R-32 is classed as mildly flammable, and some small units use flammable hydrocarbons, as in Chapter 14. Changing the refrigerant type in a unit not designed for it is not maintenance work; that decision belongs to the designer, the manufacturer, and a certified technician.

    Refrigerant leakage

    A healthy refrigerant circuit does not lose its charge. If the contractor has to add refrigerant to bring the charge back to the weight specified by the manufacturer, the mass added equals the mass that has leaked to the air since the last charging. This mass balance principle gives the simplest way to estimate leakage emissions:

    mleak≈∑madded,r=mleakmcharge×100%m_{\text{leak}} \approx \sum m_{\text{added}}, \qquad r = \frac{m_{\text{leak}}}{m_{\text{charge}}} \times 100\%

    where maddedm_{\text{added}} is the mass of refrigerant added in one period (kg), mchargem_{\text{charge}} the nominal charge of the system according to the nameplate or installation documents (kg), and rr the leak rate in percent per period. This estimate assumes that each charging brings the charge back to the nominal weight and that every charging is recorded with a scale. Refrigerant that is recovered into a cylinder during repair and then charged back in is not counted as leakage.

    A refrigerant log is a per-unit record that contains the refrigerant type, the nominal charge, the date, the mass added or recovered, leak findings, and the name of the certified technician. Without this record, leakage emissions cannot be calculated and repeated leaks go unseen. Chapter 14 already stresses that adding refrigerant repeatedly without finding and repairing the leak is a mistake, not maintenance. From the carbon footprint side, a few kilograms of high-GWP refrigerant can be equivalent to tons of carbon dioxide, as in Example 5.

    At the end of the equipment’s life, the refrigerant is recovered by a certified technician before the unit is dismantled or discarded. Opening a service valve to the air to “empty” a unit releases the entire charge at once, and with a flammable refrigerant it also creates a fire hazard.

    The Kigali Amendment and Indonesia

    The Montreal Protocol is an international agreement to phase out ozone-depleting substances, including CFCs. The Kigali Amendment of 2016 added HFCs to the list of substances controlled by that agreement, because HFCs do not deplete ozone but are powerful greenhouse gases. The control takes the form of a phased reduction of consumption and production measured in carbon dioxide equivalent, not a direct ban on using equipment that is already installed.

    Indonesia ratified the Kigali Amendment through Peraturan Presiden (Presidential Regulation) No. 129 of 2022 on the ratification of the Kigali Amendment to the Montreal Protocol, which was enacted on November 1, 2022. The amendment entered into force for Indonesia on March 14, 2023, and control began in 2024 by holding HFC consumption at its reference level.

    Indonesia is an Article 5 Group 1 country, with the reduction schedule below. For this group, the consumption baseline is the average HFC consumption from 2020 to 2022 plus 65 percent of the HCFC baseline, calculated in carbon dioxide equivalent. Consumption is frozen in 2024, then reduced by 10 percent in 2029, 30 percent in 2035, 50 percent in 2040, and 80 percent in 2045 relative to the baseline. The details of implementation in Indonesia, such as quotas and import rules, could not be confirmed as of November 2026; check with the ministries responsible for the environment and for trade.

    For hotels and laundries the consequences are practical. The supply of high-GWP HFCs will be increasingly restricted, so systems that keep leaking will become more and more expensive to maintain. Purchases of new equipment consider lower-GWP refrigerants together with safety and the availability of technicians competent for that refrigerant. A repaired leak lowers emissions and the need for charging at the same time.

    Preparing a building emissions report

    An emissions report that can be checked shows each source on one line: the activity data with their unit and source document, the emission factor or GWP with its source, year, and edition, and the result in kg or tons of CO₂e. Totals are added up after all lines are in the same unit. Rounding is done on the final result, not at each step.

    Emission intensity is emissions divided by a measure of activity, for example kg CO₂e per room-night sold for a hotel or per kilogram of linen for a laundry. Intensity allows months to be compared when the number of guests or the amount of laundry changes. More careful normalization for production and weather is covered in Chapter 15 · Data & Measurement, and cost per kilogram of linen in Chapter 22 · Laundry on cost per kg.

    The order of action follows the size of the source, not ease. In many hotels, electricity for chillers, air conditioning, and the laundry is the largest source, so the efficiency projects in Chapter 11 · Utilities and Chapter 13 give the largest reduction. Refrigerant leakage is often small in kWh but large in CO₂e, and repairing it requires no new equipment. Claimed savings must be measured against a baseline as in Chapter 15 · Data & Measurement, not calculated from equipment specifications alone.

