    Electrical & Control · Chapter 112Quantitative

    By Kurnia · Published November 14, 2026 · Version 1 · 18 min read

    Reading PLN electricity meters and bills

    tariff classes, connected power, peak-period and off-peak kWh, kVArh and power factor, peak demand, and calculating the cost

    The electricity bill of a hotel with a connected power of 1,110 kVA suddenly carries a kVArh charge line that had never appeared before, and the manager asks the technician to explain every line of the bill from the figures on the meter. This chapter covers reading PLN customer meters and bills from the building technician’s side: tariff classes and the power limits of low and medium voltage, regular and prepaid tariffs, the peak-period and off-peak kWh registers, the kVArh register, the meter multiplier with current and voltage transformers, the monthly average power factor and the 0.85 threshold, the minimum bill and operating hours, peak demand and load factor, and calculating the cost and checking the bill. Tariffs are taken from Minister of Energy and Mineral Resources Regulation No. 7 of 2024 and PLN’s tariff adjustment decision for October to December 2026; the value of the K factor and the way PLN calculates excess kVArh are not stated in those documents, so the examples use practice values. Breaking the APP seal, changing the limiter, and entering a medium-voltage switchgear room are stated as work for PLN or authorized personnel.

    Section you’re reading: Chapter opening

    The September electricity bill of a beachfront hotel rose by about seven percent, even though occupancy fell. The finance department found a new line in the bill details: a kVArh charge, which had been zero for the whole previous year. The engineering manager asked the on-duty technician to explain where every figure on the bill came from. The technician went down to the meter room, recorded the register values shown on the meter display without opening anything, and compared them with the bill. The figures showed that reactive energy had jumped after one stage of the capacitor bank stopped working, so the monthly average power factor fell below the threshold that is charged. The case shows that an electricity bill can be rechecked from the meter, provided the technician knows which register to read, what the multiplier is, and which tariff formula applies to the building’s class.

    Scope

    This chapter covers reading PLN meters and electricity bills for buildings such as hotels, hospitals, laundries, and central kitchens: tariff classes, connected power, energy registers, the average power factor, the minimum bill, peak demand, and how to calculate the cost. Official tariffs are taken from Minister of Energy and Mineral Resources Regulation (Permen ESDM) No. 7 of 2024 and PLN’s tariff adjustment decision for October to December 2026; for any other billing period, the tariff figures must be checked again against the PLN decision in force for that period.

    Active, reactive, and apparent power and the power triangle are covered in Chapter 6 on AC power and are not repeated. Power factor correction with capacitor banks and its safe limits are in Chapter 7. Energy dashboards, submeters, and consumption baselines are in Chapter 34 · Buildings & Facilities, and the carbon footprint of electricity use is in Chapter 19 · Fluids & Thermal. The low-voltage APP, seals, and the customer ownership boundary are covered in Chapter 13, the maximum demand of an installation in Chapter 19, and medium-voltage substations and switchgear in Chapter 110 on the building’s medium-voltage substation.

    This chapter only reads and calculates. The building technician reads the figures shown on the meter display, records, calculates, and reports. Breaking the seal or terminal cover of the APP, changing the limiter, replacing current transformers, and entering a medium-voltage switchgear room without authorization are work for PLN or authorized personnel, and must not be done for the purpose of reading the meter.

    Tariff classes and connected power

    Tariff class is the group of customers charged the same tariff structure and level, determined by the use of the electricity and the power limit. Permen ESDM No. 7 of 2024 divides tariffs into social services, households, business, industry, government facilities and public street lighting, traction, bulk sales, and special services. For commercial buildings, the most common is the business group: B-1/TR for 450 VA to 5,500 VA, B-2/TR for 6,600 VA to 200 kVA, and B-3/TM or B-3/TT for power above 200 kVA.

    The regulation defines voltage levels by power. Low voltage is the voltage for power up to 200 kVA, medium voltage for power above 200 kVA up to less than 30,000 kVA, and high voltage for power of 30,000 kVA or more. So a hotel with a connected power of 1,110 kVA falls in class B-3/TM, while a restaurant of 41.5 kVA in a separate building falls in B-2/TR.

