By Kurnia · Published November 15, 2026 · Version 1 · 21 min read
Lithium batteries in buildings
power banks, electric bicycles and scooters, signs of thermal runaway, charging and storage locations, suitable chargers, and incident response
Shortly before midnight, the smoke detector in a hotel’s staff changing room goes off because an employee’s electric bicycle battery, charged through an extension cord beside the lockers, is hissing and smoking. This chapter covers lithium batteries in buildings from the engineering team’s side: why lithium cells can go into thermal runaway, the sources of batteries in a hotel (guests’ power banks, electric bicycles and scooters belonging to staff and guests, devices in the lost-and-found store), calculating battery energy, warning signs before a fire, requirements for charging and storage locations, suitable chargers, damaged batteries and their disposal, and incident response. The provisions come from guidance by the UK Department for Transport, the OPSS statutory guidelines for electric bicycle batteries, OZEV guidance for covered car parks, and a US EPA page, and are presented as data from those countries; as of November 2026, no Indonesian regulation specific to charging electric bicycles in buildings has been found. Incident response is written as moving away, raising the alarm, calling the fire service, and restricting the area; this chapter does not teach how to dismantle, repair, or extinguish batteries.
This material involves real hazards. A concept explanation doesn’t replace site procedures, competency, energy isolation, the latest SDS, or a work permit.
Shortly before midnight, the smoke detector in a hotel’s staff changing room went off. The security officer who arrived first found an electric bicycle battery belonging to a kitchen employee charging on the floor beside the lockers, plugged into an extension cord that also supplied two phone chargers. The battery was hissing, its case was bulging, and white smoke was coming out of the gap in its cover. The security officer pressed the manual call point, cleared the service corridor, closed off access to the room, and waited for the fire service at the service entrance. Nobody was hurt, but smoke entered the corridor that serves as the kitchen’s exit route, and the clothes lockers nearby were scorched.
The next morning the general manager asked the engineering team to draw up rules: where electric bicycles and scooters may be charged, which chargers may be used, and what staff do when a battery starts to smoke. The technician needs to know why lithium batteries catch fire, the warning signs before a fire appears, the requirements for a charging room, and the limits of the job.
Scope
This chapter covers lithium batteries brought into hotels, laundries, kitchens, and hospitals: power banks, laptops, electric bicycles and scooters, and devices in the lost-and-found store. It covers thermal runaway, battery energy, warning signs, charging and storage locations, suitable chargers, damaged batteries, and incident response. The provisions come from UK and US government guidance and are presented as data from those countries. As of November 2026, no Indonesian regulation in the accessible JDIH databases has been found that specifically governs charging and storing electric bicycles or scooters inside buildings.
Topics in other chapters: lithium cells and traction batteries in Chapter 7 · Automotive & Electric Mobility; vehicle battery fires in Chapter 9 · Automotive & Electric Mobility on vehicle high-voltage safety; packs, chargers, and rules for staff charging locations for electric motorcycles in Chapter 17 · Automotive & Electric Mobility; electric car charging in buildings in Chapter 24 · Automotive & Electric Mobility; portable electrical equipment in Chapter 114 · Electrical & Control; fire protection in Chapter 17 · Buildings & Facilities; fire detectors in Chapter 20 · Buildings & Facilities; hazardous (B3) waste in Chapter 35 · Water & Water Treatment; forklift batteries in Chapter 13; and charging stations in hotel parking in the R24 chapter on electric vehicle charging stations (Chapter 120 · Electrical & Control).
This chapter is learning material, not a work instruction. Outside the building technician’s authority: opening, dismantling, repairing, replacing cells in, or modifying batteries and chargers; extinguishing a battery that is smoking or burning; moving a battery that is hot or smoking; setting the outcome of a fire risk assessment; and installing new circuits, outlets, or isolators in the charging room. That work belongs to the fire service, a competent fire risk assessor, the device manufacturer or authorized workshop, and licensed electrical installers. The building technician prepares and inspects the charging location, enforces the charging rules, recognizes warning signs, raises the alarm, restricts the area, and reports.
