    Water & Water Treatment · Chapter 40Quantitative

    By Kurnia · Published November 14, 2026 · Version 1 · 19 min read

    Water meters and the building water balance

    meter types, reading and recording, submeters, non-revenue water, finding hidden leaks, and calculating the balance

    A 180-room hotel receives water from the municipal water utility (PDAM) and a drilled well, has submeters for the laundry, kitchen, cooling tower, pool, and irrigation, yet 14 percent of the water coming in cannot be explained, and the main meter keeps turning at two in the morning. This chapter covers water meters from the building technician’s side: meter types and their accuracy at low flow, how to read the register and calculate consumption, including when the digits roll over to zero, recording at fixed times, installing and using submeters, building a water balance with the 10 percent unaccounted-water threshold from the United States EPA WaterSense guidance, the terms non-revenue water, real losses, and apparent losses from the standard IWA and AWWA terminology, and finding hidden leaks with night readings, the toilet tank dye test, and daily walk-throughs. The PDAM meter, its seal, and the pipe before the meter belong to the PDAM; opening up concealed pipes, installing submeters, and closing valves that supply the fire protection system are work for plumbers, contractors, and the designated staff.

    Section you’re reading: Chapter opening

    The water bill of a 180-room hotel in Bandung rose by about a fifth in two months, even though occupancy fell. The hotel receives water from the PDAM (the municipal water utility) and from its own metered drilled well, and the technicians have long recorded submeters for the laundry, kitchen, cooling tower, pool and spa, and garden irrigation. When all of that month’s figures were added together with the estimated use in guest rooms, about 14 percent of the water coming in could not be explained. The following night, at 01:00 and 03:00, the main meter was read twice, and its reading kept moving even though the laundry and kitchen had stopped. The technician needs to know whether the difference is a leak, legitimate night use, or a reading error, and how much water is lost each year.

    Scope

    This chapter covers water meters and the building water balance from the technician’s side: meter types and their accuracy, reading and recording, submeters, the water balance, the term non-revenue water, and ways to find leaks that cannot be seen. The practice is based on the WaterSense guidance of the United States EPA for commercial and institutional facilities and on the standard IWA and AWWA water audit terminology used by EPA, so the thresholds in this chapter are those institutions’ figures. As of November 2026, the rules for verification and periodic reverification of water meters in Indonesia could not be confirmed from open documents; ask the PDAM and the regional legal metrology unit before questioning the accuracy of a PDAM meter.

    The basic night meter test, zone isolation, and plumbing leak repair are covered in Chapter 15 · Buildings & Facilities on plumbing maintenance and diagnosis, the principles and installation of flow-measuring devices in Chapter 5 · Fluids & Thermal on flow measurement, the PDAM connection, roof tanks, and booster pumps in Chapter 5 · Buildings & Facilities on building water supply systems, daily water demand in Chapter 8 · Buildings & Facilities, and energy submeters, baselines, and normalization in Chapter 34 · Buildings & Facilities on building energy dashboards. Cooling tower make-up water is in Chapter 10 · Utilities, pools in Chapter 29, and irrigation in Chapter 37 on hotel garden irrigation.

    Work outside the building technician’s authority: opening, moving, or damaging the seal of the PDAM meter, altering the pipe before the meter, opening up floors, walls, or ground to search for a leaking pipe, installing or relocating submeters, and closing valves that supply the fire protection system. That work belongs to the PDAM, a plumber or plumbing contractor, and the staff designated for the fire protection system. The building technician reads meters, records, calculates the balance, walks the building, carries out tests that do not take anything apart, and reports.

    Water meter types and their accuracy

    A water meter is a device that turns water flow into a cumulative volume reading. EPA distinguishes utility-owned meters that measure all the water entering a facility for billing, and conventional meters that are read periodically by staff, typically monthly or quarterly, from advanced meters that record consumption at least hourly and transmit the data automatically. For the technician, the difference lies in how quickly a problem shows up: a meter read once a month reveals a leak only after the bill arrives.