    A hospital can fall in the social group. PLN’s tariff page classes government-owned hospitals as pure social activities, and private hospitals, polyclinics, and joint doctors’ practices as commercial social activities. In class S-2/TM, the tariff regulation uses a multiplier P = 1 for pure social and P = 1.3 for commercial social customers. Processing businesses that add value to a product can be placed in the industry group; deciding the class of a laundry or central kitchen remains PLN’s decision under the contract, not the technician’s choice.

    Connected power is the power in VA or kVA agreed by the customer and PLN in the contract. This figure sets the class, forms the basis of the minimum bill, and limits the load that may be drawn. Connected power differs from connected load, which is the sum of the nameplate power of all equipment in the building. Connected load is almost always much larger than the load that actually runs at the same time, as explained in Chapter 19 on maximum demand.

    Tariff structure: regular, prepaid, WBP, LWBP, and kVArh

    The electricity tariff consists of the regular tariff, paid after use, and the prepaid tariff, paid before use. For class B-3/TM, the prepaid column in the regulation’s annex holds a dash, so large buildings use the regular tariff.

    Peak period (WBP, waktu beban puncak) is the range of hours when the load on the local power system is highest, and off-peak period (LWBP, luar waktu beban puncak) is the remaining hours. For classes above 200 kVA, the usage charge is split by these two ranges. For B-3/TM, the regulation’s annex states WBP block = K times 1,035.78 Rp/kWh, LWBP block = 1,035.78 Rp/kWh, and kVArh = 1,114.74 Rp/kVArh. The hours of the WBP are not stated in the tariff regulation; they are programmed into the meter and read from the contract or from PLN.

    K factor is the ratio of the WBP price to the LWBP price. The regulation states that K is set by the Board of Directors of PT PLN (Persero) according to the load characteristics of the local power system, within the limits 1.4 to 2. The value of K for a particular building is not listed in the documents cited in this chapter. In every real calculation, therefore, K is taken from the bill details; if the bill shows only the rupiah amount and kWh for the WBP, K can be calculated back by dividing the WBP price per kWh by the LWBP price.

    The kVArh charge is a charge for excess reactive power use. A note to the regulation’s annex states that the charge applies when the monthly average power factor is less than 0.85. The regulation does not define how many kVArh count as excess. This chapter uses one calculation model consistent with that threshold (Example 4), noting that PLN’s actual method is read from the bill details.

    Smaller classes up to 200 kVA, such as B-2/TR, are not split into WBP and LWBP. In PLN’s decision for October to December 2026, the B-2/TR tariff is 1,444.70 Rp/kWh for both regular and prepaid.

    Tariff adjustment and the reference date

    Tariffs do not stay fixed all year. Article 6 of the tariff regulation sets a tariff adjustment for a number of non-subsidized classes, including B-2/TR, B-3/TM and B-3/TT, I-3/TM, I-4/TT, medium P-1/TR, P-2/TM, P-3/TR, and special services, every 3 months when there are changes in the exchange rate, the Indonesian crude price, inflation, and the reference coal price. PLN must announce the adjustment no later than one month before it takes effect. The social class S-2/TM is not on that list, so its tariff follows the figures in the regulation’s annex.

    PLN’s tariff adjustment decision for October to December 2026, dated October 22, 2026, covers 13 classes and uses the same figures as the regulation’s annex for the large business class: WBP block = K times 1,035.78, LWBP block = 1,035.78, and kVArh = 1,114.74. A PLN press release dated November 3, 2026 states that tariffs for the fourth quarter of 2026 remain unchanged for 13 non-subsidized and 24 subsidized classes.

    As of November 2026, PLN’s tariff page still refers to Permen ESDM No. 7 of 2024, and the JDIH ESDM page for that regulation lists no amending regulation. Every bill calculation should record its tariff reference date, because a figure that is correct for September is not necessarily correct for January.

