By Kurnia · Published November 15, 2026 · Version 1 · 20 min read
Public restrooms with sensors
toilets and urinals with flushometer valves, infrared sensors and solenoid valves, automatic faucets and hand dryers, batteries and power supply, water saving, and maintenance
The morning after a gala dinner in a hotel ballroom, the public restroom submeter recorded water flowing all night: six sensor urinals flushed by themselves every four minutes, two sensor faucets were dead because their batteries had run out, and one toilet flushometer valve ran for nine seconds. This chapter covers sensor-operated public restrooms from the building technician’s side: toilets and urinals with diaphragm and piston flushometer valves, infrared sensors and solenoid valves, phantom flushes and the manual flush button, automatic faucets and aerators, hand dryers and the CDC recommendations on washing and drying hands, batteries and adapters, calculating water use and savings with the equations of the United States EPA WaterSense guidance, and periodic maintenance. The flush volume and flow rate figures are United States figures; as of November 2026, the Indonesian requirements could not be confirmed from open documents. Replacing toilets or urinals, altering pipes, and opening energized hand dryers is work for plumbers and authorized electrical technicians.
The morning after a gala dinner in the ballroom of a hotel in Surabaya, a technician read the water submeter of the public restroom next to the ballroom and found that it had advanced by about 1.4 m³ between 22:00 and 06:00, even though the room had been locked after the event. When the door was opened, all six sensor urinals were flushing by themselves in turn roughly every four minutes. Along the row of washbasins, two sensor faucets gave no water and their small lights were blinking red, and one toilet kept running for up to nine seconds every time it was flushed. The hand dryer near the door still worked, but the floor beneath it was wet. The technician needs to sort out what is routine maintenance, what has to be handed over to a plumber or an electrical technician, and how much water is wasted if the situation is left as it is.
Scope
This chapter covers public restroom fixtures that work without being touched: toilets and urinals with flushometer valves, infrared sensors and solenoid valves, automatic faucets, hand dryers, battery and adapter power supplies, how to calculate water use and savings, and periodic maintenance. It is based on the WaterSense guidance of the United States EPA for commercial and institutional facilities, the maintenance practice of the federal energy program of the United States Department of Energy, and the CDC recommendations on hand hygiene. The flush volumes, flow rates, and use patterns in this chapter are United States figures. As of November 2026, the requirements for flush volume and faucet flow rate for buildings in Indonesia could not be confirmed from open documents; ask the building plumbing designer and the local technical office before using them for procurement.
Faucets, stop valves, flexible hoses, and air gaps are covered in Chapter 7 on fixtures and appliance connections. Blockages, odors, and pipe leaks are in Chapter 15 on plumbing maintenance and diagnosis, traps and vents in Chapter 6, submeters and the water balance in Chapter 40 · Water & Water Treatment on water meters and the building water balance, and regulating and pressure-reducing valves in Chapter 12. Spent batteries and their waste are covered in Chapter 35 · Water & Water Treatment on hazardous waste (B3), electricity in wet rooms in Chapter 37 · Electrical & Control, RCD testing in Chapter 18 · Electrical & Control, and Legionella control in hot water in Chapter 13.
Work outside the building technician’s authority: replacing toilets, urinals, or flushometer valve bodies, altering supply and drain pipes, raising the flush volume setting above the factory value, opening hand dryers or adapters connected to the 230 V supply, and running new cables or socket outlets in the restroom. That work belongs to a plumber or plumbing contractor and an authorized electrical technician. The building technician inspects, cleans, replaces batteries and valve inserts according to the manufacturer’s manual, adjusts sensors within the limits the manufacturer allows, records, and reports.
Toilets and urinals with flushometer valves
A flushometer valve is a valve that, once triggered, releases a specific volume of water at a high flow rate directly from the supply pipe to the toilet or urinal bowl, without a storage tank. Because there is no tank, flushometer-valve toilets rely on larger supply piping and fairly high supply pressure, and this is the type commonly found in public restrooms and busy places. Tank-type toilets store water in the tank first and are common in residential and light commercial buildings, including guest rooms.
