    Water & Water Treatment · Chapter 41Applied

    By Kurnia · Published November 14, 2026 · Version 1 · 21 min read

    Hotel whirlpools

    jet pumps and blowers, heaters, strainers, disinfection and pH, Legionella and biofilm, draining and cleaning, and the limits of the work

    After a long weekend, the shared rooftop spa of a resort hotel has cloudy water at 39 °C, free chlorine of 0.8 mg/L at the afternoon reading, pH 7.9, and one cracked suction outlet cover, while the suites below use whirlpool baths that are filled and drained for every guest. This chapter covers two kinds of hotel whirlpool from the building technician’s side: fill-and-drain whirlpool baths and recirculating spas, jet pumps, blowers, heaters, and strainers, turnover time and user load, the hazard of hair and bodies being drawn into suction outlets, temperature and users, disinfection and pH according to the UK HSE, the United States CDC, WHO, and the SPA water annex of Permenkes 2/2023, Legionella, Pseudomonas, and biofilm in jet pipework and air lines, microbiological testing, and draining, cleaning, and remediation. All electrical work near water, opening pumps, blowers, and heaters, replacing suction outlet covers, changing the chemical program, shock disinfection, microbiological sampling, and decisions when there is a case of illness are work for authorized electricians, the spa supplier or contractor, the water treatment provider, the laboratory, and the health office.

    High-risk material

    This material involves real hazards. A concept explanation doesn’t replace site procedures, competency, energy isolation, the latest SDS, or a work permit.

    Section you’re reading: Chapter opening

    A resort hotel on Lombok has a shared spa holding about 4 m³ on its roof terrace and six suites with whirlpool baths. After a long weekend, the morning technician finds the spa water cloudy at 39 °C, and the logbook holds only one reading a day: free chlorine 0.8 mg/L and pH 7.9 the previous afternoon. A guest reports that their child’s long hair was briefly pulled toward the suction outlet grille in the seat, and the technician sees that the grille is cracked. The pool attendant proposes leaving the blower on all night so that the water “stays fresh,” and the jet pipework of the suite whirlpool baths has never been cleaned since opening. Aerosols from warm water, low disinfectant, biofilm in the pipework, and a damaged suction outlet are four different hazards, each with its own owner of the work.

    Scope

    This chapter covers whirlpools in hotels, resorts, and hospital fitness centers from the building technician’s side: types of tub, jet pumps, blowers, heaters, and strainers, the suction outlet hazard, temperature and users, disinfection and pH, Legionella and biofilm, and draining and cleaning. The annex of Permenkes (Minister of Health Regulation) 2/2023 sets environmental health quality standards for SPA water. As of November 2026, the Ministry of Health legal database (JDIH Kemenkes) records Permenkes 2/2023 as no longer in force because it was revoked by Permenkes 3/2026, while Article 99 of Permenkes 3/2026 excepts several of its articles together with the annex from the revocation; check the latest status, and whether it applies to tubs in hotels, with the district or city health office. The practice guidance comes from the UK HSE, the United States CDC, and WHO, and its figures are those institutions’ figures.

    Circulation and filters are in Chapter 29 on swimming pool circulation and filtration, pumps in Chapter 30 on swimming pool circulation pumps, heat pump heaters in Chapter 31, DPD test kits and ORP controllers in Chapter 32 on swimming pool water quality, and chlorine dosing in Chapter 26 on chlorination systems. Pseudomonas folliculitis is in Chapter 21 · Biology & Microbiology on skin infections from spas, Legionella and aerosols in Chapter 38 on fountains and Chapter 28 · Biology & Microbiology on respiratory infections, and RCDs in Chapter 22 · Electrical & Control on RCDs and Chapter 18 · Electrical & Control on RCD testing.

    Work outside the building technician’s authority: all electrical work near water, including opening pumps, blowers, heaters, panels, and junction boxes, and restoring a circuit that trips repeatedly; replacing, removing, or modifying suction outlet covers and grilles; changing the chemical program and carrying out shock disinfection; taking microbiological samples; and decisions when there is a case of illness. That work belongs to authorized electricians, the spa supplier or contractor, the water treatment provider, the laboratory, and the health office. The building technician inspects from outside the water, measures chlorine and pH if trained, records, cleans and drains according to procedure under a work permit after isolation, closes the spa when a stop condition occurs, and reports. Electrical installation requirements specific to spas in Indonesia could not be confirmed from open documents; ask an authorized electrical designer.