    Meters, registers, and the multiplier

    APP (alat pembatas dan pengukur, limiting and metering device) is a PLN-owned device that limits power and measures energy, for both prepaid and postpaid supply, and the customer installation begins after the APP. On a medium-voltage connection, the meter does not carry the full load current. The current is stepped down by current transformers and the voltage by voltage transformers, and the meter measures these small secondary quantities.

    Register is a cumulative quantity stored and displayed by the meter. A B-3/TM customer meter generally shows several registers in turn: LWBP kWh, WBP kWh, kVArh, and maximum demand. Each register is read as a cumulative figure, so the use in one period is the difference between the final and the initial reading.

    Meter multiplier is the factor that converts the difference in the secondary register into the primary energy that is billed. When the meter measures on the secondary side of the current and voltage transformers, the multiplier equals the product of their ratios:

    FK=IprimaryIsecondary×UprimaryUsecondary,E=(Rfinal−Rinitial)×FKFK = \frac{I_\text{primary}}{I_\text{secondary}} \times \frac{U_\text{primary}}{U_\text{secondary}}, \qquad E = (R_\text{final} - R_\text{initial}) \times FK

    where FKFK is the meter multiplier (dimensionless), II the rated current of the current transformer (A), UU the rated voltage of the voltage transformer (V), RR the register value, and EE the energy for the period (kWh or kVArh). The multiplier is usually printed on the bill or on the meter panel plate. A wrong multiplier is the most expensive misreading: a register read correctly but multiplied by 1,000 instead of 2,000 makes the energy look like half its value.

    Reading the meter only needs the window or display that is provided for reading. If the display is visible only after a panel door is opened or after entering the switchgear room, the reading is done together with personnel authorized for that room.

    Average power factor and kVArh

    The monthly average power factor is calculated from the two energy registers, not from the instantaneous value on the panel. With EPE_\text{P} the active energy (kWh) and EQE_\text{Q} the reactive energy (kVArh) in one month:

    cos⁡φavg=EPEP2+EQ2\cos\varphi_\text{avg} = \frac{E_\text{P}}{\sqrt{E_\text{P}^2 + E_\text{Q}^2}}

    The derivation of this formula and the difference between instantaneous and average power factor are in Chapter 6. For the bill, what matters is the threshold. A power factor of 0.85 is equivalent to a kVArh-to-kWh ratio of tan⁡(arccos⁡0.85)=0.6197\tan(\arccos 0.85) = 0.6197. If the reactive energy in a month is more than about 62 percent of the active energy, the average power factor for that month is below 0.85 and the kVArh charge appears.

    The calculation model used in this chapter assumes that only the part of the kVArh above that limit is billed:

    EQ,excess=EQ−0.6197 EP,BkVArh=EQ,excess×TkVArhE_\text{Q,excess} = E_\text{Q} - 0.6197\,E_\text{P}, \qquad B_\text{kVArh} = E_\text{Q,excess} \times T_\text{kVArh}

    where TkVArhT_\text{kVArh} is the kVArh tariff (Rp/kVArh) and BkVArhB_\text{kVArh} the kVArh charge (Rp). This model is arithmetic from the 0.85 threshold, not a formula in the regulation. If the bill details show a different billed kVArh figure, the bill details are used, and the difference is raised with PLN.

    The causes of a sudden rise in kVArh in a building usually lie on the customer side: a capacitor bank stage with a blown fuse, a power factor regulator set to manual, or a new motor load without compensation. Inspecting and repairing the capacitor bank is covered in Chapter 7 and is done by an authorized electrical technician.

    Peak demand, minimum bill, and operating hours

    Peak demand is the highest active power recorded by the meter in one billing period. The meter does not record momentary surges; it records the average power over a short programmed interval and stores the highest value as the maximum demand register. As with the energy registers, the figure on the display is multiplied by the multiplier.

