Skip to content

Search ARSTEMA

Type a chapter, term, symptom, or tool.

    Water & Water Treatment · Chapter 36Applied

    By Kurnia · Published November 11, 2026 · Version 1 · 21 min read

    Hospital medical waste

    waste types and segregation, container color codes, sharps and infectious waste, internal transport and storage, treatment by autoclave and incinerator, and the limits of the work

    On a Saturday night, the refrigeration unit of a hospital’s infectious waste cold room stops and the room temperature rises from below 0 °C to 5 °C, although the oldest waste has already been there for five days. This chapter covers solid medical waste from the building technician’s side: waste types and their segregation, container color codes, sharps and infectious waste, trolleys and internal transport routes, the temporary storage facility and storage time limits by temperature, and autoclaves and incinerators from the infrastructure side and their records. The technical provisions come from the annexes of Permenkes 2/2023 and 7/2019, which as of November 2026 are excepted from revocation by Permenkes 3/2026, together with PP 28/2024 and WHO guidance. Clinical action, exposure management, operating waste autoclaves and incinerators, radioactive waste, and transport off the hospital site are work for designated staff, licensed operators, radiation protection officers, and licensed transporters.

    High-risk material

    This material involves real hazards. A concept explanation doesn’t replace site procedures, competency, energy isolation, the latest SDS, or a work permit.

    Section you’re reading: Chapter opening

    On a Saturday night, the technician on duty at a hospital receives an alarm from the cold room in the medical waste temporary storage facility. The compressor of the refrigeration unit has stopped, and the room temperature, normally below 0 °C, has already risen to 5 °C. Inside are yellow bags of infectious waste from the last five days, and the licensed transporter is not scheduled to come until Wednesday. The technician can repair the refrigeration unit, but the decision about the waste depends on the rule that links storage temperature to storage time. Below 0 °C, infectious waste may be stored far longer than at 3 to 8 °C, so the breakdown that night changes the collection date.

    Scope

    This chapter covers solid hospital medical waste from the building technician’s side: waste types and segregation, container colors, sharps and infectious waste, trolleys and their routes, the temporary storage facility and storage time limits, and autoclaves and incinerators from the infrastructure and records side. PP 28/2024 (Government Regulation) requires medical waste to be managed with environmentally friendly technology and personal protective equipment, at a location not close to service activities and residential areas, with equipment and facilities that meet the standard. The detailed technical requirements are set out in the annexes of Permenkes (Minister of Health Regulation) 2/2023 and Permenkes 7/2019. As of November 2026, Article 99 of Permenkes 3/2026 revokes both regulations except for several articles together with their annexes, and revokes Permenkes 18/2020 on region-based medical waste management except for Articles 8, 11, and 17 together with its annexes; the Ministry of Health legal database (JDIH Kemenkes) records all three as no longer in force, so check the latest status with the hospital’s environmental health unit. WHO guidance is used for practices the regulations do not detail.

    Standard precautions and sharps are covered in Chapter 11 · Biology & Microbiology on the chain of infection and standard precautions for technicians, sterilization and its verification in Chapter 22 · Biology & Microbiology on sterilization, and hospital wastewater in Chapter 17 · Laundry on laundry wastewater and the IPAL and Chapter 16 on wastewater characteristics. Nonmedical B3 waste such as oil, lamps, and batteries is covered in Chapter 35 on B3 waste in hotels, laundries, and workshops. Clinical action and segregation by health workers in the wards are not covered.

    Work outside the building technician’s authority: operating, opening the door of, loading, or changing the settings of waste autoclaves and incinerators; moving or opening bags of infectious waste; handling radioactive waste; managing exposures and needlestick injuries clinically; cleaning up spills of blood, cytotoxic material, or mercury; and transporting waste off the hospital site. That work belongs to the waste staff and the environmental health unit, licensed treatment operators, radiation protection officers, the infection prevention and control team, and licensed transporters. The building technician maintains the infrastructure: refrigeration units, lights, fans, drains, locks, trolleys, and the utilities of the treatment equipment, under a work permit and after the area has been decontaminated.

