    Water & Water Treatment · Chapter 38Applied

    By Kurnia · Published November 14, 2026 · Version 1 · 18 min read

    Decorative fountains and ornamental pools

    pumps and strainers, water care, Legionella and aerosols, underwater lights and electrical safety, draining and cleaning, and the limits of the work

    The lobby fountain of a hotel is at 31 °C, its walls are slimy, its free chlorine does not register, and the RCD on its lighting circuit has tripped several times, so someone proposes removing it. This chapter covers decorative fountains and ornamental pools from the building technician’s side: the arrangement of pumps, strainers, nozzles, and make-up water, Legionella and aerosols, the factors of sediment and biofilm, temperature, water age, and disinfectant residual, the control limits from the guidance of the United States CDC, underwater lights that heat the water and the electrical hazard near water, draining and cleaning under energy isolation and a work permit, and the water management program and its records. The practice guidance comes from the CDC, WHO, and the UK HSE, because the environmental health quality standards in the annex of Permenkes 2/2023 do not mention decorative fountains. All electrical work in or near the water, opening underwater lights and junction boxes, hyperchlorination, Legionella sampling, and decisions when there is a case of illness are work for authorized electricians, the water treatment provider, the laboratory, and the health office.

    High-risk material

    This material involves real hazards. A concept explanation doesn’t replace site procedures, competency, energy isolation, the latest SDS, or a work permit.

    Section you’re reading: Chapter opening

    Near the lobby fountain of a hotel, elderly guests usually sit while they wait for their cars. On the Monday morning check, the technician finds the water at 31 °C, the basin walls slick with slime, and the test kit showing no free chlorine at all. Four underwater lights run twelve hours every night, their circuit has tripped three times in a week, and a staff member proposes removing its RCD so the lobby is not dark during a weekend event. Warm, slimy water splashing toward where people sit is a Legionella risk, and an RCD that keeps tripping on a circuit of submerged lights is a sign of a fault for an electrician, not a safety device to be removed.

    Scope

    This chapter covers recirculating decorative fountains and ornamental pools in hotels, hospitals, and other buildings from the building technician’s side: pumps, strainers, and make-up water, water care, Legionella and aerosols, underwater lights and the electrical hazard, draining and cleaning, and the water management program. The annex of Permenkes (Minister of Health Regulation) 2/2023 sets environmental health quality standards for swimming pool water, SPA water, and public bathing water, including a Legionella parameter, but does not mention decorative fountains. As of November 2026, the Ministry of Health legal database (JDIH Kemenkes) records Permenkes 2/2023 as no longer in force because it was revoked by Permenkes 3/2026, while Article 99 of Permenkes 3/2026 excepts several of its articles together with the annex from the revocation; check the latest status with the person responsible for the building’s environmental health. This chapter therefore uses the guidance of the United States CDC, WHO, and the UK HSE, and its figures are those institutions’ figures.

    Circulation and filters are covered in Chapter 29 on swimming pool circulation and filtration, pumps and baskets in Chapter 30 on swimming pool circulation pumps, chlorine test kits in Chapter 32 on swimming pool water quality, and chlorine dosing and CT in Chapter 26 on chlorination systems. Legionella in cooling towers is in Chapter 10 · Utilities on cooling water and cooling towers, in hot water in Chapter 13 · Buildings & Facilities on building hot water, and the disease in Chapter 28 · Biology & Microbiology on respiratory infections in hotels and hospitals. RCDs are covered in Chapter 22 · Electrical & Control on RCDs and Chapter 18 · Electrical & Control on grounding tests and RCD testing.

    Work outside the building technician’s authority: all electrical work in or near the water, including opening underwater lights, junction boxes, and the cable connections of submersible pumps, replacing lamps, testing RCDs with a test instrument, and restoring a circuit that trips repeatedly; hyperchlorination and changes to the chemical program; Legionella sampling; and decisions when there is a case of illness. That work belongs to authorized electricians, the water treatment provider, the laboratory, and the health office. The building technician inspects from outside the water, records temperature and free chlorine, cleans strainers and the basin under a work permit after isolation, and reports. Electrical installation requirements specific to fountains could not be confirmed from open documents; ask the electrical designer and an authorized installation inspector.