    Two kinds of tub: fill-and-drain whirlpools and recirculating spas

    HSE distinguishes the types that are often all called whirlpools. A spa pool is a body of warm, agitated water for sitting or lying in, not for swimming, usually at 30 to 40 °C, filtered and chemically disinfected, with air jets that can produce aerosols, and drained after a number of bathers or a period of time. A hot tub is a factory-built unit for sitting in, holding treated water above 30 °C, without a balance tank, and its water is not changed after every use. A whirlpool bath is a tub for one or two people whose water is not treated and is filled and drained after each use, with water jets and usually an air track in the floor of the tub fed by a blower.

    HSE writes that whirlpool baths have the potential for problems similar to spa pools, namely biofilm in the pipework connected to the water and air jets, and so should be disinfected regularly. Water left in the pipes after draining is still warm water that the next guest meets. A shared spa in a hotel counts as a commercial spa pool according to HSE, with a deck-level overflow, a balance tank, a separate filter, and continuous chemical feed.

    Permenkes 2/2023 defines SPA water as water used for therapy with particular characteristics whose quality can be obtained through treatment or naturally. Whether a particular hotel spa or whirlpool bath counts as SPA water under that regulation is asked of the health office, not guessed.

    Jet pumps, blowers, heaters, and strainers

    In a recirculating spa, water is drawn through the skimmer or overflow channel and the suction outlets in the floor or seat, passes through the prestrainer and filter, receives disinfectant and pH adjustment, is heated, and returns through the inlets. A booster jet is an inlet that blends air and water into a fast, turbulent stream, and an air-blower system delivers air through holes in the floor and seats. HSE writes that blower pipework is difficult to disinfect and can support microbial growth, so it is designed to be demountable, and that the heater and dosing pumps should be interlocked to fail safe if circulation stops.

    Turnover time is the time it takes the entire spa water volume to pass through the filter and treatment and back to the spa. HSE gives a maximum design turnover time of 15 minutes for lower user loads and 6 minutes for commercial spa pools. Its relation to pump flow:

    tturn=VQ×60t_{turn} = \frac{V}{Q} \times 60

    where tturnt_{turn} is the turnover time (min), VV is the spa water volume including the balance tank (m³), and QQ is the circulation flow (m³/h). A lengthening turnover time usually means a dirty prestrainer or filter, not a reason to add more chemicals. HSE asks that sand filters be backwashed before their pressure rises 0.35 bar above the normal clean operating pressure, and that jets and blowers be limited by timers to no more than 15 minutes of continuous operation when the spa is not in use.

    The energy needed to heat the water after refilling is estimated with

    E=m c ΔT3,600,theat=EPE = \frac{m\,c\,\Delta T}{3{,}600}, \qquad t_{heat} = \frac{E}{P}

    where EE is the energy (kWh), mm is the mass of water (kg), cc is the specific heat of water, about 4.19 kJ/(kg·°C), ΔT\Delta T is the temperature rise (°C), theatt_{heat} is the heating time (h), and PP is the heater power (kW). Heat loss is ignored, so the real time is longer (Example 5).

    Suction outlets: hair and bodies drawn in

    HSE writes that there is a risk of suction entanglement and of hair or body parts being trapped in the inlets, outlets, and grilles of a spa, which is controlled through design and clearly displayed information for users. WHO explains the mechanism: an outlet with very strong suction can hold a body part or hair so that the victim’s head is held under water, and most incidents involve people with shoulder-length or longer hair. In the United States, 49 incidents of hair entrapment in hot tubs were recorded from 1990 to 1996, 13 of which ended in drowning.