    Hospital waste types and segregation

    Most hospital waste is not hazardous. WHO notes that 75 to 90 percent of the waste from health care facilities is comparable to domestic waste and comes from administration, kitchens, and housekeeping, while the remaining 10 to 25 percent is hazardous. That figure explains why segregation matters. Every bag of general waste mixed with infectious waste has to be treated as infectious waste, so the treatment load and its cost rise.

    Medical waste is the waste discharged from the medical activities of health services. The annex of Permenkes 2/2023 divides B3 waste from health care facilities into infectious, pathological, sharps, expired chemicals or spills or packaging residue, radioactive, pharmaceutical, cytotoxic, medical equipment containing heavy metals, and pressurized cylinders or containers. Infectious waste includes blood and body fluids, laboratory waste that is infectious, waste from isolation activities, and waste from activities using test animals. Pathological waste comes from body parts, organs, and tissues of humans and animals.

    Segregation runs from the source to the temporary storage facility, between B3 waste, non-B3 waste, and general waste, by placing waste in containers lined with plastic bags whose color and symbol match the type of waste. Segregation at the source is the work of health workers. The building technician’s role is to make sure the containers, lids, and their stands are available and working, because a damaged or full container leads people to put waste into the wrong one.

    Container color codes and symbols

    A container color code is the rule for the colors of bags and containers that shows the type of waste inside. The following table sets the color codes in Table 27 of the annex of Permenkes 2/2023 beside the scheme WHO recommends for countries without national rules, plus WHO’s grouping of chemical waste.

    Waste typePermenkes 2/2023WHO scheme
    Infectiousyellow, biohazard symbol, strong leak-proof plastic bag or containeryellow, biohazard symbol; highly infectious waste marked “HIGHLY INFECTIOUS” in a strong leak-proof bag or a container that can be autoclaved
    Pathologicalyellow, biohazard symbolyellow, biohazard symbol
    Sharpsyellow, biohazard symbol, strong leak-proof containeryellow, marked “SHARPS,” biohazard symbol, puncture-proof container
    Expired chemicals, spills, packaging residuebrownbrown, labeled with the appropriate hazard symbol
    Pharmaceuticalbrownbrown (grouped with chemical)
    Cytotoxicpurple, dividing cell symbolnot separated in the WHO table
    Heavy metalsbrown, strong leak-proof plastic containerincluded in chemical waste
    Radioactivered, lead box, radioactive symbollabeled with the radiation symbol, lead box
    General wastenot in the tableblack

    The differences that matter most for staff in Indonesia are purple for cytotoxic waste and red for radioactive waste. A technician who finds a red container or a radiation symbol in the ordinary waste stream does not touch it and calls the radiation protection officer. Permenkes 7/2019 sets the radioactive, infectious, and cytotoxic symbols for their respective packaging. WHO recommends that every filled container be given a label stating the area of origin, the date and time the container was closed, and the name of the person filling in the label, so that segregation problems can be traced back to the room they came from.

    Sharps and infectious waste

    Sharps waste is waste that can pierce or cut and has been in contact with an infectious agent, for example needles, lancets, syringes, microscope slides, scalpels, knives, and glass. WHO regards sharps as highly hazardous and treats them as if they were infected, whether or not they are. The hazard reaches everyone along the waste route, including the technician who repairs a door or a rack in the storage facility.

    WHO calls for waste bags and sharps containers to be filled to no more than three quarters. The annex of Permenkes 2/2023 states that waste is collected from the source once the bag is three quarters of its maximum volume or after 1 day (24 hours) at most. Bags are closed or tied firmly in a single braid, tying in the “rabbit ear” style is prohibited, and every bag that is removed is immediately replaced with a new one. WHO also prohibits stapling plastic bags. Both limits, three quarters and 24 hours, apply together: a bag that is not yet three quarters full is still collected every day.