There are two kinds of flushometer valve insert. A diaphragm valve uses a rubber disk that separates the upper and lower chambers of the valve body; when triggered, the relief valve upsets the pressure balance so the diaphragm lifts and water flows, then water fills the upper chamber through a small bypass hole in the diaphragm until the diaphragm is pushed back and the valve closes. A piston valve works in a similar way with a plastic or brass cup with a rubber lip as the piston. A dirty or brittle diaphragm does not seal tightly, and pressure that is too low can keep the diaphragm from closing at all so that water keeps running. A bypass hole clogged with debris lengthens the flush cycle, which is why some valves have a small debris screen.
According to the United States federal energy program, diaphragm valves generally operate at 30 to 80 psi, roughly 207 to 552 kPa, and piston valves at 15 to 80 psi, roughly 103 to 552 kPa; the building pressure needs to meet the minimum pressure stated by the manufacturer. The relationship between pressure and building pumps is covered in Chapter 9.
In the United States, flush volume is limited by the 1992 energy law to 1.6 gallons per flush (6.1 L) for toilets and 1.0 gallon (3.8 L) for urinals. The WaterSense label requires flushometer-valve toilets to use no more than 1.28 gallons (4.85 L) and no less than 1.0 gallon (3.8 L) in full flush; the lower limit is set so that there is enough water to carry waste along the building drain.
WaterSense labeled urinals use no more than 0.5 gallon (1.9 L), and some use only 0.125 gallon (0.47 L). Fixtures in old buildings are far more wasteful: old toilets often use 3.5 to 5.0 gallons (13.2 to 18.9 L), and old urinals 1.5 to 3.5 gallons (5.7 to 13.2 L).
Valve and bowl have to match. A low-volume insert fitted to an old bowl designed for a large volume can leave the bowl unclean and block the drain; the United States federal program advises replacing bowl and valve together, and replacement inserts must have the same rating as the valve. Replacing a diaphragm insert with one of a different rating is a quiet way of raising the flush volume.
Infrared sensors and solenoid valves
An active infrared sensor is a sensor that emits infrared light and measures its reflection; when an object stays within the detection range for a set time, the sensor assumes a user is present. On urinals and toilets, the controller waits for the user to move away and then gives the flush command. On faucets, water is turned on while the hands are under the spout and turned off shortly after the hands are withdrawn. Some fixtures use ultrasonic sensors, with the same principle but sound waves.
A solenoid valve is a valve opened and closed by an electromagnet coil. On sensor fixtures, the solenoid usually triggers a small relief valve that then moves the main diaphragm, so a small coil is enough to control a large flow. Battery-powered fixtures generally use a latching solenoid, which is a solenoid that only needs a short current pulse to switch from open to closed or the reverse and holds its position without current. How a fixture closes when its battery weakens differs by manufacturer design, so the manufacturer’s manual is read before a battery is allowed to run flat.
EPA states that sensors on toilets and urinals add no water savings; their benefit is hygiene, because users do not touch a handle. Sensors that are not adjusted and maintained properly instead cause double flushes or phantom flushes, which are flushes that happen with no user, so water use rises. Common causes in the field: a detection range set too far so that the stall door, the opposite wall, or people walking past are read as users; a sensor window that is dirty, scratched, or covered with cleaner residue; reflections from glossy surfaces; direct sunlight; and a weak battery that makes the controller behave erratically.
Sensor urinals often have a manual flush button for staff. EPA warns that the button can release a larger volume than a normal flush, so cleaning staff are trained to use it and to make sure the urinal returns to its original flush volume after cleaning. Sensors are checked and adjusted at least once a year.
Phantom flushes are calculated from the number of flushes during the time with no users:
where is the number of phantom flushes, the time without users (min), the interval between phantom flushes (min), the volume of one flush (L), and the water wasted (L). This formula assumes a fixed flush interval; irregular intervals are calculated from the submeter record or from a direct count over one hour.