    Common meter types in buildings according to the WaterSense guidance:

    • A positive displacement meter measures volume directly from a chamber that water fills and empties, is accurate at low flow, and suits small commercial buildings.
    • A velocity meter, such as a turbine or propeller meter, converts water velocity into volume, suits large continuous flows, and can be inaccurate at low flow.
    • A compound meter combines a positive displacement chamber for low flow and a turbine for high flow, so it suits large buildings.
    • Electronic meters, that is, electromagnetic and ultrasonic meters, including clamp-on models outside the pipe that can be used for spot checks.

    Meter size matters as much as type. An undersized meter causes pressure loss, reduced flow, and noise, while an oversized meter does not measure low flows accurately. A small leak is a low flow, so a large meter may not record it at all. Water that passes without being recorded counts as an apparent loss, discussed in the section on non-revenue water. For utility-owned meters, AWWA recommends testing on average every 10 years for sizes 5/8 to 1 inch, every five years for 1 to 4 inches, and every year for 4 inches and larger; these figures apply to water utilities in the United States. How each type of flow-measuring device works and its installation requirements are covered in Chapter 5 · Fluids & Thermal.

    Reading the register and recording

    The register is the row of digits on a meter that shows the volume accumulated since the meter was installed. In Indonesia the unit is usually cubic meters, with black digits for cubic meters and red digits or small pointers for fractions in liters. EPA warns of two reading errors: the meter’s unit must be noted, and many meters have one or more fixed trailing zeros that must be added after the digits read. Imported meters may use gallons or cubic feet, so the unit is written in every record.

    The volume used between two readings is calculated with

    V=R2−R1,V=R2+Rmax−R1    if R2<R1V = R_2 - R_1, \qquad V = R_2 + R_{max} - R_1 \;\; \text{if } R_2 < R_1

    where VV is the volume used (m³), R1R_1 and R2R_2 are the first and last readings (m³), and RmaxR_{max} is the register capacity, that is, the number at which the register rolls over to zero, for example 100,000 m³ for a five-digit register. The second formula applies when the register passes zero exactly once; when a meter is replaced, the old and new meter readings are recorded separately on the day of replacement. The average flow over an interval Δt\Delta t is

    q=VΔtq = \frac{V}{\Delta t}

    with qq in m³/h when Δt\Delta t is in hours.

    Meter records are useful when every line contains the date, time, full register reading with its unit, the reader’s name, and a note on conditions, for example the laundry closed or the pool refilled. EPA suggests that someone be assigned to track water use at least monthly, that staff be trained to read meters and record the figures correctly, that total and submetered use be plotted monthly, and that unexplained changes be investigated. Bills are compared with the previous month and with the same month of the previous year, allowing for seasonal changes. Reading at the same time each time makes two readings comparable, because hotel water use changes greatly between morning and night.

    Submeters and allocating use

    A submeter is a facility-owned meter that measures part of the use, for example one building in a complex, a tenant space, or one water-intensive activity. Submeters help find leaks, show malfunctioning equipment, and allocate costs to tenants. WaterSense submetering recommendations relevant to hotels and hospitals:

    UseSubmetering recommendation
    Tenant spacesmeter every tenant space individually
    Cooling towersmeter the make-up water and the blowdown water
    Steam boilersmeter the make-up water of boilers rated 500,000 Btu per hour or more
    Irrigationautomatically controlled irrigation systems
    Ornamental water featuresthe make-up water line of water features with a permanent supply
    Pools and spasthe make-up water lines of indoor and outdoor pools and spas
    Other processesuse of 1,000 gallons (3,800 L) per day or more

    Submeters are installed downstream of the main meter, in a place that is easy to read and protected, with a strainer on the inlet so that debris does not spoil accuracy, and all meters and submeters are drawn on a map that becomes part of the water management plan. Installation follows the manufacturer’s instructions, including the length of straight pipe before and after the meter (Chapter 5 · Fluids & Thermal). Submeters for internal management are not subject to the AWWA standards for billing meters, so their accuracy is checked according to the manufacturer’s recommendations.