    Prevention lies in the design. WHO recommends that the velocity of water through outlets not exceed 0.5 m/s, at least two outlets for each suction line, a size and location that cannot be blocked by the body of one person, grille gaps of less than 8 mm, and that pools and hot tubs not be used if any cover is missing, unsecured, or damaged. HSE asks that all suction outlets be duplicated and be of an anti-vortex design. The average velocity through a grille is estimated with

    v=Qn Av = \frac{Q}{n\,A}

    where vv is the velocity through the grille (m/s), QQ is the pump flow (m³/s), nn is the number of open suction outlets, and AA is the open area of one grille (m²). If one outlet is blocked by a body, all the flow moves to the other outlet and its velocity multiplies (Example 3), and a cracked or missing grille exposes the small pipe behind it so that the suction becomes much stronger. The technician never removes, wedges, or bypasses a suction outlet cover, and never runs the pump with a damaged cover.

    Temperature, user load, and rules for users

    WHO writes that high temperatures in hot tubs can cause drowsiness that may lead to unconsciousness or heat stroke and death, and recommends keeping the water below 40 °C. The SPA water annex of Permenkes 2/2023 gives a temperature of less than 40 °C. The heater thermostat and thermal cutout are not set above that limit or bypassed.

    Bather load determines water quality. HSE writes that the number of bathers must not exceed the number of seats, that the design user load per hour is about 10 times the water volume in cubic meters, and that bathers shower before entering, keep their heads above the water, and do not stay immersed for more than 15 minutes at a time. CDC asks that children under five years old not use hot tubs and that pregnant women consult a doctor first. A notice asking for long hair to be tied up is posted together with those rules.

    Disinfection and pH

    Disinfectant in a spa is used up quickly because of temperature, air agitation, and organic matter from bathers. This table summarizes the limits for chlorinated spas; the limits for bromine are in the same documents.

    InstitutionFree chlorinepHTesting frequency
    UK HSE3 to 5 mg/L (DPD1, at pH 7); combined chlorine below 1 mg/L and no more than half the free chlorine7.0 to 7.6commercial spa pools: at opening, then every two hours
    United States CDCat least 3 ppm7.0 to 7.8at least twice a day, hourly during heavy use
    CDC, Legionella module3 to 10 ppm7.2 to 7.8at least twice a day
    WHOhot tubs may need up to 2 to 3 mg/L7.2 to 7.8before opening and during heavy use
    SPA water annex of Permenkes 2/2023minimum 1 mg/L (ordinary SPA), 2 to 3 mg/L (hot SPA); ORP minimum 720 mV with a silver chloride electrode7.2 to 7.8not stated

    The figures differ, so the hotel’s water treatment program sets one limit that is no looser than the rules that apply. According to the HSE action table, pH below 7.0 or above 7.6 means the spa is closed and the acid or alkali dosing units are checked, free chlorine below 1 mg/L or above 10 mg/L means the spa is closed, corrected, and retested, and chlorine of 1 to 2 or 6 to 10 mg/L means the dosing units are checked. CDC advises that cyanuric acid or stabilized chlorine products not be used in hot tubs because they slow disinfection.

    pH determines the disinfecting power of chlorine (Chapter 26 on chlorination systems), and spa pH tends to rise because heating drives off carbon dioxide. Combined chlorine is chlorine that has reacted with organic matter from bathers, such as urine and sweat, and kills germs only slightly; its level is calculated as total chlorine minus free chlorine. HSE asks that chemical dosing be automated for busy spas, with hand dosing only in emergencies or for shock disinfection. The chemicals and doses are set by the water treatment provider.

    Legionella, Pseudomonas, and biofilm

    HSE records a number of outbreaks, including fatalities, linked to spa pools in hotels, holiday homes, and cruise ships, because the water is recirculated, its temperature in part of the system is 20 to 45 °C, and water droplets become aerosols that are inhaled. The risk is higher in people over 45, smokers and heavy drinkers, people with respiratory disease, cancer, diabetes, or heart and kidney disease, and people with weakened immune systems. CDC writes that hot tubs operate at the temperatures most favorable to Legionella, 25 to 45 °C, create aerosols, and accelerate the decay of disinfectants, so additional control measures are needed.