    Worked example

    The figures in the examples below are practice figures, unless their source is stated.

    Example 1: kitchen LPG. The kitchen uses 20 LPG cylinders of 50 kg a month. With 2.994 kg CO₂ per kg of propane and 3.029 kg CO₂ per kg of butane, one cylinder of propane gives 50×2.994=149.750 \times 2.994 = 149.7 kg CO₂ and one cylinder of butane 50×3.029=151.4550 \times 3.029 = 151.45 kg. If the LPG is taken to be a mixture of 50 percent by mass propane and 50 percent butane, one cylinder gives an average of 150.6 kg, and 20 cylinders give 20×150.6=3,01220 \times 150.6 = 3{,}012 kg, or about 3.0 tons of CO₂ a month. The difference in LPG composition changes the result by only about 1 percent.

    Example 2: generator set diesel. The generator set uses 400 L of diesel a month. With a density of 0.84 kg/L and a carbon mass fraction of 0.86, the mass of diesel is 400×0.84=336400 \times 0.84 = 336 kg and the mass of carbon 336×0.86=288.96336 \times 0.86 = 288.96 kg. The carbon dioxide formed is 288.96×44.01/12.01=1,059288.96 \times 44.01/12.01 = 1{,}059 kg, or 2.65 kg CO₂ per liter. Diesel consumption is read from the tank filling records, not from the generator set’s running hours multiplied by the catalog consumption.

    Example 3: electricity and the effect of the emission factor. The hotel uses 180,000 kWh a month according to the bill. With a practice factor of 0.80 kg CO₂/kWh, the emissions are 180,000×0.80=144,000180{,}000 \times 0.80 = 144{,}000 kg, or 144 tons of CO₂. If the consultant uses 0.70 kg CO₂/kWh without stating its source, the result is 126 tons, 12.5 percent lower without any savings. A correct report states the factor, the grid system, and its year.

    Example 4: heating water with gas, an element, or a heat pump. From the enthalpy of combustion of methane of −890.8 kJ/mol, combustion produces 44.01 g of CO₂ for every 890.8 kJ, which is 44.01/890.8×3600=17844.01/890.8 \times 3600 = 178 g CO₂ per kWh of fuel energy. A natural gas heater with an efficiency of 85 percent gives 0.178/0.85=0.2090.178/0.85 = 0.209 kg CO₂ per kWh of heat to the water. An electric element with a factor of 0.80 gives 0.80 kg per kWh of heat, and a heat pump with a COP of 3.5 gives 0.80/3.5=0.2290.80/3.5 = 0.229 kg. With these figures, replacing a gas heater with an electric element actually produces almost four times the emissions, while a heat pump comes close to gas; the result changes if the grid factor falls.

    Example 5: VRF leakage. A VRF system holds 40 kg of R-410A, and the logbook shows that 6 kg were added in one year. Its leak rate is 6/40×100%=156/40 \times 100\% = 15 percent per year, and its emissions are 6×2087.5=12,5256 \times 2087.5 = 12{,}525 kg, about 12.5 tons of CO₂e a year or 1,044 kg a month. If the same mass were R-32, the emissions would be 6×675=4,0506 \times 675 = 4{,}050 kg with the Annex F value, or 6×771=4,6266 \times 771 = 4{,}626 kg with the value of the IPCC Sixth Assessment Report. Figures that differ only because of the edition show why the edition must be written down.

    Example 6: the monthly report for the opening case. The monthly sources are LPG 3.01 tons, diesel 1.06 tons, electricity 144 tons, and refrigerant leakage 1.04 tons, so the total is about 149.1 tons of CO₂e. Electricity contributes 144/149.1=96.6144/149.1 = 96.6 percent. With 4,500 room-nights sold, the intensity is 149,100/4,500=33.1149{,}100/4{,}500 = 33.1 kg CO₂e per room-night. The consultant’s spreadsheet needs correcting in three places: the electricity factor is given its source, system, and year; the refrigerant is included with the GWP edition; and the VRF leak is passed to a certified contractor to be found and repaired. The largest reduction comes from the electricity consumption of the chillers, air conditioning, and laundry, while repairing the leak is a cheap step whose effect is seen immediately.