    Submeters also check themselves. The sum of all submeters installed in parallel downstream of the main meter is always smaller than the main meter’s consumption, because guest rooms, public toilets, and garden taps are usually unmetered. If the sum of submeters exceeds the main meter, something is wrong: submeters installed in series and counted twice, a main meter that under-reads, readings taken on different days, or units mixed up.

    The building water balance

    A water balance is an accounting of all water uses at a facility, which shows the contribution of each end use to total use and reveals unaccounted water, which may come from leaks. The steps recommended by WaterSense: sum the measured or estimated use of all end uses for each water source, calculate metered use from submeter readings, bills, or logbooks, estimate unmetered use from measured flow rates or equipment specifications and patterns of use, and record alternative water sources such as rainwater or condensate separately. For the baseline, EPA suggests at least the two most recent years of water and sewer data.

    As a formula:

    Vin=∑Vsub+∑Vest+Vun,u=VunVinV_{in} = \sum V_{sub} + \sum V_{est} + V_{un}, \qquad u = \frac{V_{un}}{V_{in}}

    where VinV_{in} is the total water from all source meters (PDAM, drilled well, tanker trucks) in one period (m³), VsubV_{sub} is the use measured by submeters (m³), VestV_{est} is the estimated unmetered use (m³), VunV_{un} is unaccounted water (m³), and uu is the unaccounted fraction. All terms are calculated for the same period. If more than 10 percent of use is unaccounted, WaterSense writes that there could be an unidentified end use, a leak, or another issue warranting investigation; in the laboratory water balance example in that guidance, unaccounted water was 6 percent and was judged not to indicate a significant leak. The 10 percent threshold is for investigating, not for tolerating: a 5 percent leak whose location is already known is still repaired.

    The quality of the balance depends on its largest estimate. In a hotel, guest room use is usually unmetered and becomes the largest estimate, so an error in the room estimate can masquerade as unaccounted water. The estimate is therefore written together with its basis, for example a measured shower flow rate or use per occupied room from months without leaks. To compare months with different occupancy, WaterSense mentions metrics of use per occupied room and per total rooms for hotels, with the way the denominator was derived recorded. This baseline and normalization are the same as for energy in Chapter 34 · Buildings & Facilities. EPA also suggests a facility water assessment about every four years.

    Non-revenue water and water losses

    IWA and AWWA developed the standard water audit terminology that EPA uses for water utilities.

    • Authorized consumption is water used by known users, that is, the sum of billed and unbilled authorized consumption.
    • Real losses are water that actually leaves the system: leaking pipes, tank overflows and leaks, and leaking connections.
    • Apparent losses are water that is consumed but appears lost because of unauthorized consumption, meter inaccuracy, and data handling errors in meter reading and billing.
    • Non-revenue water is water that is not billed and not paid for, which can consist of unbilled authorized consumption, apparent losses, and real losses.

    The calculation follows the order of a top-down audit:

    Vloss=Vin−Vauth,Vreal=Vloss−Vapp,VNRW=Vin−VbillV_{loss} = V_{in} - V_{auth}, \qquad V_{real} = V_{loss} - V_{app}, \qquad V_{NRW} = V_{in} - V_{bill}

    where VauthV_{auth} is authorized consumption (m³), VlossV_{loss} is total water loss, VappV_{app} is the estimated apparent loss, VrealV_{real} is the real loss, VbillV_{bill} is billed authorized consumption, and VNRWV_{NRW} is non-revenue water. EPA notes that average water loss in water utility systems in the United States is 16 percent, and up to 75 percent of it is recoverable.

    These terms were written for water utilities, but they fit buildings that bill their tenants by submeter, such as a hotel with leased restaurants, serviced apartments, or a hospital complex with commercial units. In such a building, water for flushing, gardens, and cleaning is unbilled authorized consumption, old tenant meters that under-read or figures mistyped are apparent losses, and leaking pipes and overflowing roof tanks are real losses. The distinction matters for action: apparent losses are fixed with meters and record keeping, real losses by repairing pipes. A hotel without tenants uses the balance from the previous section, with unaccounted water consisting of apparent and real losses.