    For class B-3/TM, the regulation’s annex lists no demand charge per kVA, only a minimum bill. So peak demand does not directly add rupiah in this class. Peak demand still matters for three reasons: it shows how close the building is to its connected power, it sets the adequacy of transformers and cables, and peak demand that falls in WBP hours means expensive energy. The relation between peak demand and energy is expressed by the load factor:

    LF=EPPmax×tLF = \frac{E_\text{P}}{P_\text{max} \times t}

    where LFLF is the load factor (dimensionless, 0 to 1), PmaxP_\text{max} the peak demand (kW), and tt the number of hours in the period (h). A low load factor means the building is paying for capacity that is rarely used.

    Operating hours (jam nyala) are the monthly energy in kWh divided by the connected power in kVA. Minimum bill is the lower limit of the bill, calculated from 40 operating hours. For B-3/TM, the regulation’s annex states RM2 = 40 (operating hours) times connected power (kVA) times the LWBP usage charge, and for classes such as B-2/TR, RM1 = 40 times connected power times the usage charge.

    JN=EPST,RM2=40×ST×TLWBPJN = \frac{E_\text{P}}{S_\text{T}}, \qquad RM_2 = 40 \times S_\text{T} \times T_\text{LWBP}

    where JNJN is the operating hours (h), STS_\text{T} the connected power (kVA), and TLWBPT_\text{LWBP} the LWBP tariff (Rp/kWh). The minimum bill matters when the building is nearly empty, for example a hotel under renovation that keeps its full connected power. How PLN compares the minimum bill with the usage charge in the bill details is read from the bill itself.

    Calculating the cost and checking the bill

    For classes with WBP and LWBP blocks, the monthly energy cost is calculated from three registers:

    B=ELWBP TLWBP+EWBP K TLWBP+BkVArhB = E_\text{LWBP}\,T_\text{LWBP} + E_\text{WBP}\,K\,T_\text{LWBP} + B_\text{kVArh}

    The bill can contain other components that are not part of the tariff regulation, for example a regional tax. Those components are read from the bill and are not calculated in this chapter, so the result of the formula above is smaller than the total paid.

    A useful monthly check for the building technician has five steps. First, record the readings of all registers on the same date each month, as close as possible to PLN’s reading date. Second, compare the multiplier, class, and connected power on the bill with the contract. Third, recalculate the LWBP kWh, WBP kWh, and kVArh, and compare them with the bill. Fourth, calculate the average power factor and the operating hours. Fifth, record the peak demand and the time it occurred if the meter stores it. This monthly log becomes input for the energy dashboard in Chapter 34 · Buildings & Facilities and the emissions calculation in Chapter 19 · Fluids & Thermal.

    PLN’s page on electricity usage enforcement (P2TL) divides violations into four categories: P-I affects the power limit, P-II affects energy measurement, P-III affects both, and P-IV is committed by non-customers. P2TL officers have the authority to temporarily disconnect the service connection or APP and to confiscate evidence. For the technician, this means seals and meters are not touched, and any irregularity at the APP is reported, not fixed by the technician.

    Worked example

    The figures in the examples below are practice figures unless their origin is stated. The tariffs 1,035.78 Rp/kWh, 1,114.74 Rp/kVArh, and 1,444.70 Rp/kWh come from PLN’s decision for October to December 2026, while K = 1.4 is the lowest value of the permitted range, used because the K value of the example building is not known.

    Example 1: determining the class and the minimum bill. A hotel with a connected power of 1,110 kVA exceeds 200 kVA, so it falls in B-3/TM and its minimum bill is 40×1,110×1,035.78=45,988,63240 \times 1{,}110 \times 1{,}035.78 = 45{,}988{,}632 rupiah. The hotel’s restaurant in a separate building, with its own 41.5 kVA connection, falls in B-2/TR; its minimum bill is 40×41.5×1,444.70=2,398,20240 \times 41.5 \times 1{,}444.70 = 2{,}398{,}202 rupiah. The two connections are billed separately, so their energy is not added together to determine the class.