    Arrangement of the fountain, pump, and strainer

    A decorative fountain is a man-made water feature that recirculates water from a basin through a pump to nozzles, cascades, or water walls, and back to the basin. A submersible pump on the basin floor, or a dry-mounted pump in a plant room, draws water through an intake strainer or basket and pushes it through a filter, if there is one, to the nozzles. A float valve or automatic filler adds make-up water to replace water lost to evaporation and splash, and an overflow pipe and a drain remove the excess and the basin contents.

    The height of a vertical nozzle jet can be estimated from the exit velocity:

    hs=v22g,v=QA,A=πd24h_s = \frac{v^2}{2g}, \qquad v = \frac{Q}{A}, \qquad A = \frac{\pi d^2}{4}

    where hsh_s is the ideal jet height (m), vv the velocity at the nozzle mouth (m/s), gg gravity 9.81 m/s², QQ the flow per nozzle (m³/s), AA the nozzle mouth area (m²), and dd its diameter (m). The real height is lower because of air friction, but the comparison is useful: jet height is proportional to the square of the flow (Example 2). Flow usually drops because the intake strainer is clogged with leaves, hair, and slime, the filter is dirty, or the nozzles are scaled. A falling water level makes a submersible pump run dry; the low-water-level switch that stops the pump is a safety device and is not wedged. Cleaning the strainer of a submersible pump means putting hands into the water, so that job waits for the circuit to be isolated.

    A fountain does not refresh its own water, because new water enters only as make-up water. Evaporating water leaves salts and hardness behind, so dissolved solids concentrate as in the cooling tower of Chapter 10 · Utilities and scale grows on the nozzles. The average water age can be estimated with

    twater≈VQpt_{water} \approx \frac{V}{Q_p}

    where twatert_{water} is the average water age (days), VV the water volume (L), and QpQ_p the make-up water rate (L/day), assuming the make-up water mixes evenly and the basin is not drained.

    Legionella and aerosols

    Legionella is a waterborne bacterium that causes Legionnaires’ disease, the pneumonia covered in Chapter 28 · Biology & Microbiology. People are infected by inhaling contaminated water droplets. WHO writes that an infected source, for example a fountain, can disseminate water droplets referred to as aerosols; most of the water in the droplets evaporates quickly and leaves particles that can be inhaled, and particles below 5 µm can enter deep into the airways. WHO also lists ornamental fountains among the sources of Legionella to be investigated in hotels.

    The CDC states that all decorative fountains produce aerosols, and asks that decorative fountains not be placed or operated in areas used by people at increased risk of Legionnaires’ disease, such as healthcare facilities. People at increased risk according to the CDC include people aged 50 years or older, current or former smokers, people with chronic lung disease, people with weak immune systems, people with cancer, and people with diabetes, kidney failure, or liver failure. The elderly guests in the opening case belong to that group, and in hospitals the placement of a fountain is decided by management and the infection prevention team.

    Its growth depends on temperature. WHO writes that L. pneumophila does not multiply below 20 °C and survives and multiplies at 25 to 45 °C, so cold water is recommended below 25 °C, ideally below 20 °C. The HSE classifies fountains and decorative water features as other risk systems, and names a temperature of 20 to 45 °C as one risk factor, together with water that is stored or recirculated, deposits and nutrient-providing materials such as rust, scale, sludge, and biofilm, a means of creating breathable droplets, and susceptible people who may be exposed. A fountain meets almost all of those factors. Biofilm is a layer of germs and the slime they secrete, which sticks to continually moist surfaces and gives Legionella a nutrient-rich place to grow. The slime on the basin walls in the opening case is biofilm.