Automatic faucets and hand dryers
In the United States, public restroom faucets are limited by the ASME and CSA standard to 0.5 gallon per minute (1.9 L/min) at a pressure of 60 psi (414 kPa), while a metering faucet, which is a faucet that delivers water for a preset time after it is triggered, is limited to 0.25 gallon per cycle (0.95 L). Many old faucets still run at 2.0 to 2.5 gallons per minute (7.6 to 9.5 L/min). A faucet aerator is an insert in the faucet spout that limits the flow rate and shapes the stream; scale clogs aerators, and a missing aerator makes a faucet run far above its rating.
EPA notes that sensor faucets do not necessarily save water, because a sensor faucet opens fully while in use, whereas users of manual faucets usually do not turn the tap fully on. The United States federal program asks for sensors to be calibrated so that water flows only when hands are being washed, not when people walk past. Sensor faucets also have a health side: EPA cites research that sensor faucets may be more easily contaminated with bacteria, including Legionella, than old faucets, and suggests that health care facilities and senior care facilities weigh their specific needs, for example by using laminar flow devices instead of aerators that mix in air. In hospitals, replacing faucets and aerators in patient areas is discussed first with the infection prevention team.
CDC recommends five steps for washing hands: wet the hands with clean running water, turn off the tap, and apply soap; lather all surfaces of the hands; scrub for at least 20 seconds; rinse; and dry the hands with a clean towel or an air dryer. Germs transfer more easily to and from wet hands, so hands are dried after washing, but the best way to dry them remains unclear because there are few studies and their results conflict; the available studies suggest a clean towel or letting hands air dry as best. For the technician, the meaning is simple: a dead hand dryer sends users out with wet hands, so repairing it matters as much as repairing the faucet.
A hand dryer is a fixed electrical appliance in a room whose floor is often wet. Water from hands drips onto the floor beneath it, and some dryers have a drip tray that has to be emptied and cleaned. An air intake filter covered with dust and tissue fibers weakens the airflow and makes the heater run hotter. Cleaning the outside and any filter that can be removed without tools is maintenance work, while opening the casing and inspecting the heater, motor, and wiring is work for an electrical technician after the appliance has been isolated (Chapter 37 · Electrical & Control on wet rooms).
Batteries, adapters, and power supply
Sensor fixtures are powered in three ways: batteries inside the fixture, an adapter from a socket outlet or a low-voltage supply behind the wall, and a small generator that uses the water flow to charge a battery. Batteries make installation easy because no wiring is needed, but they add routine work and waste. Adapters remove battery replacement but bring the utility supply close to water.
A weakening battery is usually signaled by a blinking light or a beep, according to the manufacturer’s code. Battery life depends mainly on the number of solenoid actuations, so phantom flushes drain the battery as fast as they drain water (Example 6). Battery replacement is neatest when done for a whole room at once with the date recorded, so that fixtures do not fail one by one in the middle of an event.
There are some rules for replacing batteries. Battery type and voltage follow the manual; new and old batteries are not mixed; polarity follows the markings; the rubber seal of the battery cover is checked and refitted so that cleaning water does not get in; and spent batteries are collected as waste according to Chapter 35 · Water & Water Treatment on hazardous waste (B3), not thrown into the restroom bin. Batteries that leak, swell, or get hot are not used again.
Adapters and socket outlets in the restroom are in a wet room. Their location, degree of protection against water, and residual current protection are the electrical installer’s design (Chapter 37 · Electrical & Control on wet rooms and Chapter 18 · Electrical & Control on RCD testing). The building technician checks visually that the adapter is dry, its cover intact, the cable not under strain, and no water dripping toward it; if anything is wrong, the fixture is switched off at the panel by the designated person and an electrical technician is called.
Calculating water use and savings
The WaterSense guidance gives a simple equation for the annual water use of toilets and urinals:
where is the annual use (L), the volume per flush (L), the number of flushes per day, the days of operation per year, and the saving from to . For faucets:
where is the faucet flow rate (L/min), the use time per person per day (min), and the number of people. For building occupants in the United States, EPA uses averages in which women use the toilet three times a day and men once, while men use the urinal twice a day.
Public faucets are used for 15 to 30 seconds per use for handwashing, three to four times per person per day. These figures apply to permanent occupants such as office staff. A hotel public restroom serves event guests and visitors whose numbers change every day, so the number of uses is better calculated from a submeter or a visitor counter (Chapter 40 · Water & Water Treatment).