    Pseudomonas aeruginosa causes folliculitis, a red rash in the hair follicles that usually appears about 48 hours after immersion (Chapter 21 · Biology & Microbiology on skin infections from spas), and its presence indicates a treatment failure with likely biofilm on the filter and in other parts of the system. Biofilm is a layer of microbes and slime that sticks to continually moist surfaces. In a spa, it is found in the jet pipework, air lines, filter, overflow channels, and balance tank.

    HSE recommends monthly testing for the colony count, coliforms, E. coli, and P. aeruginosa, and Legionella testing every three months by an accredited laboratory. According to HSE, Legionella below 100 cfu/L means under control, 100 to 1,000 cfu/L means resample and review the controls, and above 1,000 cfu/L means the spa is closed immediately and people are excluded from the spa area. The SPA water annex of Permenkes 2/2023 gives limits for Legionella spp., E. coli, and P. aeruginosa of less than 1 CFU/100 ml each for treated water. The units differ, so results are converted first (Example 6).

    Draining, cleaning, and remediation

    HSE asks that the water of a commercial spa pool be completely replaced at the latest when the number of bathers since the last replacement reaches 100 times the water volume in cubic meters, and that hot tubs used as a business be replaced each week or after each group of users, if earlier. CDC gives the replacement interval in days as the spa volume in gallons divided by 3, then divided by the average number of users per day.

    tHSE=100 VN,tCDC=Vgal/3Nt_{HSE} = \frac{100\,V}{N}, \qquad t_{CDC} = \frac{V_{gal}/3}{N}

    where tHSEt_{HSE} and tCDCt_{CDC} are the replacement intervals (days) according to HSE and CDC, VV is the water volume (m³), VgalV_{gal} is the volume in United States gallons (1 gallon equals 3.785 L), and NN is the average number of users per day. The shorter interval is the one used.

    The HSE schedule for commercial spa pools includes: the waterline cleaned and the strainers and grilles inspected daily, the spa drained and the whole system cleaned daily to weekly according to the risk assessment, the balance tank drained and cleaned at least twice a year, and the air lines cleaned and disinfected every three months. Spa water is emptied to the sanitary sewer and not into the swimming pool. In-room whirlpool baths are drained after every guest and their jet pipework disinfected regularly according to the manufacturer’s instructions and the hotel program, and highly chlorinated water is dechlorinated if the program requires it (Chapter 26 on dechlorination).

    Cleaning is planned work under a work permit (Chapter 76 · Electrical & Control on safe work, LOTO, and work permits): before hands go into a suction outlet, skimmer, prestrainer, or balance tank, the pump, blower, and heater are switched off, locked, and tagged by an authorized person, and the fill water valve and dosing pumps are isolated (Chapter 4 · Safety on non-electrical energy isolation). Cleaning products are used according to their safety data sheets with eye and hand protection (Chapter 6 · Safety on chemicals in technicians’ work). HSE notes that work in and around the balance tank can count as work in a confined space (Chapter 11 · Safety on confined spaces).

    Shock disinfection is temporarily raising the disinfectant level far above the routine level. According to CDC, absent illness, if there are lapses in control measures or routine testing finds Legionella, the hot tub is removed from service, free chlorine is held at 10 ppm for one hour, and then the tub is drained, scrubbed, and rinsed, the filters are cleaned, and it is refilled with fresh potable water. If the health authority suspects illness, samples are taken first according to the authority’s instructions, then the hot tub is drained, scrubbed, the filters are replaced, it is refilled, free chlorine of at least 20 ppm is held for a total of 10 hours, and use resumes in coordination with the health authority. Shock disinfection is carried out by the water treatment provider or trained personnel according to the program.

    Electricity, records, and division of work

    HSE asks that spa systems comply with the UK regulations on electricity at work. For the protection of people, HSE writes that an RCD has a rated tripping current of not more than 30 mA, must never be bypassed, and if it trips this is a sign of a fault, so the system is checked before it is used again. The RCD test button is pressed on schedule by the designated person; all other work on the pump, blower, heater, and lighting circuits is work for an authorized electrician.