    Example 2: reading the registers with the multiplier. The hotel meter uses a 20,000/100 V voltage transformer and a 50/5 A current transformer, so FK=10×200=2,000FK = 10 \times 200 = 2{,}000. The LWBP reading rises from 4,512.36 to 4,637.86, the WBP reading from 1,023.10 to 1,051.60, and the kVArh reading from 3,210.40 to 3,316.90. The energies are ELWBP=125.50×2,000=251,000E_\text{LWBP} = 125.50 \times 2{,}000 = 251{,}000 kWh, EWBP=28.50×2,000=57,000E_\text{WBP} = 28.50 \times 2{,}000 = 57{,}000 kWh, and EQ=106.50×2,000=213,000E_\text{Q} = 106.50 \times 2{,}000 = 213{,}000 kVArh. The total active energy is 308,000 kWh. Had the multiplier been read as 1,000, all of these figures would be halved and the difference from the bill would be obvious at once.

    Example 3: WBP and LWBP usage charges. With K = 1.4, the WBP price is 1.4×1,035.78=1,450.0921.4 \times 1{,}035.78 = 1{,}450.092 Rp/kWh. The LWBP charge is 251,000×1,035.78=259,980,780251{,}000 \times 1{,}035.78 = 259{,}980{,}780 rupiah, the WBP charge 57,000×1,450.092=82,655,24457{,}000 \times 1{,}450.092 = 82{,}655{,}244 rupiah, and the sum is 342,636,024 rupiah. The WBP share is only 18.5 percent of the energy but 24.1 percent of the usage charge, because each WBP kWh costs 414.31 rupiah more.

    Example 4: average power factor and the kVArh charge. From Example 2, cos⁡φavg=308,000/308,0002+213,0002=0.822\cos\varphi_\text{avg} = 308{,}000/\sqrt{308{,}000^2 + 213{,}000^2} = 0.822, below 0.85. The kVArh limit without charge is 0.6197×308,000=190,8680.6197 \times 308{,}000 = 190{,}868 kVArh, so the excess is 213,000−190,868=22,132213{,}000 - 190{,}868 = 22{,}132 kVArh and the charge is 22,132×1,114.74=24,671,42622{,}132 \times 1{,}114.74 = 24{,}671{,}426 rupiah. The total energy cost by this chapter’s formula is 367,307,450 rupiah, and the kVArh charge is about 6.7 percent of it. That figure matches the rise in the bill in the opening case.

    Example 5: operating hours during renovation. During renovation, the same hotel uses 30,000 kWh LWBP and 8,000 kWh WBP. Its operating hours are 38,000/1,110=34.238{,}000/1{,}110 = 34.2 hours, below 40 hours. Its usage charge is 30,000×1,035.78+8,000×1,450.092=42,674,13630{,}000 \times 1{,}035.78 + 8{,}000 \times 1{,}450.092 = 42{,}674{,}136 rupiah, smaller than the minimum bill of 45,988,632 rupiah from Example 1. On the reading that the larger amount is billed, the hotel pays 3,314,496 rupiah for energy it did not use. If the renovation lasts for months, management can discuss a change in connected power with PLN.

    Example 6: peak demand and shifting load out of the WBP. The maximum demand register shows 0.355, so the peak demand is 0.355×2,000=7100.355 \times 2{,}000 = 710 kW. At a power factor of 0.822, the apparent power is 710/0.822=864710/0.822 = 864 kVA, which is 78 percent of the connected power. The load factor for a 30-day month is 308,000/(710×720)=0.60308{,}000/(710 \times 720) = 0.60. If the hotel laundry, drawing 120 kW for 2 hours each day, is moved from the WBP to the LWBP, the energy shifted is 120×2×30=7,200120 \times 2 \times 30 = 7{,}200 kWh and the saving is 7,200×414.31=2,983,0327{,}200 \times 414.31 = 2{,}983{,}032 rupiah a month, without reducing the kWh at all.