    Finding hidden leaks

    A hidden leak is a continuous flow of water that is not seen, for example a tank float valve that does not close so that water leaves through the overflow pipe, a worn toilet tank flapper, a pipe embedded in a floor, or a buried pipe in the grounds. There are several ways to find one without taking anything apart.

    Night readings. WaterSense recommends reading the meter during off-peak hours when all water-using equipment can be turned off and people are not using toilets and taps, then reading it again an hour later; a significant change indicates a leak in the distribution system or within the facility. Many meters also have a leak indicator, for example a small spinning triangle or dial, or a flashing dot on electronic meters. For households, EPA suggests a two-hour period with no water use. In a hotel, use is never truly zero, so the leak rate is calculated after subtracting legitimate night use:

    qleak=Vnight−VknownΔt,Vyear=24×365×qleakq_{leak} = \frac{V_{night} - V_{known}}{\Delta t}, \qquad V_{year} = 24 \times 365 \times q_{leak}

    where qleakq_{leak} is the leak rate (m³/h), VnightV_{night} is the difference on the main meter during the test (m³), VknownV_{known} is the known legitimate use during the test read from submeters or estimated (m³), Δt\Delta t is the duration of the test (h), and VyearV_{year} is the loss over a year (m³). The annual calculation assumes the leak is constant throughout the day. Night pressure is usually higher, so this figure tends to overstate slightly, but it is enough to decide whether to search. The test is repeated on another day to confirm; zone isolation to narrow down the location is covered in Chapter 15 · Buildings & Facilities.

    Reading resolution. The smallest digit of the register limits what can be seen. A meter whose smallest digit is 10 L does not show a leak of 4 L per hour in a one-hour test. Use the liter digits or the leak indicator, or extend the test.

    Toilet tank dye test. EPA suggests putting a few drops of food coloring in the toilet tank; if color shows up in the bowl after 10 minutes, the toilet leaks, and it is flushed right away to avoid staining. This test suits rounds of vacant rooms.

    Daily walk-through. WaterSense recommends a daily tour of the places where water is used, listening and looking: toilets or kitchen equipment that keep running or dripping, unexpected discharge to floor drains in plant rooms, wet ground or pavement around the building, and water flowing to the overflow drain of a cooling tower basin. Floor leak sensors and flow monitoring devices that raise an alert when flow is abnormal can be installed on large equipment. The size of small leaks left alone is clear from the WaterSense table: a flow of 0.02 gallons per minute from a toilet becomes 860 gallons per month, and 0.2 gallons per minute becomes 8,600 gallons per month.

    Worked example

    The figures in the examples below are practice figures unless their origin is stated.

    Example 1: a register that rolls over to zero. The five-digit register of the hotel’s drilled well meter reads 99,874.6 m³ on May 1 and 00,212.3 m³ on June 1. Because R2<R1R_2 < R_1, the register has passed zero, so V=212.3+100,000−99,874.6=337.7V = 212.3 + 100{,}000 - 99{,}874.6 = 337.7 m³. If the first formula is used as is, the result is negative, 212.3−99,874.6=−99,662.3212.3 - 99{,}874.6 = -99{,}662.3 m³, and a negative figure in the record is the first sign that the register has passed zero or the meter was replaced.

    Example 2: night reading and leak rate. The main meter reads 4,512.36 m³ at 01:00 and 4,513.26 m³ at 03:00, so Vnight=4,513.26−4,512.36=0.90V_{night} = 4{,}513.26 - 4{,}512.36 = 0.90 m³. The cooling tower make-up water submeter moved 0.22 m³ over the same period, and other equipment was off. The leak rate is qleak=(0.90−0.22)/2=0.34q_{leak} = (0.90 - 0.22)/2 = 0.34 m³/h, that is, 0.34×24=8.160.34 \times 24 = 8.16 m³ per day and 8.16×365=2,978.48.16 \times 365 = 2{,}978.4 m³ per year. At a practice tariff of Rp20,000 per m³, the loss is 2,978.4×20,000=59,568,0002{,}978.4 \times 20{,}000 = 59{,}568{,}000, that is, about Rp59.6 million per year.