    The three-quarter limit leaves room for the bag to be tied without pressing on its contents and keeps needles from piercing the container wall near the top. A full container is not pressed down to make room for more. If a sharp item can be seen sticking out of a bag or container, the technician does not push it back in and does not lift that bag; sharps are never picked up by hand, but with a brush and dustpan or another suitable tool.

    Accidents and incidents, including near misses, spills, damaged containers, incorrect segregation, and any incident involving sharps, are reported to the waste management officer or another designated person. A needlestick report is urgent. WHO writes that post-exposure prophylaxis for HIV is started as soon as possible within the first few hours and no later than 72 hours after exposure to potentially infected blood or body fluids. The assessment and treatment are a matter for health workers; the technician’s part is to report without delay (Chapter 11 · Biology & Microbiology on the chain of infection and standard precautions for technicians).

    Internal transport

    B3 waste trolleys are made of strong, fairly light, watertight, rust-resistant material, fitted with a lid and wheels, kept in the temporary storage facility, marked with the words B3 waste and its symbol on the front wall, and cleaned periodically. Transport from the source room to the storage facility uses a dedicated route not used by many people or goods, or takes place after service hours or when visitors are few, by trained staff wearing adequate clothing and personal protective equipment. For small facilities where a trolley cannot be used, the annex allows manual transport while still ensuring safety.

    WHO gives some additional guidance for hospitals. Hazardous and non-hazardous waste are always transported separately. General waste trolleys are painted black, infectious waste trolleys are yellow, and chemical and pharmaceutical waste is transported separately in boxes. The waste route follows the principle “from clean to dirty,” starting from the most sensitive areas such as intensive care, dialysis, and operating rooms. Infectious waste is collected at least daily. Waste chutes are not recommended because they can increase the risk of airborne transmission.

    For trolleys, WHO calls for trolleys that are easy to load and unload, have no sharp edges, are easy to clean, are dedicated to one type of waste, are not so high that they block the view of the person pushing, can be locked for hazardous waste, and are cleaned and disinfected daily. For the building technician, the route requirements mean that the doors, ramps, and service elevators used by trolleys must be kept in good repair. An elevator that often jams leads staff to take the patient route or carry bags by hand.

    Temporary storage facility and storage time limits

    A B3 waste temporary storage facility (B3 waste TPS, from the Indonesian tempat penyimpanan sementara) is an enclosed building where waste is stored before it is transported or treated. The annex of Permenkes 2/2023 requires the TPS to be in the service area, free from flooding, and not close to service activities and residential areas, as an enclosed building with a door, adequate ventilation, an exhaust fan, a drain to a control pit or the wastewater management system, and vehicle access. The building is divided into rooms for infectious waste, liquid noninfectious waste, and solid noninfectious waste, and fitted with a fence, padlock, outdoor lighting, emergency telephone numbers, a name sign, a no-entry sign, standard operating procedures (SPO), and a logbook. For infectious waste, WHO adds that the storage place is marked with the biohazard sign, its floors and walls are sealed or tiled for easy disinfection, and untreated infectious waste must not be compacted. The TPS is also covered in Chapter 35 on B3 waste in hotels, laundries, and workshops.

    The storage time limit for medical waste depends on temperature. The annex of Permenkes 2/2023 sets two provisions for infectious, pathological, and sharps waste:

    TPS temperatureMaximum storage time
    equal to or less than 0 °Cup to 90 days
    3 to 8 °Cup to 7 days

    For other B3 waste in the hospital, such as expired chemicals, pharmaceuticals, cytotoxic waste, equipment with a high heavy metal content, and pressurized cylinders, the storage time limit is at most 90 days if 50 kg per day or more is generated, and 180 days for category 1 waste if less than 50 kg per day, counted from the date the waste is generated. The temperature table does not cover the range above 0 °C and below 3 °C, and there is no provision for temperatures above 8 °C. Storage at a temperature not listed is checked with the environmental health unit, not interpreted by oneself. As a comparison, WHO writes that without a refrigerated room, infectious waste in a warm climate is not stored for more than 48 hours in the cool season and 24 hours in the hot season.