Why lithium batteries can catch fire on their own
Thermal runaway is the condition in which the temperature of a battery cell reaches a critical point at which the chemical reactions inside it generate heat faster than that heat can be dissipated. The OPSS guidelines for electric bicycle batteries explain the sequence: the reaction produces gas inside the cell, the cell casing ruptures, and flammable and potentially toxic gases are released that can ignite as a fire or an explosion. A cell in this reaction heats the cells next to it, so the reaction can spread through the whole pack and develop rapidly.
The OZEV guidance for covered car parks adds two properties that distinguish a lithium battery fire from an ordinary fire. The electrolyte inside the cell is flammable, and the reactions inside the cell can supply their own oxygen, so the battery provides the fuel, the oxygen, and possibly the heat source as well. The vented gases can appear as a dense white cloud at low level or as a dark cloud, and if they accumulate in an enclosed space at a concentration between their lower and upper explosive limits, they can explode on meeting an ignition source.
As a result, shutting off the air does not stop the reaction, and a battery that appears extinguished can reignite. For electric cars, the OZEV guidance cites studies that recorded 13 percent of vehicles reigniting after being extinguished, and one case 22 hours after the initial fire. That is car data, but the mechanism is the same: cells near a damaged cell heat up and react later.
The triggers of the reaction fall into three groups. Thermal abuse is heat from outside, electrical abuse is overcharging, a short circuit, or an incompatible charger, and mechanical abuse is impact, dropping, or puncture. A good battery is protected by a battery management system (BMS), which is a circuit inside the pack that monitors the voltage of each cell, the pack current, and the cell temperature, then stops charging or discharging before a cell leaves its safe limits. The OPSS guidelines state that electric bicycle batteries in Great Britain must have such protection, including against incompatible chargers; counterfeit or modified batteries do not necessarily have it.
Sources of batteries in a hotel and their energy
In a hotel, lithium batteries come from many directions. Guests bring power banks, laptops, and electric wheelchairs. Employees arrive on electric bicycles or scooters and want to charge them during working hours. Delivery couriers wait in the service lobby, the lost-and-found store holds power banks left behind, and the hotel itself uses lithium batteries in handheld radios and power tools.
The UK Department for Transport guidance for premises managers records electric bicycle and scooter battery fire incidents collected from 38 fire and rescue services: at least 77 in 2020, 159 in 2021, 227 in 2022, and 338 forecast for 2023. The OPSS guidelines record that at least 10 people died in fires started by electric bicycles or scooters in the UK in 2023, with almost 200 fires recorded. According to preliminary information from fire services in the Department for Transport guidance, risk is highest while batteries are charging; electric bicycles from established brands bought as a complete system and used according to instructions are low risk; delivery riders on owner-modified bicycles are high risk; and packs that are damaged, bulging, smelly, or leaking are extremely high risk and should not be permitted in the building.
The first measure of the hazard is the stored energy. A battery label usually states the nominal voltage and the charge capacity, and the energy is calculated with:
where is energy (Wh), is nominal voltage (V), and is charge capacity (Ah). A capacity in mAh is divided by 1,000 to give Ah. This formula gives the nominal energy; the available energy depends on the state of charge and the age of the battery. Energy does not determine whether a battery will catch fire, but it determines the size and duration of the fire, and how many batteries it is reasonable to gather in one room (Examples 1 and 2).
Warning signs before a fire
The UK Department for Transport battery safety guidance for electric bicycle users lists six signs that a battery may be a fire hazard:
| Sign | What the guidance says |
|---|---|
| Heat | it is normal for batteries to get warm when charging or in use, but if one feels extremely hot to the touch, it may be defective and charging is stopped immediately |
| Bulging, lumps, and leaks | a battery bulging or swelling out of shape is a common sign of failure; use is stopped immediately, and the same applies to any lump or leak |
| Noise | failing batteries have been reported to make hissing or cracking sounds |
| Smell | a strong or unusual smell, which could be toxic, can signal that the battery is failing |
| Performance | failure to charge fully, or longer charging times, can signal that the battery is failing |
| Smoke | if the battery or device is smoking, a fire has already started |
These signs are written for electric bicycle batteries, but the mechanism is the same for power banks and phones. In a hotel, the signs are most often seen by people who are not technicians, such as room attendants, laundry staff, or security officers, so the warning signs are taught to every department together with the number to call. Hotel handheld radios or power tools whose batteries run down faster and faster are taken out of use.