    HSE asks that records of monitoring, inspection, and testing be kept for at least five years and show who did the work and when. Permenkes 2/2023 states that internal monitoring of SPA water quality by the operator is carried out at least once a year, except for certain parameters, and that the results are documented and reported to the district or city health office. The daily spa log contains the time, free and total chlorine, pH, temperature, clarity, number of bathers, condition of the grilles, RCD test button checks, draining, and deviations and actions.

    Worked example

    The figures in the examples below are practice figures unless their origin is stated.

    Example 1: turnover time and pump flow. The rooftop spa holds 4.0 m³. For a commercial turnover time of 6 minutes, the flow required is Q=4.0/(6/60)=40Q = 4.0/(6/60) = 40 m³/h. The measured flow is only 28 m³/h, so tturn=4.0/28×60=8.6t_{turn} = 4.0/28 \times 60 = 8.6 minutes, longer than 6 minutes. The design user load according to HSE is about 10×4.0=4010 \times 4.0 = 40 bathers per hour. A flow that does not recover after the prestrainer is cleaned is reported.

    Example 2: when to replace the water. The same spa is used by an average of 60 people per day. According to HSE, the water is replaced after 100×4.0=400100 \times 4.0 = 400 bathers, that is, 400/60=6.7400/60 = 6.7 days. According to the CDC formula, the volume is 4,000/3.785=1,056.84{,}000/3.785 = 1{,}056.8 gallons, so (1,056.8/3)/60=5.9(1{,}056.8/3)/60 = 5.9 days. The shorter interval is used and rounded down, so the water is replaced at least every 5 days.

    Example 3: velocity at the suction outlet grilles. A 28 m³/h pump moves 28/3,600=0.0077828/3{,}600 = 0.00778 m³/s through two grilles, each with an open area of 0.012 m². With both grilles open, v=0.00778/(2×0.012)=0.32v = 0.00778/(2 \times 0.012) = 0.32 m/s, below 0.5 m/s. If one grille is blocked by a back or by hair, v=0.00778/0.012=0.65v = 0.00778/0.012 = 0.65 m/s, that is, twice as much and above 0.5 m/s.

    Example 4: reading the chlorine and pH log. According to the HSE action table: at 08:00, free chlorine 3.8 mg/L and pH 7.4, no action needed; at 12:00, free chlorine 1.6 mg/L, the dosing units are checked; at 16:00, free chlorine 0.8 mg/L and pH 7.9, the spa is closed because chlorine is below 1 mg/L and pH is above 7.6. At 12:00 total chlorine was 2.9 mg/L, so combined chlorine is 2.9−1.6=1.32.9 - 1.6 = 1.3 mg/L, above 1 mg/L and more than half the free chlorine, so the controls are reviewed. A log of one reading a day, as in the opening case, does not catch this decline.

    Example 5: heating after refilling. A 4,000 L (4,000 kg) spa is filled with water at 28 °C and heated to 38 °C, so ΔT=10\Delta T = 10 °C and E=4,000×4.19×10/3,600=46.6E = 4{,}000 \times 4.19 \times 10/3{,}600 = 46.6 kWh. With a 9 kW heater, theat=46.6/9=5.2t_{heat} = 46.6/9 = 5.2 hours without heat loss. That is why draining is scheduled after the last bather.

    Example 6: comparing laboratory results. The laboratory reports Legionella at 300 cfu/L. According to HSE, that figure lies between 100 and 1,000 cfu/L, so the sample is repeated and the controls are reviewed. Because 1 L equals 10 times 100 ml, the figure is equivalent to 300/10=30300/10 = 30 CFU/100 ml, exceeding the Permenkes limit of less than 1 CFU/100 ml. A result of 1,400 cfu/L already exceeds 1,000 cfu/L, so according to HSE the spa is closed immediately and the area is cleared.