    Stop conditions

    1. The APP seal or the meter terminal cover is damaged, missing, or appears to have been opened: do not touch it and do not fit a seal yourself; photograph, record, and report to the engineering manager, who contacts PLN.
    2. The meter display is blank, shows an error code, or a register does not advance although the building load is running: do not open the meter or its panel; record the time and report to PLN through the engineering manager.
    3. There is a burning smell, an unusual hiss or hum, or heat at the APP cabinet, meter panel, or switchgear room: stop the reading, move away, keep people from approaching, and report to PLN and the person responsible for the building’s electrical systems (Chapter 110 on the building’s medium-voltage substation).
    4. The meter display can only be read by opening a panel door or entering the medium-voltage switchgear room: do not enter alone; the reading is done together with authorized electrical safety (K3) personnel or a PLN officer.
    5. The bill shows a class, multiplier, or connected power different from the contract, or a large billing difference that the registers do not explain: stop the analysis yourself and hand it to management for a formal complaint to PLN; the limiter and the contract must not be changed by the technician.
    6. A kVArh charge appears and the capacitor bank needs to be inspected or adjusted: hand it to an authorized electrical technician under Chapter 7; the on-duty technician only records the stages that are on and the regulator readings from outside the panel.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    The figure on the meter display is the kWh billed.

    Why is it wrong?

    On a medium-voltage connection, the register value is multiplied by the multiplier, for example 2,000. A register difference of 125.50 means 251,000 kWh, not 125.5 kWh.

    Common misconception

    The panel shows a power factor of 0.92, so there cannot be a kVArh charge.

    Why is it wrong?

    The kVArh charge uses the monthly average power factor from the kWh and kVArh registers. The instantaneous value can be high while the heaters are on and low at night, and the monthly average is set by how long each state lasts.

    Common misconception

    High peak demand directly adds to the hotel’s bill.

    Why is it wrong?

    Class B-3/TM lists no demand charge per kVA, only a minimum bill. Peak demand that falls in WBP hours adds cost through more expensive WBP energy, and peak demand close to the connected power is a sign of capacity.

    Common misconception

    The electricity tariff is the same all year.

    Why is it wrong?

    Tariffs of non-subsidized classes can be adjusted every 3 months. A correct calculation records the tariff reference date, for example the October to December 2026 decision.

    Common misconception

    Saving energy means reducing kWh.

    Why is it wrong?

    Shifting load from the WBP to the LWBP reduces rupiah without reducing kWh, and correcting the power factor removes the kVArh charge without reducing kWh. Both are still cost savings.

    Chapter 6 on AC power gives the basis for reactive power and the average power factor, and Chapter 7 on power factor correction covers the capacitor bank that drives the kVArh register. Chapter 13 on the low-voltage supply system covers the APP, seals, and the ownership boundary, while Chapter 110 on the building’s medium-voltage substation and Chapter 111 on the building’s distribution transformer cover the medium-voltage side where the B-3/TM meter is installed. The register data recorded in this chapter become input for the energy dashboard in Chapter 34 · Buildings & Facilities and the emissions calculation in Chapter 19 · Fluids & Thermal.

    Exercises and worked solutions

    Try to answer first, then open the worked solution.

    1. A commercial laundry with a connected power of 53 kVA is classed B-2/TR and uses 9,800 kWh a month. Calculate the usage charge, operating hours, and minimum bill with the October to December 2026 tariff.

      Check my answer
      See the worked solution

      The usage charge is 9,800×1,444.70=14,158,0609{,}800 \times 1{,}444.70 = 14{,}158{,}060 rupiah, because B-2/TR uses a single price per kWh with no WBP block. The operating hours are 9,800/53=184.99{,}800/53 = 184.9 hours, far above 40 hours, so the minimum bill of 40×53×1,444.70=3,062,76440 \times 53 \times 1{,}444.70 = 3{,}062{,}764 rupiah has no effect.

    2. A building records 120,000 kWh and 60,000 kVArh in a month. Is a kVArh charge applied?

      Check my answer
      See the worked solution

      The kVArh-to-kWh ratio is 0.5, below 0.6197, so the average power factor is 120,000/120,0002+60,0002=0.894120{,}000/\sqrt{120{,}000^2 + 60{,}000^2} = 0.894. That value is above 0.85, so no kVArh charge applies that month.

    3. A new technician calculates the LWBP energy from Example 2 with a multiplier of 1,000. What figure do they get, and how is the error recognized?