Charging and storage locations
The Department for Transport guidance for premises managers makes the fire risk assessment the foundation: in the UK that assessment is a legal duty, a new fire hazard requires the assessment to be reviewed by a competent person, and the manager helps by recording the number and types of electric bicycles and scooters in the building. Its best solution is safe facilities, for example purpose-designed metal lockers for storing and charging batteries, ideally located outside the building. The guidance refers to the London Fire Brigade guidance note and summarizes the following considerations for storage and charging rooms:
- Locate the room so that a fire inside it cannot obstruct the building’s means of escape.
- A ground-level room with direct access from where the fire engine parks is preferred, with information and signs for the fire service.
- If storage or charging takes place in a basement, the existing smoke control system may need upgrading.
- If there is no smoke ventilation, consider an automatically opening vent linked to the room’s detector, and water-based suppression if not already present.
- Provide an alarm that alerts all building occupants, and smoke detectors.
- Provide a means of isolating the room’s electrical supply from outside the room, clearly signed.
- Consider the effect of high-temperature fires on the building structure.
- Fighting lithium fires often requires large amounts of water, so plan for the run-off and containment of firefighting water.
The same guidance adds three considerations from other sources: enough outlets that at full capacity every charger plugs directly into a wall outlet with no extension cord or adapter; the room is not used for other purposes that add risk, such as storing flammable materials; and a separation of at least 45 cm between battery packs on charge, unless fireproof separators are used. Charging lockers, where used, are designed specifically for electric bicycle or scooter batteries, clearly labeled, contain one outlet per locker, and ideally have automatic ventilation to the outside.
The management rules in that guidance: policies against storing electric bicycles and scooters in common areas, stairwells, and escape routes are enforced and monitored; damaged batteries must not be brought in; and non-residential buildings can restrict charging without banning parking, because the range of an electric bicycle is generally enough for a commute. For a hotel, the choice is a dedicated charging room that meets the requirements above, or a ban on charging in the building together with secure bicycle parking. Guest rooms, corridors, changing rooms, linen stores, and spaces under stairs are not charging locations.
Suitable chargers and how to charge
A suitable charger is the charger supplied with the device or a replacement authorized by the manufacturer of the device or its drive system. The UK user guidance asks that only such chargers be used, because battery packs and chargers bought separately cannot be confirmed as compatible and safe to use together, and incompatible pairs carry an extremely high fire risk. The OPSS campaign page states that fire risk increases if products are counterfeit, damaged, non-compliant with safety rules, used with an incompatible charger, or modified with incompatible parts.
How to charge, according to the user guidance:
- Follow the manufacturer’s instructions for storing, charging, and maintaining the battery pack.
- Do not overcharge; unplug the charger once the battery is full.
- If the battery is hot after intensive use, let it cool before charging.
- Charge batteries only while someone is awake and alert, so that a fire can be responded to quickly; do not charge while asleep or while nobody is present.
- Do not cover the charger or battery pack while charging.
- Keep batteries away from extreme temperatures, including direct sunlight when not in use.
- Do not overload outlets or extension cords; extension cords are used uncoiled and rated for the load, especially when several chargers are used at once.
For a hotel, item 4 becomes a time window: charging only while the room is supervised by an attendant on duty nearby, and chargers unplugged before the last attendant leaves (Example 3). Item 7 is tightened by the premises guidance, which asks for enough outlets that extension cords are not needed. The current drawn by a charger is calculated from the input power on its label:
where is current (A), is the charger’s input power (W), and is supply voltage (V). Several electric bicycle chargers draw little current compared with the circuit rating, so the main hazards are extension cords, stacked adapters, and loose, hot outlets (Example 5). Circuit adequacy is assessed by the installer; inspection of charger cords and plugs follows Chapter 114 · Electrical & Control on portable electrical equipment.
