    Used cooking oil, grease, and used oil

    sources in kitchens and workshops, collection and containers, storage and fire hazards, spills, handover to licensed parties, and records

    In a single week, a hotel had two incidents: the kitchen grease interceptor overflowed after used cooking oil was poured into a sink, and a drum of used oil from a generator oil change leaked in the workshop next to a pile of cleaning rags. This chapter covers used oils from the building technician’s side: distinguishing used cooking oil and kitchen grease from used machine oil under the EPA definition, why neither may go into drains, containers and collection, storage with secondary containment and fire hazards including oily rags, the EPA spill steps, and handover to licensed parties and balance records. Used oil is treated as hazardous waste in line with the annexes of Permenkes 7/2019 and 2/2023 (their status as of November 2026 is noted), while the classification of used cooking oil is to be confirmed with the environmental agency. Data from the United States and England are marked as data from those countries.

    Section you’re reading: Chapter opening

    In the same week, a hotel had two small incidents. On Tuesday night, a dishwasher poured oil from a fryer that had cooled somewhat into a sink and rinsed it with hot water. On Thursday morning the kitchen grease interceptor overflowed, the dishwashing room floor was flooded, and a foul smell drifted into the restaurant. On Friday, a workshop technician found a drum of used oil from a generator oil change seeping onto the concrete floor, right next to an open bin of rags used to wipe machines. Both incidents came from similar material, oil that had already been used, but their disposal routes, rules, and hazards are different.

    Scope

    This chapter covers used oils that arise in hotels, restaurants, hospitals, and laundries: used cooking oil and grease from the kitchen, and used oil and oil filters from the building workshop, generators, compressors, and machines. For used oil, this chapter uses the annex of Permenkes 7/2019 (Minister of Health Regulation) on hospital environmental health and the annex of Permenkes 2/2023 on environmental health, which classify used oil as hazardous waste (Indonesian limbah B3). As of November 2026, Permenkes 3/2026 revokes both regulations except for a number of articles together with their annexes, while the JDIH Kemenkes pages (the Ministry of Health legal documentation network) mark both as not in force; check their latest status before using them for an audit. The classification of used cooking oil from commercial kitchens in waste regulations cannot yet be confirmed as of November 2026; ask the local environmental agency before choosing a collector.

    Topics in other chapters: grease interceptors and their pump-out in Chapter 15 · Buildings & Facilities on plumbing maintenance; oil filtration, fryer draining, and the hazards of hot oil in Chapter 2 · Commercial Kitchens on commercial gas fryers; hoods and grease filters in Chapter 16 · Buildings & Facilities on kitchen ventilation; fire classes and portable fire extinguishers (Indonesian alat pemadam api ringan, APAR) in Chapter 17 · Buildings & Facilities on fire protection; engine oil and its viscosity in Chapter 20 · Automotive & Electric Mobility on car engine cooling and lubrication; labels, safety data sheets, and spill kits in Chapter 6 · Safety on chemicals in technicians’ work; storage areas, storage periods, balances, and manifests for hazardous waste in Chapter 35 on hazardous waste in hotels, laundries, and workshops; and other kitchen waste in Chapter 33 on waste in hotels, laundries, and kitchens.

    Changing the oil and oil filters on generators, compressors, or vehicles is done by an assigned technician following the machine manual and the building work permit. Transporting and processing used oil is work for licensed parties. The building technician collects, labels, stores, handles small spills, keeps records, and hands over.

    Types and sources of used oils

    Used cooking oil is vegetable frying oil or animal fat that has been used for frying or cooking and will not be used again. It comes from fryers, large woks, and grills with drip trays. Kitchen fats, oils, and grease are the oils and fats carried by dishwashing water, sauce residue, and the cleaning of hood filters; most of them are caught in the grease interceptor together with water and solids (Chapter 15 · Buildings & Facilities on plumbing maintenance). Used cooking oil is collected as a liquid before it reaches the sink, while the contents of the grease interceptor are pumped out together with their water.