    Water care and control limits

    The CDC summarizes four key factors for Legionella growth in decorative fountains: sediment and biofilm, temperature, water age, and disinfectant residual. Water age is the time water takes to reach a point of use or device from its point of entry, and disinfectant residual is the amount of disinfectant still available in the water to kill bacteria. The CDC recommendations by fountain volume in US gallons:

    FactorLess than 5 gallons5 to 25 gallonsMore than 25 gallons
    Sediment and biofilm: cleaning frequencyweeklymonthlyroutinely as indicated by water quality measurements
    Temperature: control limitwater below 25 °Cwater below 25 °Cwater below 25 °C
    Water ageavoid idle water; run at least dailysamesame
    Disinfectant residual: control limit3 to 5 ppm free chlorine for at least 1 hour per day3 to 5 ppm free chlorine for at least 1 hour per day0.5 ppm free chlorine for at least 6 hours per day

    One US gallon equals 3.785 L, so the 5 and 25 gallon limits correspond to 18.9 L and 94.6 L; for dilute water, 1 ppm of free chlorine corresponds to 1 mg/L. The basin is also cleaned whenever biofilm or debris is visible. The CDC also asks that temperature and disinfectant residual be monitored at least weekly, that disinfectant feed be automated if possible, that algaecide be applied as needed, and that the fountain be cleaned and disinfected immediately if algae, biofilm, cloudy water, foul odor, or visible debris is present. Weekly is the least frequent limit.

    The temperature limit below 25 °C is hard to meet in Indonesia, because the air in open lobbies and courtyards, and even the cold water supply, is often warmer. The CDC writes that warm air, heat-generating submerged lights, or other factors that raise the water temperature into the 25 to 45 °C range will require additional mitigation strategies. In such a climate, disinfectant residual, cleaning, and flow become the main barriers, and additional measures such as lights that do not heat the water, shading, or more frequent draining are set by the water management program team. Chemical doses and how they are applied are set by the water treatment provider, not by this chapter.

    Underwater lights and electrical safety

    Underwater lights bring two hazards: they heat the water, and they place electrical equipment in water that people can touch. The CDC notes that decorative fountains with submerged lighting may contain areas where cold water is heated to temperatures that allow Legionella to grow. In an example in the CDC water management program toolkit, biofilm grew repeatedly on the basin wall near incandescent lighting and decreased after the lamps were replaced with LEDs, so the program was amended to specify only LED lamps. The heat from the lights can be estimated as an upper bound:

    ΔTmax=P tm c\Delta T_{max} = \frac{P\,t}{m\,c}

    where ΔTmax\Delta T_{max} is the largest temperature rise (°C), PP the lamp power (W), tt the time switched on (s), mm the mass of water (kg), and cc the specific heat of water, about 4,190 J/(kg·°C). All the lamp heat is assumed to enter the water with none lost to the air, so the real rise is smaller; the purpose is to compare lamp choices (Example 4).

    The HSE writes that the risk of electrical injury is greatest in harsh conditions, for example in wet surroundings, because unsuitable equipment can easily become live and can make its surroundings live. At a fountain, those surroundings are water that people touch. The protection is designed in layers by the electrical designer: equipment suitable for submersion, a supply voltage suitable for the location, grounding and equipotential bonding (Chapter 29 · Electrical & Control on grounding, protective conductors, and equipotential bonding), and RCDs. The HSE writes that RCDs for protecting people have a rated tripping current of not more than 30 mA, must never be bypassed, and when they trip indicate a fault, so the system is checked before it is used again, and that the test button is used regularly.

    For the building technician this means three habits. First, inspecting from outside the water without touching the water or opening anything: cracked or fogged lamp lenses, bubbles from a lamp housing, scuffed cables, open junction box lids, and water inside a box. Second, the RCD test button is pressed on schedule by the designated person and the result is recorded; an RCD that does not trip when tested, or that trips repeatedly, is reported and its circuit is left off until an authorized electrician has examined it (Chapter 37 · Electrical & Control on wet rooms and special locations covers other wet locations). Third, no hands, tools, or bodies go into the water until every circuit of the fountain has been isolated and locked by an authorized electrician.