Damaged and used batteries, and their disposal
Battery packs can be damaged in use, most often by being dropped or in a crash. The UK user guidance states that damaged batteries can catch fire rapidly and without warning; if damage is suspected, the battery is replaced, not charged, and not used, and used packs are treated with caution because their damage is not necessarily visible. In a hotel, a bicycle or scooter that has just fallen or been hit is not charged in the charging room until an authorized workshop has inspected it.
Disposing of lithium batteries requires a specific method. The UK user guidance forbids putting electric bicycle batteries in household waste or normal recycling because they can start fires in waste trucks and processing facilities, and the manufacturer or importer must offer a free take-back service. The US EPA recommends that each used battery or battery-containing device be placed in its own plastic bag, its terminals covered with non-conductive tape, and its manufacturer contacted if the battery is damaged, because even used batteries can hold enough energy to injure or start fires.
The lost-and-found store applies these precautions to power banks left behind: stored separately, exposed terminals covered, and away from flammable materials. Handing over used batteries as hazardous (B3) waste follows Chapter 35 · Water & Water Treatment, and batteries that are bulging, leaking, or hot are not placed in the collection container with other batteries.
Incident response: move away, raise the alarm, call, restrict the area
The UK user guidance distinguishes two situations. If a battery shows warning signs but is not yet smoking or burning, the charger is switched off and unplugged immediately; if possible, the device is carefully moved outside, away from people and combustible materials; then the manufacturer or retailer is contacted for instructions. If the device starts smoking or catches fire, the alarm is raised, people get out and stay out, and the fire service is called immediately. The OPSS campaign page stresses that people should never try to extinguish lithium battery fires themselves, but leave the area or building as quickly as possible and call the fire service.
That guidance is written for bicycle owners in their own homes. In a hotel, moving a battery that is already hot is not taught as a technician’s step; that decision belongs to the person designated by the emergency response procedure, because a hot battery can go into thermal runaway at any moment. This chapter writes incident response as four actions:
- Move away. People near the battery leave the room and do not go back to fetch belongings. The battery is not touched, not covered with cloth, and not immersed.
- Raise the alarm. The manual call point is pressed if there is smoke or fire, and evacuation follows the hotel’s emergency response plan.
- Call. The fire service is called and told that the source is a lithium battery, the type of device, and the location of the room.
- Restrict the area. Access to the room and the surrounding corridors is closed off, the room door is left closed if it is already closed, and staff wait for the fire service at the designated entrance with a floor plan. If the charging room has a signed isolator outside the room, the person designated by the procedure may switch it off from outside.
A battery that has been extinguished is still treated as a hazard until the fire service declares the incident over, because it can reignite. The engineering team does not clean up or dispose of battery remains; their handling follows the fire service’s directions and Chapter 35 · Water & Water Treatment. Once it is safe, the battery is reported to its manufacturer or retailer, and the incident is recorded so that the risk assessment can be reviewed.
Worked example
The numbers in the examples below are practice numbers unless their origin is stated.
Example 1: energy of a power bank and an electric bicycle pack. A guest’s power bank label reads 20,000 mAh and 3.7 V. Its capacity is Ah, so its energy is Wh. An employee’s electric bicycle pack reads 36 V and 14 Ah, so its energy is Wh, that is times the energy of that power bank. That is why an electric bicycle pack in a changing room is far more dangerous than a power bank on a guest room desk.
Example 2: energy gathered in a bicycle parking room. The staff bicycle parking room holds 12 electric bicycles with 504 Wh packs, so the total energy is Wh, about 6.0 kWh. If 6 packs need charging and the risk assessor limits simultaneous charging to 3 packs, rotations are needed.
Example 3: a supervised charging time window. A 504 Wh pack arrives with 20 percent charge remaining, so the amount to charge is Wh. The charger output is 42 V and 2 A, that is W, so charging takes roughly hours. The last attendant on duty near the charging room leaves at 22:00, so charging must start no later than , about 17:12, and the hotel rule rounds this to 17:00. With a charger efficiency of 0.85, the energy from the grid is Wh. Charging slows near full, so 4.8 hours is the shortest estimate and rounding to 17:00 gives a small margin.