    Used oil, under the EPA definition, is any oil that has been refined from crude oil or any synthetic oil that has been used and as a result of such use is contaminated by physical or chemical impurities, such as metal scrapings, dirt, water, or chemicals. The EPA reference table includes engine oil, transmission fluid, refrigeration oil, compressor oils, and hydraulic fluid in used oil, and excludes vegetable and animal oil, antifreeze, kerosene, and petroleum distillates used as solvents. That is a United States definition, but the distinction is useful in any building: used cooking oil and used oil are two streams that are not mixed.

    In Indonesia, the annex of Permenkes 7/2019 lists used oil and used oil filters among the types of hazardous waste produced by hospitals, together with spent batteries, spent lamps, and empty chemical containers. Hotels and laundries produce the same types from their workshops, so this chapter treats used oil in any building as hazardous waste whose route follows Chapter 35 on hazardous waste in hotels, laundries, and workshops.

    SourceTypeRoute
    Fryers, woks, grill drip traysused cooking oilused cooking oil container, used cooking oil collector
    Dishwashing water, hood filterskitchen greasegrease interceptor, grease interceptor pump-out contractor
    Generators, air compressors, pumps, building vehiclesused oil and oil filtersused oil container, hazardous waste route
    Elevators, hydraulic trolleys, lift tablesused hydraulic fluidused oil container, hazardous waste route
    Rags, sorbent padsoily clothclosed metal container; route according to the type of oil

    The EPA asks that used oil not be mixed with anything and be stored separately from all solvents and chemicals, because used oil mixed with hazardous waste can become subject to hazardous waste rules, a lengthy, costly, and strict regulatory process. The same principle applies to used cooking oil: used cooking oil mixed with machine oil, soapy water, or cleaners can be rejected by the used cooking oil collector.

    Why not into drains and soil

    Used cooking oil poured into a sink does not disappear. The oil cools in the pipe, mixes with food residue and soap, and then hardens into lumps that narrow the pipe and fill the grease interceptor long before its pump-out schedule. The annex of Permenkes 2/2023 requires the kitchen drain of food handling establishments to be fitted with a grease trap, and requires wastewater from the nutrition kitchen and canteen of health care facilities with a high oil and grease content to receive pretreatment in the form of a grease trap. A grease interceptor is designed for residual grease in dishwashing water, not for holding frying oil.

    The English workplace waste separation guidance states that cooking fats, oils, and greases can be collected with food waste for small amounts or through a used cooking oil collection, and that cooking oil must never be put down the drain. That is an English rule, but the reasons are the same in Indonesia.

    Used oil is more dangerous to water. The EPA states that used oil from one oil change can contaminate one million gallons of fresh water, a year’s supply for 50 people, and that used motor oil is insoluble, persistent, slow to degrade, sticks to beach sand and bird feathers, and can contain toxic chemicals and heavy metals. Oil that drips onto the ground in the workshop yard is carried by rain into the stormwater drain, which usually leads straight to a river without treatment.

    The amount of used oil is calculated from its volume and converted to mass with its density:

    m=ρ×Vm = \rho \times V

    where mm is the mass of used oil (kg), ρ\rho the density (kg/L), and VV the volume (L). The 2016 EPA conversion factor table records fats, oils, and grease at 412 pounds per 55-gallon drum and used motor oil at 7.4 pounds per gallon (United States data), equivalent to about 0.898 kg/L and 0.887 kg/L. Mass is needed because collectors and hazardous waste records usually use kilograms.

    Collection and containers

    Used cooking oil is moved from the fryer once it has cooled enough according to the appliance manual, into a heat-resistant metal container with a lid, as explained in Chapter 2 · Commercial Kitchens on commercial gas fryers. Once cool, the oil can be poured into a larger collection container, for example a jerry can or a drum with a screw cap supplied by the collector. The collection container meets several conditions: tightly closed, leak-free, clean and dry, never used for chemicals, labeled “used cooking oil,” and not filled to the top, so that there is headspace above the liquid for pouring and moving it without spilling. Crumbs and frying residue are strained out first so that they do not rot at the bottom of the container.