    The deadline is counted from the date the oldest bag entered:

    tremaining=T−(tnow−tin)t_{remaining} = T - (t_{now} - t_{in})

    where tremainingt_{remaining} is the remaining storage time (days), TT is the storage time limit for the temperature condition currently in effect (days), tnowt_{now} is today’s date, and tint_{in} is the date the oldest bag entered. This chapter uses the most cautious method: if the room temperature moves to a condition with a shorter storage time limit, the age of the bag is still counted from the first day it entered, not from when the temperature changed. The TPS cold room is therefore a critical utility. The technician monitors and records its temperature, checks the alarm, door seals, condensate drain, and backup power supply, and reports immediately if the temperature goes outside its set range.

    Treatment by autoclave and incinerator from the infrastructure side

    Medical waste treatment inside the hospital uses an incinerator or other equipment such as an autoclave, microwave, burial, encapsulation, and inertization that has an operating permit, or is done off site in cooperation with a licensed processor. Permenkes 7/2019 judges non-incineration technology such as an autoclave with a shredder to be more environmentally friendly because it produces no gas emissions.

    Permenkes 3/2026 adds that pathological waste and sharps may be buried if no treatment facility is available in the region or in an emergency or disaster, with the technical details following the regulations. For the building technician, that provision means no waste burial pit is dug in the hospital grounds without a decision by the management and a clear regulatory basis.

    A waste autoclave is a pressure vessel that uses saturated steam to disinfect infectious waste. WHO notes that a minimum criterion of 121 °C for 30 minutes, corresponding to a pressure of 205 kPa, was recommended in the past, but steam penetration depends on many factors, such as load size, stacking, packing density, type of bag, and residual air, so the temperature, pressure, and time are set by challenge tests with representative waste. After that, validation tests with biological indicators are performed periodically, chemical indicators are attached to every load, and every cycle is recorded: date, time, operator name, type and approximate amount of waste, and the indicator result. Volatile organic compounds, chemotherapy waste, mercury, other hazardous chemical waste, and radioactive waste are not treated in an autoclave. The principles of steam sterilization and its indicators are covered in Chapter 22 · Biology & Microbiology on sterilization.

    A waste incinerator is a furnace designed and permitted for burning medical waste. A hospital that treats its own waste by incineration must have equipment with a capacity matching the waste volume, two combustion chambers with the first chamber at least 800 °C and the second chamber at least 1,000 °C with a residence time of 2 seconds, a stack at least 14 m above the ground with an emission sampling port, and air pollution control equipment. That incinerator must not burn radioactive waste, explosive waste, or mercury and other heavy metal waste. Ash residue from incineration is treated as B3 waste, and pressurized containers must not be incinerated because they can explode.

    For the building technician, autoclaves and incinerators are utility customers: steam, water, electricity, compressed air, ventilation, and drains. Work on those utilities is done under a work permit and with energy isolation agreed with the operator (Chapter 76 · Electrical & Control on safe work). The technician may read the temperature and cycle records to recognize utility faults, but does not run cycles, does not open the vessel door or the combustion chamber, and does not change settings. When the treatment equipment fails, Permenkes 7/2019 calls for the hospital to use emergency arrangements with licensed transporters and processors.

    Third parties and records

    A hospital that sends its waste off site for treatment works with a licensed transporter and processor under one three-party memorandum of agreement, makes sure both permits match the type of waste, and sends a B3 waste manifest with every shipment, signed by all three parties and archived by the hospital. A B3 waste report is submitted at least once every three months. Balances and manifests are covered in more detail in Chapter 35 on B3 waste in hotels, laundries, and workshops. The temperature records of the TPS cold room and the maintenance records of its refrigeration unit are kept with the waste logbook as evidence of the storage conditions.