    Stop conditions

    Stop work and hand over to the person named if:

    1. There is a smell of refrigerant, oil is visible at pipe joints, or a unit with flammable refrigerant is suspected of leaking in an enclosed room; keep ignition sources away, open ventilation if it is safe, and a certified refrigeration technician takes over, as in Chapter 14.
    2. A technician without a certificate is asked to open, charge, evacuate, recover, or dispose of refrigerant, including “emptying” a unit through the service valve; refuse, and a certified contractor does the work.
    3. There is a smell of LPG in the kitchen, the cylinder store, or the dryer room; do not switch any switch on or off, close the cylinder valve only if it is safe, keep people away, and follow the emergency response in Chapter 5 · Commercial Kitchens with the occupational safety and health (K3) officer and the fire department.
    4. The burner flame is yellow or sooty, or a carbon monoxide alarm sounds, on a dryer, boiler, or cooking appliance; shut it down according to the procedure, and an authorized gas technician inspects it, as in Chapter 25 · Laundry and Chapter 1 · Commercial Kitchens.
    5. The generator set is being run for a test in a room with inadequate ventilation or with a leaking exhaust duct; stop and hand over to the utilities supervisor.
    6. The kWh data can only be read by opening a live panel; do not open it, use the bill or the main meter, and an authorized electrician installs the measuring instrument, as in Chapter 76 · Electrical & Control.
    7. An emissions report for an outside party or a regulator is required to use an emission factor without a source and year, or a GWP without an edition; stop and hand over to the person responsible for environmental reporting or an authorized consultant.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    Electricity is clean because there is no smoke at the hotel.

    Why is it wrong?

    Its emissions occur at the power plant and are calculated as kWh multiplied by the grid emission factor; in many buildings electricity is in fact the largest source.

    Common misconception

    There are only a few kilograms of refrigerant, so its emissions are small.

    Why is it wrong?

    Each kilogram of R-410A is equivalent to about 2.1 tons of carbon dioxide, so a leak of 6 kg a year is equivalent to more than 12 tons.

    Common misconception

    The GWP of R-32 is definitely 675.

    Why is it wrong?

    The value 675 is the Annex F value of the Montreal Protocol, which is the same as the IPCC Fourth Assessment Report; the Sixth Assessment Report gives 771. The edition is always written down.

    Common misconception

    The Kigali Amendment bans HFCs starting now.

    Why is it wrong?

    The Kigali Amendment reduces HFC consumption and production in stages relative to the baseline up to 2045; installed equipment may still be maintained properly.

    Common misconception

    Replacing a gas heater with an electric element always lowers emissions.

    Why is it wrong?

    With a grid factor of 0.80 kg CO₂/kWh, an electric element produces almost four times the emissions of a gas heater per kWh of heat; a heat pump or a lower grid factor can reverse that result.

    Chapter 49 · Biology & Microbiology explains why greenhouse gases warm the Earth. Chapter 25 · Physics on the vapor compression cycle, Chapter 9 · Utilities on commercial refrigeration, and Chapter 14 on room air conditioners explain the circuits from which refrigerant leaks and the limits of authority for that work. Chapter 13 on heat pumps, Chapter 97 · Electrical & Control on electric heating appliances, Chapter 5 · Commercial Kitchens on LPG, and Chapter 25 · Laundry and Chapter 1 · Commercial Kitchens on gas burners provide the activity data and their safety. Chapter 11 · Utilities on laundry energy efficiency, Chapter 15 · Data & Measurement on measuring energy savings, and Chapter 22 · Laundry on cost per kg translate emissions into projects and indicators.

    Exercises and worked solutions

    Try to answer first, then open the worked solution.

    1. A laundry dryer uses 30 LPG cylinders of 50 kg, taken to be pure propane, in a month. What are its carbon dioxide emissions?

      Check my answer
      See the worked solution

      The mass of propane is 30×50=1,50030 \times 50 = 1{,}500 kg, so the emissions are 1,500×2.994=4,4911{,}500 \times 2.994 = 4{,}491 kg, about 4.5 tons of CO₂. Assuming pure propane gives a close lower bound, because butane raises the factor by only about 1 percent.

    2. The generator set uses 250 L of diesel in a month because of power outages. With the density and carbon fraction of Example 2, what are its emissions?