    Example 3: monthly water balance. In June, the hotel received 5,200 m³ from the PDAM and 1,300 m³ from the drilled well, so Vin=6,500V_{in} = 6{,}500 m³. Submeters: laundry 1,150, kitchen 620, cooling tower make-up water 1,480, pool and spa 210, and irrigation 390 m³, totaling ∑Vsub=3,850\sum V_{sub} = 3{,}850 m³. Estimates: guest rooms, 4,300 occupied room-nights times 0.35 m³, that is, 4,300×0.35=1,5054{,}300 \times 0.35 = 1{,}505 m³, and public toilets and offices 235 m³. Accounted water is 3,850+1,505+235=5,5903{,}850 + 1{,}505 + 235 = 5{,}590 m³, so Vun=6,500−5,590=910V_{un} = 6{,}500 - 5{,}590 = 910 m³ and u=910/6,500=14.0u = 910/6{,}500 = 14.0 percent, above the 10 percent threshold. The leak from Example 2 over 30 days, 8.16×30=244.88.16 \times 30 = 244.8 m³, explains 244.8/910=26.9244.8/910 = 26.9 percent of the unaccounted water, so the rest is still to be found, starting with the room estimate and the accuracy of the meters.

    Example 4: non-revenue water in serviced apartments. A serviced apartment building owned by the hotel receives 3,000 m³ a month. The units are billed from submeters for 2,430 m³, and unbilled authorized use (gardens, pool, cleaning) is metered at 240 m³. Non-revenue water is VNRW=3,000−2,430=570V_{NRW} = 3{,}000 - 2{,}430 = 570 m³, that is, 570/3,000=19.0570/3{,}000 = 19.0 percent. Water loss is Vloss=3,000−(2,430+240)=330V_{loss} = 3{,}000 - (2{,}430 + 240) = 330 m³. Apparent losses are estimated from unit meters that under-read by 2 percent, 0.02×2,430=48.60.02 \times 2{,}430 = 48.6 m³, plus one broken meter estimated at 12 m³, a total of 60.6 m³. Real losses are 330−60.6=269.4330 - 60.6 = 269.4 m³, that is, 269.4/3,000=9.0269.4/3{,}000 = 9.0 percent of the water coming in.

    Example 5: a toilet leak and register resolution. A toilet leak of 0.02 gallons per minute from the WaterSense table equals 0.02×3.785=0.07570.02 \times 3.785 = 0.0757 L/min, that is, 0.0757×60=4.540.0757 \times 60 = 4.54 L/h and 4.54×24=1094.54 \times 24 = 109 L per day. Over 30 days, 109×30=3,270109 \times 30 = 3{,}270 L, about 3.27 m³, consistent with 860 gallons per month, because 860×3.785=3,255860 \times 3.785 = 3{,}255 L. Twelve such toilets leak 12×4.54=54.512 \times 4.54 = 54.5 L in a one-hour night test, so a meter whose smallest digit is 10 L moves only five steps. A single toilet, 4.54 L, does not show at all, so the dye test is faster for checking toilets one by one.

    Example 6: use per occupied room. June used 6,500 m³ with 4,300 occupied room-nights, that is, 6,500/4,300=1.516{,}500/4{,}300 = 1.51 m³ per room-night. August used 5,900 m³ with 3,400 room-nights, that is, 5,900/3,400=1.745{,}900/3{,}400 = 1.74 m³ per room-night. Total use fell by (6,500−5,900)/6,500=9.2(6{,}500 - 5{,}900)/6{,}500 = 9.2 percent, but use per occupied room rose by (1.74−1.51)/1.51=15.2(1.74 - 1.51)/1.51 = 15.2 percent. A lower bill does not mean things have improved, because much of the use, such as the cooling tower, irrigation, and leaks, does not fall along with occupancy.