    Worked example

    The figures in the examples below are practice figures, unless their origin is stated.

    Example 1: remaining storage time after the refrigeration fails. The oldest bag enters the TPS cold room on day 0, a Monday. On day 5, Saturday night, the refrigeration unit fails and the room temperature holds at 5 °C. While the room is below 0 °C, the remaining time is tremaining=90−5=85t_{remaining} = 90 - 5 = 85 days. At 3 to 8 °C, the storage time limit is 7 days, so with the cautious method tremaining=7−5=2t_{remaining} = 7 - 5 = 2 days, that is, until day 7, Monday. The Wednesday collection falls on day 9, 9−7=29 - 7 = 2 days late. The technician repairs the unit, while the environmental health unit asks for the collection to be brought forward.

    Example 2: yellow bags needed per day. Wards with 120 occupied beds generate 0.5 kg of infectious waste per bed per day, or 120×0.5=60120 \times 0.5 = 60 kg/day. A 60 L bag holds about 6 kg when full, so at three quarters it holds 0.75×6=4.50.75 \times 6 = 4.5 kg. By weight, 60/4.5=13.360/4.5 = 13.3 bags are needed, rounded up to 14. But there are 20 collection points that must be collected at least every 24 hours, so at least 20 bags per day are needed, plus spares at each point.

    Example 3: when to replace a sharps container. A 5 L sharps container is filled to three quarters, or 0.75×5=3.750.75 \times 5 = 3.75 L. If one syringe with needle takes up about 0.025 L, the container holds 3.75/0.025=1503.75/0.025 = 150 items. A ward that uses 60 syringes per day fills it in 150/60=2.5150/60 = 2.5 days, so the container is replaced every 2 days, not when it looks full.

    Example 4: cold room capacity. A cold room with inside dimensions of 2.0 m by 1.5 m by 2.2 m has a volume of 2.0×1.5×2.2=6.62.0 \times 1.5 \times 2.2 = 6.6 m³. If only half of it can be filled with racks and bags, the usable volume is 0.5×6.6=3.30.5 \times 6.6 = 3.3 m³. With a bagged waste density of 100 kg/m³, the room holds 3.3×100=3303.3 \times 100 = 330 kg, or 330/60=5.5330/60 = 5.5 days of the generation in Example 2. Although the temperature rule below 0 °C allows 90 days, the room capacity limits collection to at most every 5 days.

    Example 5: number of trolley trips. A yellow trolley carries 8 bags filled to three quarters, or 8×4.5=368 \times 4.5 = 36 kg. For 60 kg/day, 60/36=1.6760/36 = 1.67 trips are needed, rounded up to 2 trips per day. The first trip starts from intensive care and the operating rooms, then goes to the general wards, following the principle from clean to dirty.

    Example 6: reading the treatment records. The hospital has set from its challenge tests that an autoclave cycle must reach 121 °C for 30 minutes. The records show load A at 121 °C for 32 minutes with the indicator changed, load B at 118 °C for 30 minutes, and load C at 121 °C for 22 minutes. Load B is short by 121−118=3121 - 118 = 3 °C and load C is short by 30−22=830 - 22 = 8 minutes, so both are reported to the operator as loads that have not met the cycle. In the incinerator records, the second combustion chamber is recorded at 960 °C, short by 1,000−960=401{,}000 - 960 = 40 °C, or 40/1,000=440/1{,}000 = 4 percent below the requirement of at least 1,000 °C. The technician reports the finding and does not change the settings.