    The number of containers is calculated from the volume collected during the pickup interval:

    n=⌈Vcollϕ×Vcont⌉n = \left\lceil \frac{V_{coll}}{\phi \times V_{cont}} \right\rceil

    where nn is the number of containers, VcollV_{coll} the volume of used oil collected during the pickup interval (L), ϕ\phi the portion of the container volume that may be filled (dimensionless), and VcontV_{cont} the nominal volume of one container (L). The collected volume of used cooking oil depends on the number and capacity of the fryers, how often the oil is changed, and the portion of the oil that can be drained; the rest is absorbed by food or left in the appliance.

    For used oil, the EPA requires all containers and tanks to be labeled “Used Oil,” kept in good condition without rust, leaks, or deterioration, and requires used oil never to be stored in anything other than tanks and containers. In Indonesia, hazardous waste labels and symbols follow Chapter 35 on hazardous waste in hotels, laundries, and workshops. Used oil filters contain a fair amount of oil; the EPA describes the common practice of puncturing and draining the filters, collecting their oil with the used oil, and then recycling the filters as scrap metal. In the building, filter draining is done by the workshop technician at the time of the oil change, and drained filters are stored in a separate closed container.

    Funnels, catch buckets, and drip trays for the kitchen and the workshop are kept separate, and empty chemical containers are not used for used cooking oil or used oil.

    Storage and fire hazards

    Cooking oil and machine oil do not ignite as easily as gasoline at room temperature, but both burn fiercely once alight and feed other fires. The English fire risk assessment guidance for sleeping accommodation includes cooking oils among the fuels commonly found in such premises, notes that flammable liquids in plastic containers are a problem in a fire because the containers melt and spill their contents, and asks for combustible materials to be stored away from ignition sources and not in escape routes. Storage for used cooking oil and used oil is therefore chosen away from stoves, grills, electrical panels, boilers, and welding work, in an area that guests do not pass through, protected from rain and direct sunlight, and not blocking exit doors.

    Oily rags and pads are a hazard of their own. Vegetable oil on cloth reacts slowly with oxygen and gives off heat; in a pile that cannot shed that heat, the temperature can rise until the cloth ignites on its own hours later. The same English guidance notes that cleaning cloths and mop heads placed in dryers can spontaneously combust if there is any chemical residue left on them, and shows a fire-resisting metal pedal bin for rags contaminated with solvent. For a hotel, this means oily rags are collected in a closed metal container and emptied every day, and oily kitchen linen is handled according to the laundry procedure in Chapter 15 · Laundry on drying and finishing.

    In the kitchen, a cooking oil fire is not extinguished with water, because the water sinks and instantly boils under the hot oil and then throws out the burning oil (Chapter 17 · Buildings & Facilities on fire protection). The English guidance classes cooking oil fires as class F, says that extinguishers for that class are suitable for commercial kitchens with deep-fat fryers, states that foam extinguishers are not suitable for deep-fat fryers, and asks for extract ducting, grease traps, and filters to be cleaned and maintained regularly. Fire class letters differ between standards; the ones used in a building follow the APAR label and the applicable regulations.

    Secondary containment is a tray or bund under drums and jerry cans that holds the contents if a container leaks. The EPA requires secondary containment for used oil processors, re-refiners, transfer facilities, and burners, and encourages it for used oil generators. The annex of Permenkes 2/2023 requires liquid hazardous waste such as used oil in the temporary storage area of health care facilities to be placed in leak-proof drums on an impermeable floor fitted with a drain and a bund to hold spills. The bund height of the secondary containment is calculated from the volume it must hold:

    h=VholdAbund−Aconth = \frac{V_{hold}}{A_{bund} - A_{cont}}

    where hh is the liquid height inside the containment (m), VholdV_{hold} the volume that must be held (m³), AbundA_{bund} the inside floor area of the containment (m²), and AcontA_{cont} the footprint of the containers standing inside it (m²). The container footprint is subtracted because spilled liquid only fills the space around the containers. The size of VholdV_{hold}, for example the whole contents of the largest container plus a margin, is set according to the applicable rules together with the person responsible for hazardous waste.