    Draining and cleaning

    Draining and cleaning are planned work under a work permit (Chapter 76 · Electrical & Control on safe work, LOTO, and work permits), with isolation of three energy sources. The circuits of the pump, lights, and other equipment are switched off, locked, tagged, and proven dead by an authorized electrician. The make-up water valve and automatic filler are closed and tagged, as in non-electrical energy isolation in Chapter 4 · Safety. The chemical dosing pump is stopped and its line isolated. The area is cordoned off and slippery floors are marked.

    Scrubbing the walls raises splashes, and pressure spraying raises aerosols from the biofilm. Workers wear suitable respiratory and eye protection, pressure spraying is used only when the procedure allows it, and other people are kept away (Chapter 10 · Biology & Microbiology on bioaerosols and Chapter 5 · Safety on personal protective equipment). Cleaning agents are used according to their safety data sheets (Chapter 6 · Safety on chemicals in technician work). In a corrective action example in the CDC toolkit, the worker who finds slime immediately shuts off the fountain, drains it to the sanitary sewer, scrubs it with a detergent recommended by the manufacturer, refills it, checks the disinfectant residual, records it, and informs the supervisor. Freshly hyperchlorinated water is not discharged to a storm drain or garden without dechlorination (Chapter 26 on chlorination systems). An underground balance tank or a cramped pump room may count as a confined space that requires an entry permit (Chapter 11 · Safety on confined spaces).

    Hyperchlorination is raising free chlorine far above the routine level for a limited time. The CDC uses it in two remediations. When there is no illness but control measures are ineffective or routine test results are poor, the fountain is removed from service, hyperchlorinated at 10 ppm free chlorine for one hour, drained, scrubbed, its filters cleaned, refilled with fresh potable water, and returned to the routine disinfectant residual before use. When the health authority suspects an outbreak or illness, testing is done together with that authority before and after remediation; the fountain is drained, scrubbed, its filters or filter media replaced, repaired, refilled, hyperchlorinated with a minimum of 20 ppm free chlorine for 10 hours, then drained, rinsed, and refilled with fresh potable water. Hyperchlorination is carried out by the water treatment provider or trained personnel according to the program.

    That sequence differs from the “drain it now” reaction when there is a case. WHO writes that in an outbreak investigation, potential sources are sampled before any precautionary disinfection, and that a fountain can be made safe simply by switching it off until sampling and disinfection are complete. Draining before samples are taken erases the evidence needed to find the source.

    Water management program, records, and the limits of the work

    A water management program is a written plan to identify where Legionella can grow and spread in a building and to reduce that risk. The CDC sets it out in seven steps: establish a team, describe the water systems with text and flow diagrams, identify where Legionella could grow and spread, decide on control points and how to monitor them, establish actions for when control limits are not met, make sure the program is running and effective, and document and communicate all the activities. The program is reviewed at least once a year, and also when control measures are persistently outside their limits, when there is a major change in equipment or water use such as a hotel’s high and low season, or when cases of disease are thought to be associated.

    In the United Kingdom, the HSE’s L8 requires employers and those in control of premises to identify and assess sources of risk, prepare a written scheme where appropriate, implement and monitor precautions, keep records, and appoint a competent person with sufficient authority and knowledge of the installation; records of monitoring, inspections, and tests with their dates are kept for at least five years. That is a UK rule, but it suits good practice in hotels and hospitals.

    The fountain record contains the date and time, water temperature, free chlorine, the condition of the water and strainer, water level, the RCD test button result, cleaning, and deviations with the actions taken. The division of work follows the Scope: the building technician measures, records, cleans under a work permit, and reports; the authorized electrician works on circuits, lights, junction boxes, and submersible pumps; the water treatment provider sets the chemicals; the laboratory tests samples; the health office assesses cases; and management decides placement and operating hours.

    Worked example

    The figures in the examples below are practice figures unless their origin is stated.

    Example 1: volume and CDC category. A lobby basin 2.4 m by 1.0 m with an average water depth of 0.25 m holds 2.4×1.0×0.25=0.62.4 \times 1.0 \times 0.25 = 0.6 m³, or 600 L. In US gallons, 600/3.785=158.5600/3.785 = 158.5 gallons, far above 25 gallons. Its limit is 0.5 ppm free chlorine for at least 6 hours per day, and its cleaning follows water quality measurements. A tabletop fountain at reception holds 12 L, or 12/3.785=3.1712/3.785 = 3.17 gallons, less than 5 gallons, so it is cleaned weekly with 3 to 5 ppm free chlorine for at least 1 hour per day.