    Stop conditions

    1. The seal of the PDAM meter is broken, the meter leaks, is installed backward, or someone proposes moving the meter: do not open, turn, or move it; report to management to be passed on to the PDAM.
    2. A leak is suspected in a pipe embedded in a floor, wall, or the ground, or in the pipe before the PDAM meter: do not open up or dig; hand over to a plumber or plumbing contractor, and to the PDAM if it is before the meter.
    3. Leaking water is dripping onto an electrical panel, pump motor, or socket outlet, or a pump room is flooded: do not step into the water and do not touch the equipment; have the designated person switch off the power at a panel outside the wet area, and hand over to an authorized electrician.
    4. A night test or zone isolation would require closing a valve that also supplies sprinklers, hydrants, or water for patient care areas: do not close it; postpone the test until it is approved by the fire protection system staff and the building or hospital management.
    5. Inspecting a roof tank, underground tank, or meter pit would require climbing onto a roof or entering an enclosed space: stop until a work-at-height permit or confined space entry permit is issued (Chapter 11 · Safety on confined spaces).
    6. A water heater relief valve keeps discharging water, or hot water is coming out onto the floor: do not close or plug the relief valve; report to the water heater technician (Chapter 12 · Buildings & Facilities on valves and water control).
    7. Consumption on the bill is far above the meter readings, or a pipe connection that is not on the meter map is found: do not disconnect or alter the connection yourself; record it and report to management.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    A lower bill means the leak has gone.

    Why is it wrong?

    The bill follows occupancy and weather. Use per occupied room and night readings are what reveal a leak, as in Example 6.

    Common misconception

    A meter that stays still at night means there is no leak.

    Why is it wrong?

    A large meter and a smallest digit of 10 L do not show a small leak within an hour. The leak indicator, the liter digits, or a longer test are needed.

    Common misconception

    Unaccounted water below 10 percent means nothing needs repairing.

    Why is it wrong?

    The 10 percent threshold is the limit for investigating. A leak that has been found is still repaired, whatever its share.

    Common misconception

    Non-revenue water is the same as leakage.

    Why is it wrong?

    Non-revenue water also includes unbilled authorized consumption and apparent losses from meters and record keeping. Only real losses are fixed by repairing pipes.

    Common misconception

    The sum of submeters may exceed the main meter because the main meter is coarse anyway.

    Why is it wrong?

    The sum of parallel submeters cannot exceed the main meter. If it does, look for a submeter counted twice, mixed-up units, readings on different days, or a main meter that under-reads.

    Chapter 15 · Buildings & Facilities on plumbing maintenance and diagnosis uses night readings and zone isolation to locate leaks; this chapter builds the figures around them. How flow-measuring devices work and their straight-pipe requirements are in Chapter 5 · Fluids & Thermal, the PDAM supply, drilled wells, and roof tanks in Chapter 5 · Buildings & Facilities, and estimates of use per room in Chapter 8 · Buildings & Facilities on water demand and pipe sizing. The cooling tower water submeter is read together with cycles of concentration in Chapter 10 · Utilities, and the way to build a baseline and read trends is the same as for the energy dashboard in Chapter 34 · Buildings & Facilities.

    Exercises and worked solutions

    The figures in the exercises are for practice.

    Try to answer first, then open the worked solution.

    1. The five-digit register of a PDAM meter reads 99,950 m³ and a month later 00,130 m³. What is the consumption?

      Check my answer
      See the worked solution

      The register has passed zero because the last reading is smaller, so V=130+100,000−99,950=180V = 130 + 100{,}000 - 99{,}950 = 180 m³. The ordinary difference formula gives −99,820-99{,}820 m³, and that negative figure signals that the second formula is the one to use.