    Stop conditions

    1. A suction outlet cover or grille is cracked, missing, loose, or unsecured, or there is a report of hair or a body part being drawn toward a suction outlet: get all bathers out, have the designated person switch the pump off at a panel outside the wet area, close the spa, do not remove, wedge, or bypass the cover, and hand the repair over to the spa supplier or contractor.
    2. The RCD of the spa circuit trips repeatedly, does not trip when its test button is pressed, or someone proposes bypassing it, someone feels tingling in the water, or a pump, blower, socket outlet, or cable is wet: do not touch the water or the equipment, get the bathers out, have the designated person switch the circuit off at a panel outside the wet area, and hand over to an authorized electrician.
    3. The work requires hands or tools to go into a suction outlet, skimmer, prestrainer, or balance tank, while the pump, blower, and heater have not yet been switched off, locked, and tagged by an authorized person: do not start until isolation is confirmed.
    4. Free chlorine is below 1 mg/L or above 10 mg/L, pH is below 7.0 or above 7.6, or outside the limits of the hotel program, the water is cloudy, or there is a strong chemical smell: close the spa, check whether the dosing units are working without changing their settings, and report to the water treatment provider.
    5. A laboratory result shows Legionella above 1,000 cfu/L, P. aeruginosa above 50 cfu/100 ml, or a value beyond the program limits: close the spa immediately, clear the spa area, and hand remediation over to the water treatment provider and management.
    6. Two or more guests have a rash, fever, or pneumonia thought to be linked to the spa, or the health office asks for records: close the spa, do not drain, clean, or disinfect it before samples are taken according to the health office’s instructions, prepare the records, and leave the decision to management and the health office.
    7. The water temperature is above 40 °C, or the heater thermostat or thermal cutout is not working: close the spa, do not reset or bypass the cutout, and call the heater technician or the spa supplier.
    8. Shock disinfection or chemical mixing is requested without a procedure, training, or protective equipment, or the balance tank would have to be entered without a confined space entry permit: postpone it and hand over to the water treatment provider, or stop until the permit is issued.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    An in-room whirlpool bath is safe because its water is always fresh.

    Why is it wrong?

    Fresh water enters jet pipework and air lines that hold biofilm, so HSE asks that the pipework be disinfected regularly.

    Common misconception

    A blower running all the time keeps the water fresher.

    Why is it wrong?

    Air agitation speeds up the loss of disinfectant and increases aerosols. HSE limits jets and blowers with timers when the spa is not in use.

    Common misconception

    A cracked suction outlet grille can still be used as long as guests are careful.

    Why is it wrong?

    A damaged grille concentrates the suction and can hold hair or a body under water. WHO asks that pools and hot tubs not be used if any cover is missing, unsecured, or damaged.

    Common misconception

    Enough chlorine in the morning means enough all day.

    Why is it wrong?

    Spa chlorine drops quickly during heavy use, as in Example 4, so HSE asks for testing at opening and then every two hours for commercial spa pools.

    Common misconception

    If there is a case of illness, the spa must be drained and cleaned at once.

    Why is it wrong?

    CDC asks that samples be taken first according to the health authority’s instructions. Closing the spa is enough; draining before sampling erases the evidence of the source of illness.

    Recirculating spa equipment is the same as swimming pool equipment in Chapter 29 to Chapter 31, and chlorine and pH are measured as in Chapter 32 on swimming pool water quality. Legionella from other water systems is covered in Chapter 38 on fountains, Chapter 10 · Utilities on cooling towers, and Chapter 13 · Buildings & Facilities on building hot water. The spa make-up water meter is read as in Chapter 40 on water meters and the building water balance.

    Exercises and worked solutions

    The figures in the exercises are for practice.

    Try to answer first, then open the worked solution.

    1. A spa holding 2.5 m³ is circulated by a 20 m³/h pump. What is its turnover time, and how does it compare with the HSE limits?

      Check my answer
      See the worked solution

      The turnover time is tturn=2.5/20×60=7.5t_{turn} = 2.5/20 \times 60 = 7.5 minutes, between 6 minutes for commercial spa pools and 15 minutes for lower user loads. For a busy shared spa that flow is too low, so its cause is investigated and reported.

    2. A villa hot tub holding 1,500 L is used by an average of 4 people per day by one family renting it for a week. What is the replacement interval according to the CDC formula, and what does HSE ask for?