    Example 2: jet height and a clogged strainer. A nozzle with an 8 mm mouth and a flow of 0.3 L/s has an area A=π×0.0042=5.03×10−5A = \pi \times 0.004^2 = 5.03 \times 10^{-5} m², so v=0.0003/(5.03×10−5)=5.96v = 0.0003/(5.03 \times 10^{-5}) = 5.96 m/s and the ideal jet height is hs=5.962/(2×9.81)=1.81h_s = 5.96^2/(2 \times 9.81) = 1.81 m. A clogged intake strainer lowers the flow by 20 percent to 0.24 L/s, so v=0.8×5.96=4.77v = 0.8 \times 5.96 = 4.77 m/s and hs=4.772/19.62=1.16h_s = 4.77^2/19.62 = 1.16 m, which is 0.82=0.640.8^2 = 0.64 times the original height.

    Example 3: evaporation, water age, and concentration. The basin of Example 1 has a surface of 2.4×1.0=2.42.4 \times 1.0 = 2.4 m², and its water level drops 8 mm per day from evaporation and splash, so the make-up water is 2.4×0.008=0.01922.4 \times 0.008 = 0.0192 m³, or 19.2 L per day. The average water age is twater≈600/19.2=31.3t_{water} \approx 600/19.2 = 31.3 days. If all of that loss is evaporation and the basin is not drained, after 14 days the dissolved solids become 1+14×19.2/600=1.451 + 14 \times 19.2/600 = 1.45 times the level in the supply water. What refreshes the water is scheduled draining.

    Example 4: heat from underwater lights. Four 50 W incandescent lamps, or 200 W, run for 12 hours, or 43,200 s, in 600 L (600 kg) of water. The largest temperature rise is ΔTmax=200×43,200/(600×4,190)=3.4\Delta T_{max} = 200 \times 43{,}200/(600 \times 4{,}190) = 3.4 °C per night. Four 9 W LED lamps, or 36 W, give at most 36×43,200/(600×4,190)=0.636 \times 43{,}200/(600 \times 4{,}190) = 0.6 °C. Morning water at 27 °C can rise to about 30 °C with incandescent lamps; replacing the lamps is done by an authorized electrician.

    Example 5: reading the weekly record. For the 600 L basin, the limits are 0.5 ppm free chlorine for at least 6 hours per day and a temperature below 25 °C. The four-week record: free chlorine 0.8, 0.6, 0.3, and 0 ppm, and temperatures 27, 28, 29, and 31 °C. Two of the four chlorine readings are below the limit, that is 2/4=502/4 = 50 percent, and every temperature reading exceeds the limit by 27−25=227 - 25 = 2 °C to 31−25=631 - 25 = 6 °C. The fourth week, with zero chlorine and slime, requires immediate cleaning and disinfection, and the steadily rising temperature is reported to the program team for additional measures.

    Example 6: two levels of hyperchlorination. The product of concentration and time, like CT in Chapter 26 on chlorination systems, compares the two CDC procedures. Remediation without illness uses 10×60=60010 \times 60 = 600 ppm·minutes, while remediation when illness is suspected uses at least 20×600=12,00020 \times 600 = 12{,}000 ppm·minutes, which is 12,000/600=2012{,}000/600 = 20 times larger. The routine limit for a large basin, 0.5 ppm for 6 hours, corresponds to 0.5×360=1800.5 \times 360 = 180 ppm·minutes per day. The second procedure starts only after samples have been taken together with the health office.