    Spills

    The EPA gives an order for dealing with leaks and spills of used oil. This order is also useful for used cooking oil:

    1. Stop the oil from flowing at the source. If a leak from a container cannot be stopped, transfer the oil to another container.
    2. Contain the spill, for example with a berm of sorbent material or by spreading sorbent over the oil.
    3. Clean up the oil and manage it as the used oil it was before it spilled.
    4. Remove, repair, or replace the damaged container immediately.

    The EPA also requires sorbent materials to be available on site. Rags and sorbent materials that still contain free-flowing oil are handled under the used oil rules, and all oil collected during cleanup is handled as used oil. For used oil in Indonesia, those spent sorbents go into the hazardous waste route in Chapter 35. Spill kits and personal protective equipment are covered in Chapter 6 · Safety on chemicals in technicians’ work.

    An oil spill on a kitchen floor adds a slipping hazard. A floor made slippery by oil is not cleaned by spraying water and soap into the floor drain, because that moves the oil into the grease interceptor and the pipes. The oil is absorbed first, the sorbent is collected into a closed container, and only then is the floor cleaned. Used cooking oil that is still hot is left alone and cordoned off until it cools; nobody walks through it.

    The spill volume gives an idea of how much sorbent is needed. The oil layer on the floor has a thickness t=V/At = V/A, where VV is the spill volume and AA the area covered, and the sorbent mass is roughly VV divided by the sorbent’s absorption capacity per kilogram stated on its data sheet.

    Handover to licensed parties and records

    Used cooking oil and used oil are handed over to parties that actually process or use them. The EPA names several ways to use used oil: re-refining into lubricating base stock, which is the preferred option because it closes the loop with the same product, insertion into a petroleum refinery, and processing into fuel, which is less preferable because the oil is used only once more. In Indonesia, used oil as hazardous waste is handed over to licensed transporters and processors or users, with the documents covered in Chapter 35 on hazardous waste in hotels, laundries, and workshops.

    For used cooking oil, the hotel chooses a collector that can state the intended use and issue a receipt. The contract states the volume or mass, the pickup frequency, the condition of the containers, and a prohibition on reselling the used cooking oil as frying oil. The classification and licensing of used cooking oil collectors are to be confirmed with the environmental agency, as noted in the Scope.

    Records are the evidence that used oil has not disappeared into drains or been sold quietly. For used oil transporters, processors, burners, and marketers, the EPA requires records of each acceptance and delivery to be kept for three years (a United States rule). The hotel record contains at least the date, source, type of oil, volume or mass, container number, recipient name, and receipt number. The record is checked with an oil balance, a comparison between the oil that comes in and the oil that goes out:

    Vdiff=Vbuy−ΔS−Vout−VlossV_{diff} = V_{buy} - \Delta S - V_{out} - V_{loss}

    where VdiffV_{diff} is the oil that cannot be accounted for (L), VbuyV_{buy} the new oil purchased in the period (L), ΔS\Delta S the increase in the new oil stock in the storeroom (L, negative if the stock falls), VoutV_{out} the used oil handed over or still stored as used oil (L), and VlossV_{loss} the portion that is genuinely absorbed by food, burned, or left in the machines based on previous months’ experience (L). A difference that suddenly grows is a signal to investigate, not proof that someone is at fault.

    Worked example

    The numbers in the examples below are practice numbers, unless their origin is stated.