      Check my answer
      See the worked solution

      They get 125.50×1,000=125,500125.50 \times 1{,}000 = 125{,}500 kWh, half of 251,000 kWh. The error is recognized because the result is only half the bill figure, and the correct multiplier is calculated from the current and voltage transformer ratios or read from the bill.

    4. If K for the hotel in Example 3 turns out to be 2, how much is the extra WBP charge compared with K = 1.4?

      Check my answer
      See the worked solution

      The WBP price becomes 2×1,035.78=2,071.562 \times 1{,}035.78 = 2{,}071.56 Rp/kWh, so the WBP charge is 57,000×2,071.56=118,078,92057{,}000 \times 2{,}071.56 = 118{,}078{,}920 rupiah. The extra is 118,078,920−82,655,244=35,423,676118{,}078{,}920 - 82{,}655{,}244 = 35{,}423{,}676 rupiah, so the actual K value needs to be read from the bill before calculating savings.

    5. How many kVArh must the capacitor bank remove in the month of Example 4 for the average power factor to be exactly 0.85, and who carries out the repair?

      Check my answer
      See the worked solution

      The reactive energy needs to fall by the excess, that is 22,132 kVArh, to 190,868 kVArh, because at a ratio of 0.6197 the average power factor is exactly 0.85. Inspecting the fuses, stages, and regulator of the capacitor bank is work for an authorized electrical technician under Chapter 7, while the on-duty technician records the registers before and after the repair.

    6. A private hospital in class S-2/TM uses 180,000 kWh LWBP a month. What is its LWBP charge according to the annex of the tariff regulation?

      Check my answer
      See the worked solution

      A private hospital is classed as commercial social, so P = 1.3 and the LWBP price is 1.3×735=955.51.3 \times 735 = 955.5 Rp/kWh. The charge is 180,000×955.5=171,990,000180{,}000 \times 955.5 = 171{,}990{,}000 rupiah; class S-2/TM is not among the classes adjusted every quarter, so the figure in the regulation’s annex is used.

    References

    External sources

    • Peraturan Menteri Energi dan Sumber Daya Mineral Nomor 7 Tahun 2024 tentang Tarif Tenaga Listrik yang Disediakan oleh PT Perusahaan Listrik Negara (Persero)jdih.esdm.go.id
    • Peraturan Menteri Energi dan Sumber Daya Mineral Nomor 7 Tahun 2024 Tentang Tarif Tenaga Listrik Yang Disediakan Oleh PT. Perusahaan Listrik Negara (Persero)jdih.esdm.go.id
    • Penetapan Penyesuaian Tarif Tenaga Listrik (Tariff Adjustment) Bulan Oktober - Desember 2026pln.co.id
    • Tariff Adjustmentpln.co.id
    • Q4 2026 Electricity Tariffs Remains, PLN Supports Indonesian Economic Growthpln.co.id
    • Energy Usage Regulationpln.co.id

    Revision history

    DateVersionChange
    November 14, 20261First published

    How to cite

    Kurnia (2026). Reading PLN electricity meters and bills: tariff classes, connected power, peak-period and off-peak kWh, kVArh and power factor, peak demand, and calculating the cost. ARSTEMA Academy. Revised November 14, 2026. arstema.com/en/academy/konsep/membaca-meter-dan-tagihan-listrik-pln-golongan-tarif-daya-tersambung-kwh-waktu-beban-puncak-dan-luar-beban-puncak-kvarh-dan-faktor-daya-beban-puncak-serta-menghitung-biaya

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated
    1

    A commercial laundry with a connected power of 53 kVA is classed B-2/TR and uses 9,800 kWh a month. Calculate the usage charge, operating hours, and minimum bill with the October to December 2026 tariff.

    2

    A building records 120,000 kWh and 60,000 kVArh in a month. Is a kVArh charge applied?

    3

    A new technician calculates the LWBP energy from Example 2 with a multiplier of 1,000. What figure do they get, and how is the error recognized?

    Self-assessment progress0%