    Stop conditions

    1. The RCD of a fountain circuit trips repeatedly, does not trip when its test button is pressed, or someone proposes bypassing or removing the RCD: do not restore the circuit and do not bypass the protection; leave the circuit off and call an authorized electrician.
    2. An underwater lamp lens is cracked, there is water in a junction box, a cable is damaged, or someone feels tingling when touching the water: do not touch the water, keep people away from the basin, have the designated person switch the circuit off at a panel outside the wet area, and hand over to an authorized electrician.
    3. The work would require hands, tools, or a body to go into the water, for example to clean the strainer of a submersible pump, while the circuit has not yet been isolated and locked by an authorized electrician: do not enter the water until isolation is confirmed.
    4. The water is cloudy, smells foul, has algae or slime, has visible debris, or has free chlorine below the control limit: stop the fountain, clean and disinfect it according to the water management program, and report to the program team if it recurs.
    5. There is a case of pneumonia or Legionnaires’ disease thought to be linked to the building, or the health office asks for records: switch the fountain off, do not drain, clean, or disinfect it before samples are taken, prepare the records, and leave the decision to management and the health office.
    6. A fountain is operating in an area for people at increased risk, such as a hospital patient waiting room: report to management and the infection prevention and control team for a decision on its placement.
    7. Hyperchlorination or chemical feeding is requested without a procedure, training, or suitable protective equipment: postpone it and hand over to the water treatment provider.
    8. Pressure-spray cleaning is about to be done with people nearby or without respiratory protection, or an underground balance tank would have to be entered without a confined space entry permit: stop until the area is cordoned off, protection is available, and the permit is issued.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    A fountain is only decoration, so there is no aerosol.

    Why is it wrong?

    The CDC states that all decorative fountains produce aerosols. The evaporating droplets leave particles that people nearby can inhale.

    Common misconception

    Water that keeps moving cannot grow bacteria.

    Why is it wrong?

    The pump recirculates the same water, and biofilm grows on continually moist surfaces. The water is refreshed mainly by draining.

    Common misconception

    Clear water means safe water.

    Why is it wrong?

    Legionella cannot be seen. Cloudy water and slime are warning signs, but clear water still needs its free chlorine and temperature measured.

    Common misconception

    An RCD that trips often can be removed for a while to keep the lights on.

    Why is it wrong?

    A tripping RCD indicates a fault that can make the water live. The circuit is left off until an authorized electrician finds the cause.

    Common misconception

    If there is a case, the fountain must be drained and chlorinated at once.

    Why is it wrong?

    WHO and the CDC ask for samples to be taken first, together with the health authority. Switching the fountain off is enough; draining before sampling erases the evidence of the source.

    The equipment of a large fountain is the same as that of the swimming pools in Chapter 29 and Chapter 30, and its free chlorine is measured as in Chapter 32. Legionella in other systems is covered in Chapter 10 · Utilities on cooling towers and Chapter 13 · Buildings & Facilities on building hot water, and the bacterium in Chapter 14 · Biology & Microbiology on bacterial diversity. Irrigation, another aerosol source in hotel grounds, is covered in Chapter 37 on hotel garden irrigation.

    Exercises and worked solutions

    The figures in the exercises are for practice.

    Try to answer first, then open the worked solution.

    1. A wall fountain in a hospital café holds 80 L. Which CDC category does it fall in, and what is questioned before its maintenance is discussed?

      Check my answer
      See the worked solution

      It holds 80/3.785=21.180/3.785 = 21.1 gallons, in the 5 to 25 gallon category, so it is cleaned monthly with 3 to 5 ppm free chlorine for at least 1 hour per day. However, the CDC asks that decorative fountains not be operated in healthcare facilities, so the first question is its placement, which is decided by management and the infection prevention team.

    2. The jet height of a nozzle drops from 1.8 m to 1.2 m in a month. What is the estimated drop in flow, and what is checked?

      Check my answer
      See the worked solution

      Jet height is proportional to the square of the flow, so the flow is roughly 1.2/1.8=0.82\sqrt{1.2/1.8} = 0.82 times the original, a drop of about 18 percent. The intake strainer, filter, and nozzles are checked, and the strainer of a submersible pump is cleaned only after its circuit has been isolated and locked by an authorized electrician.