    Example 1: used cooking oil per week. The kitchen has three fryers holding 25 L each, and the oil is changed twice a week. The portion that can be drained is 85 percent. The collected volume is V=3×25×2×0.85=127.5V = 3 \times 25 \times 2 \times 0.85 = 127.5 L per week. With a density of 0.898 kg/L from the EPA value for fats, oils, and grease, the mass is 0.898×127.5=114.50.898 \times 127.5 = 114.5 kg per week.

    Example 2: number of jerry cans. The collector supplies 20 L jerry cans that are filled to at most 90 percent, that is, 18 L. If the used cooking oil is picked up every week, n=⌈127.5/18⌉=8n = \lceil 127.5/18 \rceil = 8 jerry cans. If it is picked up every two weeks, n=⌈255/18⌉=15n = \lceil 255/18 \rceil = 15 jerry cans. Each jerry can holds about 18×0.898=16.218 \times 0.898 = 16.2 kg, so the jerry cans are moved with a trolley and not stacked higher than can be lifted safely.

    Example 3: a year of used generator oil. The building has three generators with 40 L oil pans, and according to the maintenance schedule their oil is changed six times a year. If 95 percent of the oil can be drained, V=3×40×6×0.95=684V = 3 \times 40 \times 6 \times 0.95 = 684 L per year. With 0.887 kg/L from the EPA value for used motor oil, the mass is 684×0.887=607684 \times 0.887 = 607 kg. A 200 L drum filled to 90 percent holds 180 L, so ⌈684/180⌉=4\lceil 684/180 \rceil = 4 drums are needed per year. Drained oil filters are recorded separately; the EPA records one drum of uncrushed filters at about 175 pounds, or 79 kg.

    Example 4: bund height of a secondary containment. Two 200 L used oil drums stand in a containment with inside dimensions of 1.5 m by 1.2 m. The person responsible for hazardous waste specifies that the containment must hold the whole contents of one drum, that is, 0.2 m³. The drum diameter is 0.58 m, so the footprint of two drums is 2×π×0.292=0.5282 \times \pi \times 0.29^2 = 0.528 m². The free area is 1.8−0.528=1.2721.8 - 0.528 = 1.272 m², and the liquid height is h=0.2/1.272=0.157h = 0.2/1.272 = 0.157 m. The bund is made higher than 16 cm, because the liquid inside the containment must not reach its rim when it sloshes.

    Example 5: used cooking oil balance. In one month the kitchen buys 600 L of frying oil, the storeroom stock does not change, and 270 L of used cooking oil is handed over. The portion absorbed by food and left in the appliances is 600−270=330600 - 270 = 330 L, or 330/600=0.55330/600 = 0.55; this figure becomes the reference. The next month the purchases and menu are the same, but only 150 L of used cooking oil is handed over. With Vloss=330V_{loss} = 330 L, Vdiff=600−0−150−330=120V_{diff} = 600 - 0 - 150 - 330 = 120 L. The technician checks the grease interceptor pump-out records and the used cooking oil containers before drawing any conclusion, because the 120 L of missing oil may have gone into the drains.

    Example 6: a jerry can spill in the kitchen. A jerry can holding 20 L of used cooking oil falls and its contents spread over 4 m² of floor. The layer thickness is t=20/4=5t = 20/4 = 5 L/m², that is, 5 mm. A sorbent that, according to its data sheet, absorbs 1 L of oil per kg requires about 20 kg. The spent sorbent holds roughly 20×0.898=1820 \times 0.898 = 18 kg of oil, so the collected mass is about 38 kg and is divided into several bags or containers so that it can be lifted.