The actual flush volume can be estimated from the length of the flush cycle. The WaterSense guidance gives a flushometer-valve toilet volume formula of 0.42 gallon per second of cycle, which is 1.59 L per second, and states that a properly functioning 1.6-gallon (6.1 L) toilet valve does not have a cycle longer than four seconds. For urinals, the formula is 0.25 gallon per second, and a properly functioning 1.0-gallon (3.8 L) urinal valve also does not cycle longer than four seconds.
The United States federal program states that the cycle of a 1.6-gallon toilet or a 1.0-gallon urinal should not exceed four to five seconds. In liters:
where is the cycle time from triggering until the valve closes (s). This formula is a rough estimate for ordinary supply pressure; if the result is far above the rated volume, the diaphragm or piston insert is replaced.
Periodic maintenance and inspection
Maintenance of sensor restrooms, compiled from the WaterSense guidance and the United States federal program:
| Part | Check | Interval |
|---|---|---|
| Flushometer valve | inspect diaphragm or piston, measure cycle time, replace worn parts | at least once a year |
| Control stop at the flushometer valve | fully open in normal operation; used to shut off water during maintenance | periodically |
| Volume adjustment screw | unchanged from the installation setting | periodically |
| Toilet and urinal sensors | adjust so there are no double or phantom flushes | at least once a year |
| Faucet aerator | not missing, not scaled; clean or replace | periodically |
| Faucet supply pressure | between 20 and 80 psi (138 to 552 kPa) | at testing or on complaint |
The faucet flow rate is checked with a timer and a container of known volume, for example a measuring cup or a flow bag. Some aerators need a special key, so maintenance staff are given the right tools and training. Users and cleaning staff are asked to report any toilet, urinal, or faucet that keeps running, leaks, or does not work, and signs tell users not to flush wet wipes, sanitary products, or trash.
A non-water urinal is a urinal that carries urine through a trap seal to the drain without flush water, usually with a cartridge containing a liquid sealant that keeps odors and sewer gas from escaping. The cartridge and sealant are cleaned and replaced on the manufacturer’s schedule. Water and other liquids are not poured into such a urinal, because they can rinse out the sealant. Because no water pushes sediment along, the United States plumbing codes cited by EPA require at least one water-using fixture, for example a washbasin, upstream on the drain of a non-water urinal, and EPA suggests flushing the drain now and then with a bucket of water. Odor from a non-water urinal often means a saturated cartridge or depleted sealant; traps and vents are covered in Chapter 6.
Worked example
The figures in the examples below are practice figures, unless their origin is stated.
Example 1: a toilet flushometer valve with too long a cycle. The toilet in the opening case is rated 6.1 L and cycles for 9 seconds. Its estimated volume is L, which is times the rated volume. A properly functioning valve cycles no longer than 4 seconds, that is L, slightly above 6.1 L because the formula is an estimate. In gallons, gallons or L, the same result. The diaphragm or piston insert is inspected and replaced with an insert rated 6.1 L, then the cycle time is measured again.
Example 2: a 1.9 L urinal cycling for 6 seconds. A urinal rated 1.9 L should cycle for about seconds. A 6-second cycle means L, three times the rated volume. If the urinal is used 150 times a day, the excess is L per day. A clogged bypass hole and a wrongly rated diaphragm are the first suspects.
Example 3: phantom flushes overnight. The six 1.9 L urinals in the opening case flush by themselves every 4 minutes from 22:00 to 06:00, that is minutes. Each urinal flushes times, so the six of them waste L, about 1.37 m³, which matches the submeter reading of about 1.4 m³. If this happens every night, a year wastes m³, or at a practice tariff of Rp20,000 per m³ about rupiah. The sensor windows are cleaned, the detection range is reset according to the manual, and the urinals are observed for an hour with the room empty.
Example 4: replacing 3.8 L urinals with 1.9 L. The men’s restroom in the lobby serves an average of 300 urinal uses per day, 365 days a year. The old use is L and the new use is L, so the saving is L, about 208 m³ per year. This saving is achieved only if the urinals and their valves have the same rating and the sensors do not cause phantom flushes; 120 phantom flushes per night on a single urinal already use L, about 40 percent of that saving.