    2. In a one-hour night test, the main meter moved 0.36 m³ and the ice machine and cooling tower submeters together moved 0.10 m³. What are the leak rate and the loss per day?

      Check my answer
      See the worked solution

      The leak rate is qleak=(0.36−0.10)/1=0.26q_{leak} = (0.36 - 0.10)/1 = 0.26 m³/h, so the loss per day is 0.26×24=6.240.26 \times 24 = 6.24 m³. The test is repeated on another night before the location is searched for, because a legitimate use that was missed, such as tank filling, can masquerade as a leak.

    3. A hospital receives 4,000 m³ a month and its balance accounts for 3,720 m³. Does it need investigating under the WaterSense threshold, and what is still done?

      Check my answer
      See the worked solution

      Unaccounted water is 4,000−3,720=2804{,}000 - 3{,}720 = 280 m³, that is, 280/4,000=7.0280/4{,}000 = 7.0 percent, below the 10 percent threshold. A major investigation is not yet needed, but night readings and daily walk-throughs continue, and any leak that is found is still repaired.

    4. The sum of a hotel’s submeters this month is 3,100 m³, while the main meter shows 2,950 m³. What is checked first?

      Check my answer
      See the worked solution

      The sum of parallel submeters cannot exceed the main meter, so the 150 m³ difference is an error, not consumption. What is checked first is a submeter installed in series and so counted twice, mixed-up units, and different reading dates, and only then the possibility that the main meter under-reads, which is reported to the PDAM.

    5. An imported meter in a building shows 201,670 cubic feet. How many cubic meters is that, if 1 cubic foot equals 0.02832 m³?

      Check my answer
      See the worked solution

      The volume is 201,670×0.02832=5,711201{,}670 \times 0.02832 = 5{,}711 m³. The unit is written in the record because cubic feet mixed with cubic meters would make the balance wrong by about a factor of 35.

    6. A building that bills its tenants receives 2,000 m³, bills 1,640 m³, and uses 120 m³ of authorized water without billing, with apparent losses estimated at 40 m³. Calculate the non-revenue water and the real losses.

      Check my answer
      See the worked solution

      Non-revenue water is 2,000−1,640=3602{,}000 - 1{,}640 = 360 m³, that is, 18 percent. Water loss is 2,000−(1,640+120)=2402{,}000 - (1{,}640 + 120) = 240 m³, so real losses are 240−40=200240 - 40 = 200 m³, which is the part searched for with night readings and repaired in the pipes.

    References

    External sources

    • WaterSense at Work: Getting Started With Water Management, 1.2 Water Management Planningepa.gov
    • WaterSense at Work: Water Use Monitoring, 2.1 Metering and Submeteringepa.gov
    • WaterSense at Work: Water Use Monitoring, 2.2 Leak Detection and Repairepa.gov
    • Water Audits and Water Loss Control for Public Water Systemsepa.gov
    • Fix a Leak Weekepa.gov
    • WaterSense at Work: Water Use Monitoring, 2.3 Benchmarkingepa.gov

    Revision history

    DateVersionChange
    November 14, 20261First published

    How to cite

    Kurnia (2026). Water meters and the building water balance: meter types, reading and recording, submeters, non-revenue water, finding hidden leaks, and calculating the balance. ARSTEMA Academy. Revised November 14, 2026. arstema.com/en/academy/konsep/meter-air-dan-neraca-air-gedung-jenis-meter-membaca-dan-mencatat-submeter-air-tak-berekening-mencari-kebocoran-tersembunyi-serta-menghitung-neraca

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated
    1

    The five-digit register of a PDAM meter reads 99,950 m³ and a month later 00,130 m³. What is the consumption?

    2

    In a one-hour night test, the main meter moved 0.36 m³ and the ice machine and cooling tower submeters together moved 0.10 m³. What are the leak rate and the loss per day?

    3

    A hospital receives 4,000 m³ a month and its balance accounts for 3,720 m³. Does it need investigating under the WaterSense threshold, and what is still done?