    Stop conditions

    1. The oil in a fryer or container is still hot, smoking, or has not yet reached the draining temperature in the appliance manual: do not pour or move it; wait for it to cool and leave the decision to the head chef (Chapter 2 · Commercial Kitchens on commercial gas fryers).
    2. A fire in a fryer, wok, used cooking oil container, or oil spill: do not throw water on it; turn off the heat source if safe, use an APAR suited to it according to its label or a fire blanket only if trained, sound the alarm, and hand over to the emergency response team and the fire department (Chapter 17 · Buildings & Facilities on fire protection).
    3. A spill has entered a floor drain, stormwater drain, gutter, or open ground, or is larger than the spill kit can handle: stop the flow at the source if safe, cover the drain opening with sorbent, keep people away, and report to the person responsible for hazardous waste or the building’s environmental officer, who contacts the environmental agency if the spill leaves the site.
    4. A used oil drum or jerry can is leaking, rusted, bulging, or unlabeled: stop using that container, catch the leak, and ask the person responsible for hazardous waste to transfer its contents to a sound container and label it.
    5. Used oil is mixed with solvent, gasoline, chemicals, or a large amount of water, or the origin of a container’s contents is unknown: do not pour it into another used oil drum; set it apart, mark it “contents unknown,” and hand it over to the person responsible for hazardous waste (Chapter 35 on hazardous waste in hotels, laundries, and workshops).
    6. A pile of oily rags, sorbent pads, or linen feels warm, is smoking, or smells of burning, in a bin, trolley, or dryer: do not break up the pile; keep people away, sound the alarm, and hand over to the emergency response team (Chapter 17 · Buildings & Facilities on fire protection).
    7. A collector of used cooking oil or used oil cannot show a license, receipt, or the requested documents: postpone the handover and report to the engineering manager or the environmental officer.
    8. Used oil containers are found in an escape route, near a heat source or welding work, or the secondary containment is already full: stop adding to that place and report to the chief technician for relocation or an extra pickup.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    Used cooking oil may be poured into the sink as long as it is rinsed with hot water and soap.

    Why is it wrong?

    Hot water and soap only carry the oil farther before it cools and hardens in the pipe or the grease interceptor. Used cooking oil is collected as a liquid in a container.

    Common misconception

    Used cooking oil and used oil are both oil, so they may be mixed in one drum.

    Why is it wrong?

    They are different streams. Used oil is hazardous waste, and used cooking oil mixed with used oil can be rejected by used cooking oil collectors and adds to the amount of hazardous waste.

    Common misconception

    The grease interceptor is the place to dispose of used cooking oil.

    Why is it wrong?

    A grease interceptor catches residual grease in dishwashing water. Large amounts of frying oil fill it quickly and make it overflow.

    Common misconception

    Oily rags are safe once they have been washed and dried.

    Why is it wrong?

    Residual oil or chemicals left on the cloth can self-heat after drying if the cloth is piled while hot. Oily rags are collected in a closed metal container and handled according to the laundry procedure.

    Common misconception

    The collector that pays the most is the best choice.

    Why is it wrong?

    Price does not guarantee the intended use. What is assessed first is the license, the receipt, and the processing destination, especially for used oil as hazardous waste.

    The pump-out and sizing of grease interceptors are in Chapter 15 · Buildings & Facilities on plumbing maintenance, and the oil and grease load in kitchen wastewater in Chapter 16 on wastewater characteristics. Draining oil from a fryer and its temperature limit are in Chapter 2 · Commercial Kitchens on commercial gas fryers. Storage, storage periods, balances, and manifests for hazardous waste, including used oil and spent sorbents, are covered in Chapter 35 on hazardous waste in hotels, laundries, and workshops. Food waste and other kitchen waste are calculated in Chapter 33 on waste in hotels, laundries, and kitchens.

    Exercises and worked solutions

    Try to answer first, then open the worked solution.

    1. A hotel restaurant has two fryers holding 18 L each whose oil is changed three times a week, and 80 percent of the oil can be drained. How many liters and kilograms of used cooking oil are produced per week?

      Check my answer
      See the worked solution

      The volume is 2×18×3×0.8=86.42 \times 18 \times 3 \times 0.8 = 86.4 L per week, and the mass is 86.4×0.898=77.686.4 \times 0.898 = 77.6 kg. The mass is calculated because collectors and records usually use kilograms, while fryers are measured in liters.