Example 4: number of charging positions with 45 cm spacing. One wall of the charging room is 5.4 m long, and each pack with its charger needs a width of 0.30 m. With 0.45 m between packs on charge, positions need , so , hence 7 positions. Check: m, under 5.4 m. That wall needs 7 outlets, one per position.
Example 5: current of several chargers. Seven chargers are each labeled with an input power of 120 W on a 230 V supply. The current of one charger is A and of seven chargers A. A current that small does not make the breaker operate, even if all seven chargers are plugged into one extension cord with a loose connection. The hazard is controlled by the number of outlets, sound plugs, and a ban on extension cords.
Example 6: reading the incident trend in the UK guidance. Recorded incidents rose from 77 in 2020 to 227 in 2022, that is times in two years. The 2023 forecast of 338 means times the 2022 figure, or more incidents. These are UK data, not the probability of a fire in one hotel, but they show a growing hazard, so the risk assessment is reviewed periodically.
Stop conditions
- A battery or device is smoking, flaming, popping, or venting gas: do not approach, touch, cover, or try to extinguish it; leave the room, press the manual call point, call the fire service, close off access to the area, and hand the response over to the fire service.
- A battery on charge feels extremely hot, is bulging, hissing, cracking, smells unusual, or is leaking, but is not yet smoking: switch off and unplug the charger if the outlet can be reached without touching the battery, keep people and combustible materials away from it, and hand the next decision to the person designated by the hotel’s emergency response procedure. Do not move that battery unless designated by the procedure.
- A battery pack that is cracked, dented, bulging, leaking, or has just been dropped or hit is brought to the charging room: do not charge it or store it inside the building; ask the owner to have it inspected by an authorized workshop and report to the duty manager.
- There is a request to open, repair, replace cells in, fit a speed modifier to, or modify a battery or charger in the hotel workshop: refuse and direct it to the device manufacturer or an authorized workshop.
- A battery is being charged with a charger that is not the original or not authorized by the manufacturer, through stacked extension cords, or in a guest room, changing room, corridor, stairwell, or escape route: stop the charging by unplugging the charger if there are no warning signs, and direct it to the designated charging room.
- A detector, alarm, ventilation, outside isolator, or outlet in the charging room is faulty, or the room is being used to store flammable materials: stop using the room for charging; hand repair of alarms and detectors to the fire system contractor, and electrical repair to a licensed installer.
- After a battery fire: do not re-enter the room, clean up remains, or dispose of the battery until the fire service declares the area safe; battery remains are handled according to their directions and Chapter 35 · Water & Water Treatment on hazardous (B3) waste.
Common misinterpretations
Guess what’s wrong first, then open the explanation.
Common misconception
A battery whose fire has gone out is no longer dangerous.
Why is it wrong?
Cells around the damaged cell can heat up and reignite hours later. The area stays restricted until the fire service declares the incident over.
Common misconception
Any charger will do as long as the plug fits.
Why is it wrong?
A plug that fits does not guarantee that the voltage and current match. Incompatible battery and charger pairs carry an extremely high fire risk; only the original charger or a manufacturer-authorized replacement is used.
Common misconception
The breaker will trip if charging becomes dangerous.
Why is it wrong?
A charger draws little current, and thermal runaway happens inside the battery. A breaker does not see a battery heating up; the people supervising and the detectors do.
Common misconception
If a battery smokes, just douse it or use the nearest extinguisher.
Why is it wrong?
UK guidance forbids people from trying to extinguish lithium battery fires themselves. Fighting them takes large amounts of water and is done by the fire service; the job in the building is to move away, raise the alarm, call, and restrict the area.
Common misconception
A small power bank does not need rules.
Why is it wrong?
Its energy is small compared with an electric bicycle pack, but a bulging power bank in a guest room or the lost-and-found store can still start a fire. The same warning signs and storage practices apply.
Links to other chapters
Chapter 7 · Automotive & Electric Mobility on traction batteries explains lithium cells and state of charge, and Chapter 17 · Automotive & Electric Mobility on electric motorcycle batteries covers staff charging locations for larger vehicles. Vehicle battery fires are in Chapter 9 · Automotive & Electric Mobility, parking with electric car charging points in Chapter 24 · Automotive & Electric Mobility and in the R24 chapter on electric vehicle charging stations (Chapter 120 · Electrical & Control), alarms in Chapter 17 · Buildings & Facilities and Chapter 20 · Buildings & Facilities, chargers and cords in Chapter 114 · Electrical & Control, and used batteries in Chapter 35 · Water & Water Treatment on hazardous (B3) waste.