    3. A guest feels tingling when touching the water of an ornamental pool on the terrace. What does the technician do?

      Check my answer
      See the worked solution

      The technician does not touch the water, keeps people away from the pool, and has the designated person switch the circuit off at a panel outside the wet area. Tingling means the water may be live, so the pool is not used until an authorized electrician declares it safe.

    4. Two 75 W halogen lamps run for 10 hours in a basin holding 400 L. What is the largest temperature rise per night, and why is the real figure smaller?

      Check my answer
      See the worked solution

      The largest rise is 150×36,000/(400×4,190)=3.2150 \times 36{,}000/(400 \times 4{,}190) = 3.2 °C per night. The real figure is smaller because some heat is lost to the air and the basin walls, but this upper bound is enough to show that hot lamps push the water into the growth range of Legionella.

    5. The health office reports two hotel guests with Legionnaires’ disease. The manager wants the lobby fountain drained and cleaned that same night. What is the technician’s answer?

      Check my answer
      See the worked solution

      The fountain is switched off, but it is not drained, cleaned, or disinfected before samples are taken together with the health office, because draining erases the evidence of the source. The technician prepares the records of temperature, free chlorine, and cleaning, while remediation, including hyperchlorination at a minimum of 20 ppm for 10 hours according to the CDC, is decided together with the health authority.

    6. An ornamental pool with a surface of 3 m² holding 900 L loses 10 mm of water level per day. What is the make-up water per day, the average water age, and the concentration of dissolved solids after 10 days without draining?

      Check my answer
      See the worked solution

      The make-up water is 3×0.010=0.033 \times 0.010 = 0.03 m³, or 30 L per day, so the average water age is 900/30=30900/30 = 30 days. After 10 days the dissolved solids become 1+10×30/900=1.331 + 10 \times 30/900 = 1.33 times the level in the supply water if all of the loss is evaporation, so scheduled draining is needed to refresh the water.

    References

    External sources

    • Controlling Legionella in Decorative Fountainscdc.gov
    • Toolkit for Controlling Legionella in Common Sources of Exposure (Legionella Control Toolkit)cdc.gov
    • Developing a Water Management Program to Reduce Legionella Growth & Spread in Buildingscdc.gov
    • Legionella and the prevention of legionellosisiris.who.int
    • Legionnaires' disease. The control of legionella bacteria in water systems. Approved Code of Practice and guidance on regulations (L8)hse.gov.uk
    • Legionnaires' disease: Technical guidance. Part 3: The control of legionella bacteria in other risk systems (HSG274 Part 3)hse.gov.uk
    • Electrical safety and you: A brief guide (INDG231)hse.gov.uk
    • Peraturan Menteri Kesehatan Nomor 2 Tahun 2023 tentang Peraturan Pelaksanaan Peraturan Pemerintah Nomor 66 Tahun 2014 tentang Kesehatan Lingkunganjdih.kemkes.go.id
    • Peraturan Menteri Kesehatan Nomor 3 Tahun 2026 tentang Penanggulangan Penyakitjdih.kemkes.go.id

    Revision history

    DateVersionChange
    November 14, 20261First published

    How to cite

    Kurnia (2026). Decorative fountains and ornamental pools: pumps and strainers, water care, Legionella and aerosols, underwater lights and electrical safety, draining and cleaning, and the limits of the work. ARSTEMA Academy. Revised November 14, 2026. arstema.com/en/academy/konsep/air-mancur-dan-kolam-hias-pompa-dan-saringan-perawatan-air-legionella-dan-aerosol-lampu-bawah-air-dan-keselamatan-listrik-pengurasan-dan-pembersihan-serta-batas-pekerjaan

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated

    Safety limits still apply. This quiz tests reasoning; it doesn’t authorize mixing, adjusting, dismantling, live measurement, or field action.

    1

    A wall fountain in a hospital café holds 80 L. Which CDC category does it fall in, and what is questioned before its maintenance is discussed?

    2

    The jet height of a nozzle drops from 1.8 m to 1.2 m in a month. What is the estimated drop in flow, and what is checked?

    3

    A guest feels tingling when touching the water of an ornamental pool on the terrace. What does the technician do?

    Self-assessment progress0%