    Stop conditions

    1. A sharp item is sticking out of a bag or container, or a sharps container is more than three quarters full, torn, or punctured: do not push, press, or lift it; secure the spot and call the waste staff or the environmental health unit.
    2. The technician has had a needlestick or a splash of blood or body fluid: stop the work, give first aid according to the hospital procedure, and report immediately to the designated person for post-exposure follow-up.
    3. The TPS cold room temperature is outside its set range, or the storage time limit of the oldest bag is about to be exceeded: report immediately to the environmental health unit for collection by a licensed transporter; the technician repairs the unit but does not move or open the waste bags.
    4. A bag is leaking, or there is a spill of blood, cytotoxic material, or mercury: secure the area and do not clean it up yourself; hand it over to trained staff with a spill kit.
    5. A red container, a lead box, or a radiation symbol is found in the ordinary waste stream: do not touch or move it; call the radiation protection officer.
    6. The technician is asked to run, open the door of, load, or change the settings of a waste autoclave or incinerator, or to enter its combustion chamber or vessel: refuse; that work belongs to the licensed operator and the equipment vendor.
    7. The transporter cannot show a permit matching the type of waste, the vehicle does not match the permit, or the manifest has not been filled in: do not hand over the waste; report to the environmental health unit.
    8. A repair is needed inside the TPS, on a trolley, or on a contaminated drain: stop until the area or equipment has been decontaminated by authorized staff and a work permit has been issued.

    Common misinterpretations

    Guess what’s wrong first, then open the explanation.

    Common misconception

    All hospital waste is infectious.

    Why is it wrong?

    According to WHO, most of the waste from health care facilities is comparable to domestic waste. Mixing it with infectious waste only increases the amount of waste that needs special treatment.

    Common misconception

    A yellow bag may be filled to the top as long as it can still be tied.

    Why is it wrong?

    Bags are collected when three quarters full or after 24 hours at most. An overfilled bag is hard to tie and easily pierced by needles.

    Common misconception

    As long as the room is cold, waste may be stored for any length of time.

    Why is it wrong?

    The storage time limit depends on the temperature: up to 90 days at 0 °C or less and up to 7 days at 3 to 8 °C. A room that is merely cool does not give 90 days.

    Common misconception

    An autoclave can treat all medical waste.

    Why is it wrong?

    An autoclave is not used for volatile chemical waste, chemotherapy waste, mercury, or radioactive waste. Such waste is separated before loading and sent to suitable treatment.

    Common misconception

    Incinerator ash is already safe and may go into general waste.

    Why is it wrong?

    Ash residue from incineration is treated as B3 waste. It is stored and handed over like other B3 waste.

    Chapter 11 · Biology & Microbiology on the chain of infection and standard precautions for technicians explains how to work safely near blood, body fluids, and sharps. Chapter 22 · Biology & Microbiology on sterilization explains the moist heat principles and indicators used by autoclaves. Chapter 35 on B3 waste in hotels, laundries, and workshops covers the TPS, balances, manifests, and spills in general. Hospital wastewater is covered in Chapter 17 · Laundry on laundry wastewater and the IPAL and Chapter 16 on wastewater characteristics, and work permits for repairs to treatment utilities in Chapter 76 · Electrical & Control on safe work.

    Exercises and worked solutions

    The figures in the exercises are for practice.

    Try to answer first, then open the worked solution.

    1. The TPS cold room is below 0 °C, and the oldest bag is already 40 days old. How much storage time remains, and what changes if the refrigeration fails and the temperature becomes 6 °C?

      Check my answer
      See the worked solution

      The remaining storage time is 90−40=5090 - 40 = 50 days as long as the room stays below 0 °C. If the temperature becomes 6 °C, the 7-day storage time limit applies, and a bag that is already 40 days old is far past it, so the waste must be collected by a licensed transporter immediately and the environmental health unit informed.

    2. A small hospital generates 45 kg of infectious waste per day from 14 collection points, with bags holding 4.5 kg at three quarters full. How many bags are needed per day?

      Check my answer
      See the worked solution

      By weight, 45/4.5=1045/4.5 = 10 bags per day are needed. Because the 14 collection points are collected at least every 24 hours, at least 14 bags are needed, plus spares at each point.