Example 5: old faucets and 1.9 L/min faucets. Six public restroom faucets serve 500 handwashes per day with water running for 15 seconds each time, that is 0.25 minute. Old 8.3 L/min faucets use L per day, and 1.9 L/min faucets use L per day. The saving is L per day, or m³ per year. If the sensor is left to run for another 3 seconds after the hands are withdrawn, the extra use is L per day.
Example 6: battery life and phantom flushes. The manual of a urinal states that its battery pack lasts for about 150,000 actuations. With 120 uses a day, the battery life is days, about years. If the sensor also phantom-flushes 120 times every night, actuations become 240 per day and battery life drops to days, about 1.7 years. Phantom flushes use up water and batteries at the same rate, so a battery replacement record with shrinking intervals is a sign that the sensor needs checking.
Stop conditions
- The floor is wet or water is dripping near a hand dryer, adapter, socket outlet, or sensor fixture cable: do not touch the appliance and do not stand in the puddle to unplug it; ask the designated person to disconnect the supply at a panel outside the wet room, and hand over to an authorized electrical technician (Chapter 37 · Electrical & Control on wet rooms).
- The hand dryer smells burnt, its casing is hot, it sparks, or its cable is stripped: stop using it, put up a sign, and hand over to an electrical technician; the casing is not opened by the building technician.
- The flushometer valve keeps running and its control stop cannot close, leaks, or is stuck: do not force the valve or take apart the pressurized valve body; close the zone isolation valve according to the building procedure if designated to do so, then hand over to a plumber (Chapter 12 on valves and water control).
- A toilet or urinal overflows, sewage rises from a floor drain, or there are signs of backflow: close the room to users, wear gloves and protection, and hand over to a plumber (Chapter 15 on plumbing maintenance and diagnosis).
- A battery is leaking, swollen, or hot, or the battery compartment is corroded and wet: do not reuse it and do not short-circuit it; collect it as hazardous waste (B3) under Chapter 35 · Water & Water Treatment.
- The repair would call for an insert or valve with a volume different from the bowl rating, a volume setting above the factory value, or replacement of the toilet or urinal: stop; the decision belongs to the plumbing designer and the manufacturer, the installation to a plumber.
- Faucets, aerators, or flow devices in patient areas of a hospital or senior care facility are due to be replaced: postpone until the infection prevention team approves (Chapter 13 on hot water and Legionella control).
Common misinterpretations
Guess what’s wrong first, then open the explanation.
Common misconception
Automatic sensors save water.
Why is it wrong?
EPA states that sensors on toilets and urinals add no water savings; their benefit is hygiene. Poorly maintained sensors instead raise use through phantom flushes, and sensor faucets open fully.
Common misconception
A longer flush makes the toilet cleaner.
Why is it wrong?
Volume above the bowl rating only wastes water. A clean bowl and drain depend on matching valve and bowl, supply pressure, and a sound insert.
Common misconception
The manual flush button is the same as a normal flush.
Why is it wrong?
The button can release a larger volume, so staff make sure the urinal returns to its original volume after cleaning.
Common misconception
Non-water urinals need no maintenance.
Why is it wrong?
The cartridge and sealant must be replaced on schedule, water must not be poured into them, and their drain needs rinsing now and then.
Common misconception
Hand dryers are certainly more hygienic than towels, or the reverse.
Why is it wrong?
According to CDC, the best way to dry hands remains unclear; what is certain is that hands need drying with a clean towel or in the air.
Links to other chapters
Chapter 7 on fixtures and appliance connections covers the faucets, stop valves, and hoses that supply the fixtures in this chapter, and Chapter 12 covers the isolation and pressure-reducing valves that set the pressure at the flushometer valve. Water wasted by phantom flushes shows up in the submeter and water balance of Chapter 40 · Water & Water Treatment, and blockages and odors from toilets and urinals are traced in Chapter 15 and Chapter 6. Spent batteries go to Chapter 35 · Water & Water Treatment on hazardous waste (B3), adapters and hand dryers in wet rooms follow Chapter 37 · Electrical & Control, and hospital faucets relate to Legionella control in Chapter 13.