      Check my answer
      See the worked solution

      The volume is 1,500/3.785=396.31{,}500/3.785 = 396.3 gallons, so according to CDC (396.3/3)/4=33(396.3/3)/4 = 33 days. HSE asks that business hot tubs have their water replaced each week or after each group of users, if earlier, so that shorter interval is used and the water is replaced after the family leaves.

    3. A child with long hair screams because their hair is pulled toward a spa seat, then comes free. What does the technician do?

      Check my answer
      See the worked solution

      The bathers are taken out, the pump is switched off at the panel by the designated person, and the spa is closed, because the suction outlet cover may be damaged or loose. The cover is inspected from outside the water without removing it, and the repair is handed over to the spa supplier or contractor.

    4. The afternoon reading of a chlorinated spa shows free chlorine of 1.5 mg/L and pH 7.8. What follows according to HSE and according to CDC?

      Check my answer
      See the worked solution

      According to HSE, chlorine of 1.5 mg/L falls in the 1 to 2 mg/L range, so the dosing units are checked, and pH 7.8 is above 7.6, so the spa is closed. According to CDC, chlorine is below the minimum of 3 ppm even though pH is still within 7.0 to 7.8, so both guidelines call for action.

    5. The laboratory reports Legionella at 80 cfu/L. Is it under control according to HSE, and how does it compare with Permenkes?

      Check my answer
      See the worked solution

      The figure is below 100 cfu/L, so according to HSE it is under control, with the controls maintained. In Permenkes units, 80/10=880/10 = 8 CFU/100 ml, above the limit of less than 1 CFU/100 ml, so the result is reported to management and the water treatment provider for a decision under the rules that apply to the hotel.

    6. A 1,500 L hot tub is filled with water at 27 °C and heated to 38 °C with a 3 kW heater. What are the energy and the shortest heating time?

      Check my answer
      See the worked solution

      The energy is E=1,500×4.19×11/3,600=19.2E = 1{,}500 \times 4.19 \times 11/3{,}600 = 19.2 kWh, so theat=19.2/3=6.4t_{heat} = 19.2/3 = 6.4 hours without heat loss. The real time is longer, so filling is scheduled well before the next guests.

    References

    External sources

    • The control of legionella and other infectious agents in spa-pool systems (HSG282)hse.gov.uk
    • Electrical safety and you: A brief guide (INDG231)hse.gov.uk
    • Guidelines for safe recreational water environments. Volume 2: Swimming pools and similar environmentsiris.who.int
    • Operating and Managing Public Pools, Hot Tubs and Splash Padscdc.gov
    • Peraturan Menteri Kesehatan Nomor 2 Tahun 2023 tentang Peraturan Pelaksanaan Peraturan Pemerintah Nomor 66 Tahun 2014 tentang Kesehatan Lingkunganjdih.kemkes.go.id
    • Controlling Legionella in Hot Tubscdc.gov
    • Peraturan Menteri Kesehatan Nomor 3 Tahun 2026 tentang Penanggulangan Penyakitjdih.kemkes.go.id

    Revision history

    DateVersionChange
    November 14, 20261First published

    How to cite

    Kurnia (2026). Hotel whirlpools: jet pumps and blowers, heaters, strainers, disinfection and pH, Legionella and biofilm, draining and cleaning, and the limits of the work. ARSTEMA Academy. Revised November 14, 2026. arstema.com/en/academy/konsep/bak-whirlpool-hotel-pompa-jet-dan-blower-pemanas-saringan-disinfeksi-dan-ph-legionella-dan-biofilm-pengurasan-dan-pembersihan-serta-batas-pekerjaan

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated

    Safety limits still apply. This quiz tests reasoning; it doesn’t authorize mixing, adjusting, dismantling, live measurement, or field action.

    1

    A spa holding 2.5 m³ is circulated by a 20 m³/h pump. What is its turnover time, and how does it compare with the HSE limits?

    2

    A villa hot tub holding 1,500 L is used by an average of 4 people per day by one family renting it for a week. What is the replacement interval according to the CDC formula, and what does HSE ask for?

    3

    A child with long hair screams because their hair is pulled toward a spa seat, then comes free. What does the technician do?

    Self-assessment progress0%