    3. A trolley worker reports a needle sticking out of a yellow bag on a trolley about to enter the elevator. What does a technician nearby do?

      Check my answer
      See the worked solution

      The technician does not push the needle back in and does not lift the bag, because sharps are never picked up by hand. The trolley is held outside the elevator, the area is secured, and the waste staff are called to handle the bag with a suitable tool.

    4. A 7 L sharps container is filled to three quarters, one syringe takes up about 0.035 L, and 50 syringes are used per day. When is the container replaced?

      Check my answer
      See the worked solution

      The usable volume of the container is 0.75×7=5.250.75 \times 7 = 5.25 L, so it holds 5.25/0.035=1505.25/0.035 = 150 syringes. At 50 syringes per day the container fills in 3 days, so it is replaced at least every 3 days.

    5. A broken mercury thermometer is found inside a yellow bag about to be loaded into the autoclave. Why must the process be stopped?

      Check my answer
      See the worked solution

      Mercury must not be treated in an autoclave because it would vaporize and contaminate the air and the treated waste, and the incinerator is also prohibited from burning mercury waste. The bag is separated by trained staff and handed over as heavy metal waste to a licensed processor.

    6. The incinerator records show the first combustion chamber at 780 °C. How does the technician assess it?

      Check my answer
      See the worked solution

      The requirement is at least 800 °C, so 780 °C is short by 20 °C, or 2.5 percent below the requirement. The technician reports the finding to the operator and the environmental health unit and does not change the settings, because operating the incinerator is the authority of the licensed operator.

    References

    External sources

    • Peraturan Menteri Kesehatan Nomor 2 Tahun 2023 tentang Peraturan Pelaksanaan Peraturan Pemerintah Nomor 66 Tahun 2014 tentang Kesehatan Lingkunganjdih.kemkes.go.id
    • Peraturan Menteri Kesehatan Nomor 7 Tahun 2019 tentang Kesehatan Lingkungan Rumah Sakitjdih.kemkes.go.id
    • Peraturan Menteri Kesehatan Nomor 3 Tahun 2026 tentang Penanggulangan Penyakitjdih.kemkes.go.id
    • Peraturan Pemerintah Nomor 28 Tahun 2024 tentang Peraturan Pelaksanaan Undang-Undang Nomor 17 Tahun 2023 tentang Kesehatanjdih.kemkes.go.id
    • Safe management of wastes from health-care activitiesiris.who.int

    Revision history

    DateVersionChange
    November 11, 20261First published

    How to cite

    Kurnia (2026). Hospital medical waste: waste types and segregation, container color codes, sharps and infectious waste, internal transport and storage, treatment by autoclave and incinerator, and the limits of the work. ARSTEMA Academy. Revised November 11, 2026. arstema.com/en/academy/konsep/limbah-medis-rumah-sakit-jenis-limbah-dan-pemilahan-kode-warna-wadah-limbah-tajam-dan-infeksius-pengangkutan-internal-dan-penyimpanan-pengolahan-dengan-autoklaf-dan-insinerator-serta-batas-pekerjaan

    Self-check · 3 questions

    Check your understanding before moving on

    Write your answer in your own words, then compare it with the worked solution from this chapter’s exercises. The system doesn’t judge open answers as right or wrong; you decide which parts you’ve understood.

    0/3rated

    Safety limits still apply. This quiz tests reasoning; it doesn’t authorize mixing, adjusting, dismantling, live measurement, or field action.

    1

    The TPS cold room is below 0 °C, and the oldest bag is already 40 days old. How much storage time remains, and what changes if the refrigeration fails and the temperature becomes 6 °C?

    2

    A small hospital generates 45 kg of infectious waste per day from 14 collection points, with bags holding 4.5 kg at three quarters full. How many bags are needed per day?

    3

    A trolley worker reports a needle sticking out of a yellow bag on a trolley about to enter the elevator. What does a technician nearby do?

    Self-assessment progress0%