Exercises and worked solutions
The figures in the exercises are for practice.
Try to answer first, then open the worked solution.
A toilet flushometer valve rated 6.1 L cycles for 5 seconds. What is its estimated volume, and what is the action?
Check my answer
See the worked solution
The estimate is L, about 1.3 times the 6.1 L rating, and the cycle exceeds the four-second limit. The diaphragm or piston insert and its bypass hole are inspected, and a worn insert is replaced with one of the same rating.
A 3.8 L urinal flushes by itself every 10 minutes for 12 hours with no users. How much water is wasted?
Check my answer
See the worked solution
In 12 hours there are phantom flushes, so L is wasted. This figure is compared with the night submeter reading, then the sensor window and detection range are checked.
Why can replacing a flush handle with a sensor not be recorded as a water-saving project?
Check my answer
See the worked solution
A sensor does not change the volume of each flush, so the volume per use stays the same; EPA names hygiene as its benefit. If the sensor causes double or phantom flushes, use actually rises, so savings come only from a smaller flush volume.
A sensor faucet in a public restroom fills a 1 L container in 25 seconds. What is its flow rate, and what is checked?
Check my answer
See the worked solution
Its flow rate is L/min, above the 1.9 L/min limit for public faucets under the United States standard cited by EPA. The aerator is checked for being missing, the wrong size, or damaged, and the supply pressure is checked to still be between 20 and 80 psi.
A non-water urinal in the lobby restroom smells even though the floor is clean. What is checked, and what must cleaning staff not do?
Check my answer
See the worked solution
The cartridge and sealant are probably saturated or depleted, so they are replaced on the manufacturer’s schedule, and the drain is rinsed if needed. Staff do not pour water or cleaning liquid into the urinal, because it can rinse out the sealant and make the odor worse.
Cleaning staff report a puddle under the hand dryer and the sensor faucet adapter. What does the technician do?
Check my answer
See the worked solution
The technician does not touch the appliances and does not stand in the puddle to unplug the adapter, because water and the utility supply are in the same place. The designated person disconnects the supply at a panel outside the wet room, the room is closed temporarily, and an authorized electrical technician then inspects the source of the water and the adapter.
References
External sources
- WaterSense at Work: Sanitary Fixtures and Equipment, 3.1 Toilets (Water Closets)epa.gov
- WaterSense at Work: Sanitary Fixtures and Equipment, 3.2 Urinalsepa.gov
- WaterSense at Work: Sanitary Fixtures and Equipment, 3.3 Faucetsepa.gov
- Best Management Practice #6: Toilets and Urinalsenergy.gov
- Best Management Practice #7: Faucets and Showerheadsenergy.gov
- About Handwashingcdc.gov
- Handwashing Factscdc.gov
Revision history
| Date | Version | Change |
|---|---|---|
| November 15, 2026 | 1 | First published |
How to cite
Kurnia (2026). Public restrooms with sensors: toilets and urinals with flushometer valves, infrared sensors and solenoid valves, automatic faucets and hand dryers, batteries and power supply, water saving, and maintenance. ARSTEMA Academy. Revised November 15, 2026. arstema.com/en/academy/konsep/toilet-umum-bersensor-kloset-dan-urinal-dengan-katup-gelontor-sensor-inframerah-dan-katup-solenoid-keran-dan-pengering-tangan-otomatis-baterai-dan-catu-daya-penghematan-air-serta-perawatan
Self-check · 3 questions
Check your understanding before moving on
Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.
A toilet flushometer valve rated 6.1 L cycles for 5 seconds. What is its estimated volume, and what is the action?
A 3.8 L urinal flushes by itself every 10 minutes for 12 hours with no users. How much water is wasted?
Why can replacing a flush handle with a sensor not be recorded as a water-saving project?
Nearby chapters
Reading order by shelf: Buildings & Facilities · Chapter 46.
Reading order by shelf: Buildings & Facilities · Chapter 44.