    2. Why must an empty floor cleaner jerry can not be used for used cooking oil, even after rinsing?

      Check my answer
      See the worked solution

      Leftover chemical residue contaminates the used cooking oil, so the collector can reject it and that oil has to be handled as mixed waste. A used cooking oil container must be clean, dry, and never used for chemicals.

    3. The hotel workshop produces 300 L of used oil a year. How many 200 L drums filled to 90 percent are needed, and what is the mass?

      Check my answer
      See the worked solution

      One drum holds 180 L, so ⌈300/180⌉=2\lceil 300/180 \rceil = 2 drums. The mass is 300×0.887=266300 \times 0.887 = 266 kg, and this mass is the figure entered in the hazardous waste record.

    4. One 200 L used oil drum stands in a containment with inside dimensions of 1.0 m by 1.0 m. What is the liquid height if the whole drum spills?

      Check my answer
      See the worked solution

      The free area is 1.0−π×0.292=0.7361.0 - \pi \times 0.29^2 = 0.736 m², so h=0.2/0.736=0.272h = 0.2/0.736 = 0.272 m. The bund must be higher than 27 cm; if that is impractical, a larger containment is chosen so that the bund can be lower.

    5. A technician is about to clean a workshop floor stained with oil by spraying water into the yard drain. What is your response?

      Check my answer
      See the worked solution

      The water would carry the oil into the stormwater drain, which usually leads straight to a river, and oil does not dissolve in water. The oil is absorbed first with sorbent, the spent sorbent is handled as hazardous waste, and the yard drain is covered during cleaning.

    6. A kitchen’s used cooking oil balance over three months shows differences of 10, 15, and 95 L. What does the technician do?

      Check my answer
      See the worked solution

      Differences of 10 and 15 L are within normal variation, but 95 L deviates far from the pattern of the two previous months. The technician checks the purchase, stock, handover, and grease interceptor pump-out records before drawing conclusions, because the rise in the difference is a signal to investigate, not proof that someone is at fault.

    References

    External sources

    • Peraturan Menteri Kesehatan Nomor 2 Tahun 2023 tentang Peraturan Pelaksanaan Peraturan Pemerintah Nomor 66 Tahun 2014 tentang Kesehatan Lingkunganjdih.kemkes.go.id
    • Peraturan Menteri Kesehatan Nomor 7 Tahun 2019 tentang Kesehatan Lingkungan Rumah Sakitjdih.kemkes.go.id
    • Peraturan Menteri Kesehatan Nomor 3 Tahun 2026 tentang Penanggulangan Penyakitjdih.kemkes.go.id
    • Managing Used Oil: Answers to Frequent Questions for Businessesepa.gov
    • Managing, Reusing, and Recycling Used Oilepa.gov
    • Volume-to-Weight Conversion Factorsepa.gov
    • Simpler recycling: workplace recycling in Englandgov.uk
    • Fire safety risk assessment: sleeping accommodation (accessible)gov.uk

    Revision history

    DateVersionChange
    November 11, 20261First published

    How to cite

    Kurnia (2026). Used cooking oil, grease, and used oil: sources in kitchens and workshops, collection and containers, storage and fire hazards, spills, handover to licensed parties, and records. ARSTEMA Academy. Revised November 11, 2026. arstema.com/en/academy/konsep/minyak-jelantah-lemak-dan-oli-bekas-sumber-di-dapur-dan-bengkel-pengumpulan-dan-wadah-penyimpanan-dan-bahaya-kebakaran-tumpahan-penyerahan-ke-pihak-berizin-serta-catatan

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated
    1

    A hotel restaurant has two fryers holding 18 L each whose oil is changed three times a week, and 80 percent of the oil can be drained. How many liters and kilograms of used cooking oil are produced per week?

    2

    Why must an empty floor cleaner jerry can not be used for used cooking oil, even after rinsing?

    3

    The hotel workshop produces 300 L of used oil a year. How many 200 L drums filled to 90 percent are needed, and what is the mass?

    Self-assessment progress0%