      Check my answer
      See the worked solution

      The mass of carbon is 250×0.84×0.86=180.6250 \times 0.84 \times 0.86 = 180.6 kg, so the carbon dioxide is 180.6×44.01/12.01=662180.6 \times 44.01/12.01 = 662 kg. This figure uses the practice density and carbon fraction; an official report uses the supplier’s specification or an official emission factor.

    3. A chiller holds 300 kg of HFC-134a with a leak rate of 5 percent per year. What is the CO₂e per year with the Annex F value, and with the value of the IPCC Sixth Assessment Report?

      Check my answer
      See the worked solution

      The leakage is 300×0.05=15300 \times 0.05 = 15 kg a year, equivalent to 15×1430=21,45015 \times 1430 = 21{,}450 kg with the Annex F value, or 15×1530=22,95015 \times 1530 = 22{,}950 kg with the Sixth Assessment Report value. The difference of 1.5 tons is due only to the edition, so the report names the edition used.

    4. The HFC consumption baseline of a Group 1 country is 10 million tons of CO₂e. What are its consumption limits in 2029, 2035, and 2045?

      Check my answer
      See the worked solution

      The limit is 90 percent of the baseline in 2029, which is 9 million tons; 70 percent in 2035, which is 7 million tons; and 20 percent in 2045, which is 2 million tons of CO₂e. The reduction is calculated relative to the baseline, not relative to the previous year’s consumption.

    5. A project to replace lamps and adjust the chiller controls saves 12,000 kWh a month according to measurement. What is the emissions reduction per month and per year with a factor of 0.80 kg CO₂/kWh, and what is the condition for this claim?

      Check my answer
      See the worked solution

      The reduction is 12,000×0.80=9,60012{,}000 \times 0.80 = 9{,}600 kg a month, or 9,600×12=115,2009{,}600 \times 12 = 115{,}200 kg, about 115 tons of CO₂ a year. This claim is valid only if the savings are measured against a normalized baseline as in Chapter 15 · Data & Measurement, and the emission factor used is the same as the factor in the report.

    6. A general technician is asked to “empty” an R-32 split air conditioner holding 1.2 kg by opening the service valve before the unit is discarded. How much CO₂e is released, and what is the correct answer?

      Check my answer
      See the worked solution

      The entire charge is released, which is 1.2×675=8101.2 \times 675 = 810 kg CO₂e, and the mildly flammable R-32 also creates a flame hazard. The correct answer is to refuse, because refrigerant recovery is done by a certified technician with a recovery machine and cylinder before the unit is dismantled.

    References

    External sources

    • OpenStax: Chemistry 2eopenstax.org
    • 2006 IPCC Guidelines for National Greenhouse Gas Inventories, Volume 2: Energy, Chapter 1: Introductionipcc-nggip.iges.or.jp
    • Metodologi Konversi dari Pembangkit Single Cycle menjadi Combined Cyclegatrik.esdm.go.id
    • Annex F: Hydrofluorocarbonsozone.unep.org
    • Global Warming Potential Values (August 2024)ghgprotocol.org
    • The Kigali Amendment to the Montreal Protocol: HFC Phase-downwedocs.unep.org
    • Perpres No. 129 Tahun 2022peraturan.bpk.go.id
    • Indonesia terapkan kebijakan amendemen Kigali mulai 14 Maret 2023bengkulu.antaranews.com

    Revision history

    DateVersionChange
    November 10, 20261First published

    How to cite

    Kurnia (2026). The carbon footprint of engineering work in hotels and laundries: emissions from electricity, LPG, and diesel, emission factors, refrigerants and global warming potential, refrigerant leakage, the Kigali Amendment, and calculating emissions. ARSTEMA Academy. Revised November 10, 2026. arstema.com/en/academy/konsep/jejak-karbon-pekerjaan-teknik-di-hotel-dan-laundry-emisi-dari-listrik-lpg-dan-solar-faktor-emisi-refrigeran-dan-potensi-pemanasan-global-kebocoran-refrigeran-amandemen-kigali-dan-menghitung-emisi

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated
    1

    A laundry dryer uses 30 LPG cylinders of 50 kg, taken to be pure propane, in a month. What are its carbon dioxide emissions?

    2

    The generator set uses 250 L of diesel in a month because of power outages. With the density and carbon fraction of Example 2, what are its emissions?

    3

    A chiller holds 300 kg of HFC-134a with a leak rate of 5 percent per year. What is the CO₂e per year with the Annex F value, and with the value of the IPCC Sixth Assessment Report?

    Self-assessment progress0%