Exercises and worked solutions
The numbers in the exercises are for practice.
Try to answer first, then open the worked solution.
A guest’s laptop label reads 11.4 V and 5,000 mAh. What is its energy in Wh?
Check my answer
See the worked solution
The capacity is Ah, so the energy is Wh. That is less than the 74 Wh power bank in Example 1, but the warning signs and storage practices are the same.
A room attendant finds a bulging, warm power bank on the desk of an empty guest room. What is done, and what is not done?
Check my answer
See the worked solution
The attendant does not charge, press, or carry the power bank to the store, but leaves and reports to the duty manager or the person designated by the emergency response procedure while keeping people out of the room. If the power bank starts smoking, the alarm is raised and the fire service is called, because bulging is a common sign of battery failure.
An employee asks permission to charge an electric scooter in the changing room because the charging room is full. What is the technician’s answer?
Check my answer
See the worked solution
The request is refused, because the changing room is not a charging location and a fire there can block an exit route, as in the opening case. The scooter is parked in the designated parking without charging, or charged in the next rotation in the charging room, because the journey home is generally possible without charging.
A 48 V 10 Ah scooter pack has 40 percent remaining and is charged with a charger rated at 54.6 V 2 A output. The last attendant on duty leaves at 23:00. When must charging start at the latest?
Check my answer
See the worked solution
The amount to charge is Wh, and the charger output is W, so charging takes about hours. Charging starts no later than about , that is 20:24, and the hotel rule rounds this to 20:00 because charging slows near full.
A charging room wall is 4.0 m, each pack with its charger is 0.35 m wide, and the spacing between packs is 0.45 m. How many charging positions fit?
Check my answer
See the worked solution
The condition is , so , that is 5 positions. The check gives m, and each position still needs its own outlet.
Why does a charging room need an isolator that can be operated from outside the room, even though the charger current is small?
Check my answer
See the worked solution
When a battery is on fire, nobody may enter the room to unplug chargers, while the chargers still switched on keep delivering energy to the batteries next to it. An isolator outside the room lets the designated person or the fire service cut the supply to the whole room without entering, as the UK premises guidance asks.
References
External sources
- E-cycle and e-scooter batteries: managing fire risk for premisesgov.uk
- Battery safety for e-cycle usersgov.uk
- Statutory guidelines on lithium-ion battery safety for e-bikesgov.uk
- Buy Safe, Be Safe: avoid e-bike and e-scooter firesgov.uk
- Covered car parks - fire safety guidance for electric vehiclesassets.publishing.service.gov.uk
- Used Lithium-Ion Batteriesepa.gov
Revision history
| Date | Version | Change |
|---|---|---|
| November 15, 2026 | 1 | First published |
How to cite
Kurnia (2026). Lithium batteries in buildings: power banks, electric bicycles and scooters, signs of thermal runaway, charging and storage locations, suitable chargers, and incident response. ARSTEMA Academy. Revised November 15, 2026. arstema.com/en/academy/konsep/baterai-litium-di-gedung-power-bank-sepeda-dan-skuter-listrik-tanda-thermal-runaway-tempat-pengisian-dan-penyimpanan-alat-pengisi-yang-sesuai-serta-tanggap-kejadian
Self-check · 3 questions
Check your understanding before moving on
Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.
Safety limits still apply. This quiz tests reasoning; it doesn’t authorize mixing, adjusting, dismantling, live measurement, or field action.
A guest’s laptop label reads 11.4 V and 5,000 mAh. What is its energy in Wh?
A room attendant finds a bulging, warm power bank on the desk of an empty guest room. What is done, and what is not done?
An employee asks permission to charge an electric scooter in the changing room because the charging room is full. What is the technician’s answer?
Nearby chapters
Reading order by shelf: Safety · Chapter 18.